State and Local Government Facilities:
Guidance on the Revisions to 28 CFR 35.151
Guidance on the Revisions to 28 CFR 35.151
Section 35.151(a), which provided that those facilities that are constructed
or altered by, on behalf of, or for the use of a public entity shall be
designed, constructed, or altered to be readily accessible to and usable by
individuals with disabilities, is unchanged in the final rule, but has been
redesignated as Sec. 35.151(a)(1). The Department has added a new section,
designated as Sec. 35.151(a)(2), to provide that full compliance with the
requirements of this section is not required where an entity can demonstrate
that it is structurally impracticable to meet the requirements. Full
compliance will be considered structurally impracticable only in those rare
circumstances when the unique characteristics of terrain prevent the
incorporation of accessibility features. This exception was contained in the
title III regulation and in the 1991 Standards (applicable to both public
accommodations and facilities used by public entities), so it has applied to
any covered facility that was constructed under the 1991 Standards since the
effective date of the ADA. The Department added it to the text of Sec. 35.151
to maintain consistency between the design requirements that apply under title
II and those that apply under title III. The Department received no
significant comments about this section.
§ 35.151(b) Alterations
The 1991 title II regulation does not contain any specific regulatory language
comparable to the 1991 title III regulation relating to alterations and path
of travel for covered entities, although the 1991 Standards describe standards
for path of travel during alterations to a primary function. See 28 CFR part
36, app A., section 4.1.6(a) (2009). The path of travel requirements contained
in the title III regulation are based on section 303(a)(2) of the ADA, 42
U.S.C. 12183(a)(2), which provides that when an entity undertakes an
alteration to a place of public accommodation or commercial facility that
affects or could affect the usability of or access to an area that contains a
primary function, the entity shall ensure that, to the maximum extent
feasible, the path of travel to the altered area--and the restrooms,
telephones, and drinking fountains serving it--is readily accessible to and
usable by individuals with disabilities, including individuals who use
wheelchairs. The NPRM proposed amending Sec. 35.151 to add both the path of
travel requirements and the exemption relating to barrier removal (as modified
to apply to the program accessibility standard in title II) that are contained
in the title III regulation to the title II regulation. Proposed Sec.
35.151(b)(4) contained the requirements for path of travel. Proposed Sec.
35.151(b)(2) stated that the path of travel requirements of Sec. 35.151(b)(4)
shall not apply to measures taken solely to comply with program accessibility
requirements. Where the specific requirements for path of travel apply under
title III, they are limited to the extent that the cost and scope of
alterations to the path of travel are disproportionate to the cost of the
overall alteration, as determined under criteria established by the Attorney
General. The Access Board included the path of travel requirement for
alterations to facilities covered by the standards (other than those subject
to the residential facilities standards) in section 202.4 of 2004 ADAAG.
Section 35.151(b)(4)(iii) of the final rule establishes the criteria for
determining when the cost of alterations to the path of travel is
“disproportionate” to the cost of the overall alteration. The NPRM also
provided that areas such as supply storage rooms, employee lounges and locker
rooms, janitorial closets, entrances, and corridors are not areas containing a
primary function. Nor are restroom areas considered to contain a primary
function unless the provision of restrooms is a primary purpose of the
facility, such as at a highway rest stop. In that situation, a restroom would
be considered to be an “area containing a primary function” of the facility.
The Department is not changing the requirements for program accessibility. As
provided in Sec. 35.151(b)(2) of the regulation, the path of travel
requirements of Sec. 35.151(b)(4) only apply to alterations undertaken solely
for purposes other than to meet the program accessibility requirements. The
exemption for the specific path of travel requirement was included in the
regulation to ensure that the specific requirements and disproportionality
exceptions for path of travel are not applied when areas are being altered to
meet the title II program accessibility requirements in Sec. 35.150. In
contrast, when areas are being altered to meet program accessibility
requirements, they must comply with all of the applicable requirements
referenced in section 202 of the 2010 Standards. A covered title II entity
must provide accessibility to meet the requirements of Sec. 35.150 unless
doing so is an undue financial and administrative burden in accordance with
Sec. 35.150(a)(3). A covered title II entity may not use the
disproportionality exception contained in the path of travel provisions as a
defense to providing an accessible route as part of its obligation to provide
program accessibility. The undue financial and administrative burden standard
does not contain any bright line financial tests. The Department's proposed
Sec. 35.151(b)(4) adopted the language now contained in Sec. 36.403 of the
title III regulation, including the disproportionality limitation (i.e.,
alterations made to provide an accessible path of travel to the altered area
would be deemed disproportionate to the overall alteration when the cost
exceeds 20 percent of the cost of the alteration to the primary function
area). Proposed Sec. 35.151(b)(2) provided that the path of travel
requirements do not apply to alterations undertaken solely to comply with
program accessibility requirements. The Department received a substantial
number of comments objecting to the Department's adoption of the exemption for
the path of travel requirements when alterations are undertaken solely to meet
program accessibility requirements. These commenters argued that the
Department had no statutory basis for providing this exemption nor does it
serve any purpose. In addition, these commenters argued that the path of
travel exemption has the effect of placing new limitations on the obligations
to provide program access. A number of commenters argued that doing away with
the path of travel requirement would render meaningless the concept of program
access. They argued that just as the requirement to provide an accessible path
of travel to an altered area (regardless of the reason for the alteration),
including making the restrooms, telephones, and drinking fountains that serve
the altered area accessible, is a necessary requirement in other alterations,
it is equally necessary for alterations made to provide program access.
Several commenters expressed concern that a readily accessible path of travel
be available to ensure that persons with disabilities can get to the physical
location in which programs are held. Otherwise, they will not be able to
access the public entity's service, program, or activity. Such access is a
cornerstone of the protections provided by the ADA. Another commenter argued
that it would be a waste of money to create an accessible facility without
having a way to get to the primary area. This commenter also stated that the
International Building Code (IBC) requires the path of travel to a primary
function area, up to 20 percent of the cost of the project. Another commenter
opposed the exemption, stating that the trigger of an alteration is frequently
the only time that a facility must update its facilities to comply with
evolving accessibility standards. In the Department's view, the commenters
objecting to the path of travel exemption contained in Sec. 35.151(b)(2) did
not understand the intention behind the exemption. The exemption was not
intended to eliminate any existing requirements related to accessibility for
alterations undertaken in order to meet program access obligations under Sec.
35.149 and Sec. 35.150. Rather, it was intended to ensure that covered
entities did not apply the path of travel requirements in lieu of the
overarching requirements in this Subpart that apply when making a facility
accessible in order to comply with program accessibility. The exemption was
also intended to make it clear that the disproportionality test contained in
the path of travel standards is not applicable in determining whether
providing program access results in an undue financial and administration
burden within the meaning of Sec. 35.150(a)(3). The exemption was also
provided to maintain consistency with the title III path of travel exemption
for barrier removal, see Sec. 36.304(d), in keeping with the Department's
regulatory authority under title II of the ADA. See 42 U.S.C. 12134(b); see
also H. R Rep. No. 101B485, pt. 2, at 84 (1990) (“The committee intends,
however, that the forms of discrimination prohibited by section 202 be
identical to those set out in the applicable provisions of titles I and III of
this legislation.”). For title II entities, the path of travel requirements
are of significance in those cases where an alteration is being made solely
for reasons other than program accessibility. For example, a public entity
might have six courtrooms in two existing buildings and might determine that
only three of those courtrooms and the public use and common use areas serving
those courtrooms in one building are needed to be made accessible in order to
satisfy its program access obligations. When the public entity makes those
courtrooms and the public use and common use areas serving them accessible in
order to meet its program access obligations, it will have to comply with the
2010 Standards unless the public entity can demonstrate that full compliance
would result in undue financial and administrative burdens as described in
Sec. 35.150(a)(3). If such action would result in an undue financial or
administrative burden, the public entity would nevertheless be required to
take some other action that would not result in such an alteration or such
burdens but would ensure that the benefits and services provided by the public
entity are readily accessible to persons with disabilities. When the public
entity is making modifications to meet its program access obligation, it may
not rely on the path of travel exception under Sec. 35.151(b)(4), which limits
the requirement to those alterations where the cost and scope of the
alterations are not disproportionate to the cost and scope of the overall
alterations. If the public entity later decides to alter courtrooms in the
other building, for purposes of updating the facility (and, as previously
stated, has met its program access obligations) then in that case, the public
entity would have to comply with the path of travel requirements in the 2010
Standards subject to the disproportionality exception set forth in Sec.
35.151(b)(4). The Department has slightly revised proposed Sec. 35.151(b)(2)
to make it clearer that the path of travel requirements only apply when
alterations are undertaken solely for purposes other than program
accessibility.
§ 35.151(b)(4)(ii)(C) Path of travel--safe harbor
In Sec. 35.151(b)(4)(ii)(C) of the NPRM, the Department included a provision
that stated that public entities that have brought required elements of path
of travel into compliance with the 1991 Standards are not required to retrofit
those elements in order to reflect incremental changes in the 2010 Standards
solely because of an alteration to a primary function area that is served by
that path of travel. In these circumstances, the public entity is entitled to
a safe harbor and is only required to modify elements to comply with the 2010
Standards if the public entity is planning an alteration to the element. A
substantial number of commenters objected to the Department's imposition of a
safe harbor for alterations to facilities of public entities that comply with
the 1991 Standards. These commenters argued that if a public entity is already
in the process of altering its facility, there should be a legal requirement
that individuals with disabilities be entitled to increased accessibility by
using the 2010 Standards for path of travel work. They also stated that they
did not believe there was a statutory basis for “grandfathering” facilities
that comply with the 1991 Standards. The ADA is silent on the issue of
“grandfathering” or establishing a safe harbor for measuring compliance in
situations where the covered entity is not undertaking a planned alteration to
specific building elements. The ADA delegates to the Attorney General the
responsibility for issuing regulations that define the parameters of covered
entities' obligations when the statute does not directly address an issue.
This regulation implements that delegation of authority. One commenter
proposed that a previous record of barrier removal be one of the factors in
determining, prospectively, what renders a facility, when viewed in its
entirety, usable and accessible to persons with disabilities. Another
commenter asked the Department to clarify, at a minimum, that to the extent
compliance with the 1991 Standards does not provide program access,
particularly with regard to areas not specifically addressed in the 1991
Standards, the safe harbor will not operate to relieve an entity of its
obligations to provide program access. One commenter supported the proposal to
add a safe harbor for path of travel. The final rule retains the safe harbor
for required elements of a path of travel to altered primary function areas
for public entities that have already complied with the 1991 Standards with
respect to those required elements. The Department believes that this safe
harbor strikes an appropriate balance between ensuring that individuals with
disabilities are provided access to buildings and facilities and potential
financial burdens on existing public entities that are undertaking alterations
subject to the 2010 Standards. This safe harbor is not a blanket exemption for
facilities. If a public entity undertakes an alteration to a primary function
area, only the required elements of a path of travel to that area that already
comply with the 1991 Standards are subject to the safe harbor. If a public
entity undertakes an alteration to a primary function area and the required
elements of a path of travel to the altered area do not comply with the 1991
Standards, then the public entity must bring those elements into compliance
with the 2010 Standards.
§ 35.151(b)(3) Alterations to historic facilities
The final rule renumbers the requirements for alterations to historic
facilities enumerated in current Sec. 35.151(d)(1) and (2) as Sec.
35.151(b)(3)(i) and (ii). Currently, the regulation provides that alterations
to historic facilities shall comply to the maximum extent feasible with
section 4.1.7 of UFAS or section 4.1.7 of the 1991 Standards. See 28 CFR
35.151(d)(1). Section 35.151(b)(3)(i) of the final rule eliminates the option
of using UFAS for alterations that commence on or after March 15, 2012. The
substantive requirement in current Sec. 35.151(d)(2)--that alternative methods
of access shall be provided pursuant to the requirements of Sec. 35.150 if it
is not feasible to provide physical access to an historic property in a manner
that will not threaten or destroy the historic significance of the building or
facility--is contained in Sec. 35.151(b)(3)(ii).
§ 35.151(c) Accessibility standards for new construction and alterations
Section 35.151(c) of the NPRM proposed to adopt ADA Chapter 1, ADA Chapter 2,
and Chapters 3 through 10 of the Americans with Disabilities Act and
Architectural Barriers Act Guidelines (2004 ADAAG) into the ADA Standards for
Accessible Design (2010 Standards). As the Department has noted, the
development of these standards represents the culmination of a lengthy effort
by the Access Board to update its guidelines, to make the Federal guidelines
consistent to the extent permitted by law, and to harmonize the Federal
requirements with the private sector model codes that form the basis of many
State and local building code requirements. The full text of the 2010
Standards is available for public review on the ADA Home Page
(http://www.ada.gov) and on the Access Board's Web site
(http://www.access-board.gov/gs.htm) (last visited June 24, 2010). The Access
Board site also includes an extensive discussion of the development of the
2004 ADA/ABA Guidelines, and a detailed comparison of the 1991 Standards, the
2004 ADA/ABA Guidelines, and the 2003 International Building Code. Section 204
of the ADA, 42 U.S.C. 12134, directs the Attorney General to issue regulations
to implement title II that are consistent with the minimum guidelines
published by the Access Board. The Attorney General (or his designee) is a
statutory member of the Access Board (see 29 U.S.C. 792(a)(1)(B(vii)) and was
involved in the development of the 2004 ADAAG. Nevertheless, during the
process of drafting the NPRM, the Department reviewed the 2004 ADAAG to
determine if additional regulatory provisions were necessary. As a result of
this review, the Department decided to propose new sections, which were
contained in Sec. 35.151(e)-(h) of the NPRM, to clarify how the Department
will apply the proposed standards to social service center establishments,
housing at places of education, assembly areas, and medical care facilities.
Each of these provisions is discussed below. Congress anticipated that there
would be a need for close coordination of the ADA building requirements with
State and local building code requirements. Therefore, the ADA authorized the
Attorney General to establish an ADA code certification process under title
III of the ADA. That process is addressed in 28 CFR part 36, subpart F.
Revisions to that process are addressed in the regulation amending the title
III regulation published elsewhere in the Federal Register today. In addition,
the Department operates an extensive technical assistance program. The
Department anticipates that once this rule is final, revised technical
assistance material will be issued to provide guidance about its
implementation. Section 35.151(c) of the 1991 title II regulation establishes
two standards for accessible new construction and alteration. Under paragraph
(c), design, construction, or alteration of facilities in conformance with
UFAS or with the 1991 Standards (which, at the time of the publication of the
rule were also referred to as the Americans with Disabilities Act
Accessibility Guidelines for Buildings and Facilities (1991 ADAAG)) is deemed
to comply with the requirements of this section with respect to those
facilities (except that if the 1991 Standards are chosen, the elevator
exemption does not apply). The 1991 Standards were based on the 1991 ADAAG,
which was initially developed by the Access Board as guidelines for the
accessibility of buildings and facilities that are subject to title III. The
Department adopted the 1991 ADAAG as the standards for places of public
accommodation and commercial facilities under title III of the ADA and it was
published as Appendix A to the Department's regulation implementing title III,
56 FR 35592 (July 26, 1991) as amended, 58 FR 17522 (April 5, 1993), and as
further amended, 59 FR 2675 (Jan. 18, 1994), codified at 28 CFR part 36
(2009). Section 35.151(c) of the final rule adopts the 2010 Standards and
establishes the compliance date and triggering events for the application of
those standards to both new construction and alterations. Appendix B of the
final title III rule (Analysis and Commentary on the 2010 ADA Standards for
Accessible Design) (which will be published today elsewhere in this volume and
codified as Appendix B to 28 CFR part 36) provides a description of the major
changes in the 2010 Standards (as compared to the 1991 ADAAG) and a discussion
of the public comments that the Department received on specific sections of
the 2004 ADAAG. A number of commenters asked the Department to revise certain
provisions in the 2004 ADAAG in a manner that would reduce either the required
scoping or specific technical accessibility requirements. As previously
stated, although the ADA requires the enforceable standards issued by the
Department under title II and title III to be consistent with the minimum
guidelines published by the Access Board, it is the sole responsibility of the
Attorney General to promulgate standards and to interpret and enforce those
standards. The guidelines adopted by the Access Board are “minimum
guidelines.” 42 U.S.C. 12186(c).
Compliance date. When the ADA was enacted, the effective dates for
various provisions were delayed in order to provide time for covered entities
to become familiar with their new obligations. Titles II and III of the ADA
generally became effective on January 26, 1992, six months after the
regulations were published. See 42 U.S.C. 12131 note; 42 U.S.C. 12181 note.
New construction under title II and alterations under either title II or title
III had to comply with the design standards on that date. See 42 U.S.C.
12183(a)(1). For new construction under title III, the requirements applied to
facilities designed and constructed for first occupancy after January 26,
1993--18 months after the 1991 Standards were published by the Department. In
the NPRM, the Department proposed to amend Sec. 35.151(c)(1) by revising the
current language to limit the application of the 1991 standards to facilities
on which construction commences within six months of the final rule adopting
revised standards. The NPRM also proposed adding paragraph (c)(2) to Sec.
35.151, which states that facilities on which construction commences on or
after the date six months following the effective date of the final rule shall
comply with the proposed standards adopted by that rule. As a result, under
the NPRM, for the first six months after the effective date, public entities
would have the option to use either UFAS or the 1991 Standards and be in
compliance with title II. Six months after the effective date of the rule, the
new standards would take effect. At that time, construction in accordance with
UFAS would no longer satisfy ADA requirements. The Department stated that in
order to avoid placing the burden of complying with both standards on public
entities, the Department would coordinate a government-wide effort to revise
Federal agencies' section 504 regulations to adopt the 2004 ADAAG as the
standard for new construction and alterations. The purpose of the proposed
six-month delay in requiring compliance with the 2010 Standards was to allow
covered entities a reasonable grace period to transition between the existing
and the proposed standards. For that reason, if a title II entity preferred to
use the 2010 Standards as the standard for new construction or alterations
commenced within the six-month period after the effective date of the final
rule, such entity would be considered in compliance with title II of the ADA.
The Department received a number of comments about the proposed six-month
effective date for the title II regulation that were similar in content to
those received on this issue for the proposed title III regulation. Several
commenters supported the six-month effective date. One commenter stated that
any revisions to its State building code becomes effective six months after
adoption and that this has worked well. In addition, this commenter stated
that since 2004 ADAAG is similar to IBC 2006 and ICC/ANSI A117.1-2003, the
transition should be easy. By contrast, another commenter advocated for a
minimum 12-month effective date, arguing that a shorter effective date could
cause substantial economic hardships to many cities and towns because of the
lengthy lead time necessary for construction projects. This commenter was
concerned that a six-month effective date could lead to projects having to be
completely redrawn, rebid, and rescheduled to ensure compliance with the new
standards. Other commenters advocated that the effective date be extended to
at least 18 months after the publication of the rule. One of these commenters
expressed concern that the kinds of bureaucratic organizations subject to the
title II regulations lack the internal resources to quickly evaluate the
regulatory changes, determine whether they are currently compliant with the
1991 standards, and determine what they have to do to comply with the new
standards. The other commenter argued that 18 months is the minimum amount of
time necessary to ensure that projects that have already been designed and
approved do not have to undergo costly design revisions at taxpayer expense.
The Department is persuaded by the concerns raised by commenters for both the
title II and III regulations that the six-month compliance date proposed in
the NPRM for application of the 2010 Standards may be too short for certain
projects that are already in the midst of the design and permitting process.
The Department has determined that for new construction and alterations,
compliance with the 2010 Standards will not be required until 18 months from
the date the final rule is published. Until the time compliance with the 2010
Standards is required, public entities will have the option of complying with
the 2010 Standards, the UFAS, or the 1991 Standards. However, public entities
that choose to comply with the 2010 Standards in lieu of the 1991 Standards or
UFAS prior to the compliance date described in this rule must choose one of
the three standards, and may not rely on some of the requirements contained in
one standard and some of the requirements contained in the other standards.
Triggering event. In Sec. 35.151(c)(2) of the NPRM, the Department
proposed that the commencement of construction serve as the triggering event
for applying the proposed standards to new construction and alterations under
title II. This language is consistent with the triggering event set forth in
Sec. 35.151(a) of the 1991 title II regulation. The Department received only
four comments on this section of the title II rule. Three commenters supported
the use of “start of construction” as the triggering event. One commenter
argued that the Department should use the “last building permit or start of
physical construction, whichever comes first,” stating that “altering a design
after a building permit has been issued can be an undue burden.” After
considering these comments, the Department has decided to continue to use the
commencement of physical construction as the triggering event for application
of the 2010 Standards for entities covered by title II. The Department has
also added clarifying language at Sec. 35.151(c)(4) to the regulation to make
it clear that the date of ceremonial groundbreaking or the date a structure is
razed to make it possible for construction of a facility to take place does
not qualify as the commencement of physical construction. Section 234 of the
2010 Standards provides accessibility guidelines for newly designed and
constructed amusement rides. The amusement ride provisions do not provide a
“triggering event” for new construction or alteration of an amusement ride. An
industry commenter requested that the triggering event of “first use,” as
noted in the Advisory note to section 234.1 of the 2004 ADAAG, be included in
the final rule. The Advisory note provides that “[a] custom designed and
constructed ride is new upon its first use, which is the first time amusement
park patrons take the ride.” The Department declines to treat amusement rides
differently than other types of new construction and alterations. Under the
final rule, they are subject to Sec. 35.151(c). Thus, newly constructed and
altered amusement rides shall comply with the 2010 Standards if the start of
physical construction or the alteration is on or after 18 months from the
publication date of this rule. The Department also notes that section 234.4.2
of the 2010 Standards only applies where the structural or operational
characteristics of an amusement ride are altered. It does not apply in cases
where the only change to a ride is the theme.
Noncomplying new construction and alterations. The element-by-
element safe harbor referenced in Sec. 35.150(b)(2) has no effect on new or
altered elements in existing facilities that were subject to the 1991
Standards or UFAS on the date that they were constructed or altered, but do
not comply with the technical and scoping specifications for those elements in
the 1991 Standards or UFAS. Section 35.151(c)(5) of the final rule sets forth
the rules for noncompliant new construction or alterations in facilities that
were subject to the requirements of this part. Under those provisions,
noncomplying new construction and alterations constructed or altered after the
effective date of the applicable ADA requirements and before March 15, 2012
shall, before March 15, 2012, be made accessible in accordance with either the
1991 Standards, UFAS, or the 2010 Standards. Noncomplying new construction and
alterations constructed or altered after the effective date of the applicable
ADA requirements and before March 15, 2012, shall, on or after March 15, 2012
be made accessible in accordance with the 2010 Standards.
§ 35.151(d) Scope of coverage
In the NPRM, the Department proposed a new provision, Sec. 35.151(d), to
clarify that the requirements established by Sec. 35.151, including those
contained in the 2004 ADAAG, prescribe what is necessary to ensure that
buildings and facilities, including fixed or built-in elements in new or
altered facilities, are accessible to individuals with disabilities. Once the
construction or alteration of a facility has been completed, all other aspects
of programs, services, and activities conducted in that facility are subject
to the operational requirements established in this final rule. Although the
Department may use the requirements of the 2010 Standards as a guide to
determining when and how to make equipment and furnishings accessible, those
determinations fall within the discretionary authority of the Department. The
Department also wishes to clarify that the advisory notes, appendix notes, and
figures that accompany the 1991 and 2010 Standards do not establish separately
enforceable requirements unless specifically stated otherwise in the text of
the standards. This clarification has been made to address concerns expressed
by ANPRM commenters who mistakenly believed that the advisory notes in the
2004 ADAAG established requirements beyond those established in the text of
the guidelines (e.g., Advisory 504.4 suggests, but does not require, that
covered entities provide visual contrast on stair tread nosing to make them
more visible to individuals with low vision). The Department received no
significant comments on this section and it is unchanged in the final rule.
Definitions of residential facilities and transient lodging. The 2010
Standards add a definition of “residential dwelling unit” and modify the
current definition of “transient lodging.” Under section 106.5 of the 2010
Standards, “residential dwelling unit” is defined as “[a] unit intended to be
used as a residence, that is primarily long-term in nature” and does not
include transient lodging, inpatient medical care, licensed long-term care,
and detention or correctional facilities. Additionally, section 106.5 of the
2010 Standards changes the definition of “transient lodging” to a building or
facility “containing one or more guest room(s) for sleeping that provides
accommodations that are primarily short-term in nature.” “Transient lodging”
does not include residential dwelling units intended to be used as a
residence. The references to “dwelling units” and “dormitories” that are in
the definition of the 1991 Standards are omitted from the 2010 Standards. The
comments about the application of transient lodging or residential standards
to social service center establishments, and housing at a place of education
are addressed separately below. The Department received one additional comment
on this issue from an organization representing emergency response personnel
seeking an exemption from the transient lodging accessibility requirements for
crew quarters and common use areas serving those crew quarters (e.g., locker
rooms, exercise rooms, day room) that are used exclusively by on-duty
emergency response personnel and that are not used for any public purpose. The
commenter argued that since emergency response personnel must meet certain
physical qualifications that have the effect of exempting persons with
mobility disabilities, there is no need to build crew quarters and common use
areas serving those crew quarters to meet the 2004 ADAAG. In addition, the
commenter argued that applying the transient lodging standards would impose
significant costs and create living space that is less usable for most
emergency response personnel. The ADA does not exempt spaces because of a
belief or policy that excludes persons with disabilities from certain work.
However, the Department believes that crew quarters that are used exclusively
as a residence by emergency response personnel and the kitchens and bathrooms
exclusively serving those quarters are more like residential dwelling units
and are therefore covered by the residential dwelling standards in the 2010
Standards, not the transient lodging standards. The residential dwelling
standards address most of the concerns of the commenter. For example, the
commenter was concerned that sinks in kitchens and lavatories in bathrooms
that are accessible under the transient lodging standards would be too low to
be comfortably used by emergency response personnel. The residential dwelling
standards allow such features to be adaptable so that they would not have to
be lowered until accessibility was needed. Similarly, grab bars and shower
seats would not have to be installed at the time of construction provided that
reinforcement has been installed in walls and located so as to permit their
installation at a later date.
§ 35.151(e) Social service center establishments
In the NPRM, the Department proposed a new Sec. 35.151(e) requiring group
homes, halfway houses, shelters, or similar social service center
establishments that provide temporary sleeping accommodations or residential
dwelling units to comply with the provisions of the 2004 ADAAG that apply to
residential facilities, including, but not limited to, the provisions in
sections 233 and 809. The NPRM explained that this proposal was based on two
important changes in the 2004 ADAAG. First, for the first time, residential
dwelling units are explicitly covered in the 2004 ADAAG in section 233.
Second, the 2004 ADAAG eliminates the language contained in the 1991 Standards
addressing scoping and technical requirements for homeless shelters, group
homes, and similar social service center establishments. Currently, such
establishments are covered in section 9.5 of the transient lodging section of
the 1991 Standards. The deletion of section 9.5 creates an ambiguity of
coverage that must be addressed. The NPRM explained the Department's belief
that transferring coverage of social service center establishments from the
transient lodging standards to the residential facilities standards would
alleviate conflicting requirements for social service center providers. The
Department believes that a substantial percentage of social service center
establishments are recipients of Federal financial assistance from the
Department of Housing and Urban Development (HUD). The Department of Health
and Human Services (HHS) also provides financial assistance for the operation
of shelters through the Administration for Children and Families programs. As
such, these establishments are covered both by the ADA and section 504 of the
Rehabilitation Act. UFAS is currently the design standard for new construction
and alterations for entities subject to section 504. The two design standards
for accessibility--the 1991 Standards and UFAS--have confronted many social
service providers with separate, and sometimes conflicting, requirements for
design and construction of facilities. To resolve these conflicts, the
residential facilities standards in the 2004 ADAAG have been coordinated with
the section 504 requirements. The transient lodging standards, however, are
not similarly coordinated. The deletion of section 9.5 of the 1991 Standards
from the 2004 ADAAG presented two options: (1) Require coverage under the
transient lodging standards, and subject such facilities to separate,
conflicting requirements for design and construction; or (2) require coverage
under the residential facilities standards, which would harmonize the
regulatory requirements under the ADA and section 504. The Department chose
the option that harmonizes the regulatory requirements: coverage under the
residential facilities standards. In the NPRM, the Department expressed
concern that the residential facilities standards do not include a requirement
for clear floor space next to beds similar to the requirement in the transient
lodging standards and as a result, the Department proposed adding a provision
that would require certain social service center establishments that provide
sleeping rooms with more than 25 beds to ensure that a minimum of 5 percent of
the beds have clear floor space in accordance with section 806.2.3 or 2004
ADAAG. In the NPRM, the Department requested information from providers who
operate homeless shelters, transient group homes, halfway houses, and other
social service center establishments, and from the clients of these facilities
who would be affected by this proposed change, asking, “[t]o what extent have
conflicts between the ADA and section 504 affected these facilities? What
would be the effect of applying the residential dwelling unit requirements to
these facilities, rather than the requirements for transient lodging guest
rooms?” 73 FR 34466, 34491 (June 17, 2008). Many of the commenters supported
applying the residential facilities requirements to social service center
establishments, stating that even though the residential facilities
requirements are less demanding in some instances, the existence of one clear
standard will result in an overall increased level of accessibility by
eliminating the confusion and inaction that are sometimes caused by the
current existence of multiple requirements. One commenter also stated that “it
makes sense to treat social service center establishments like residential
facilities because this is how these establishments function in practice.” Two
commenters agreed with applying the residential facilities requirements to
social service center establishments but recommended adding a requirement for
various bathing options, such as a roll-in shower (which is not required under
the residential standards). One commenter objected to the change and asked the
Department to require that social service center establishments continue to
comply with the transient lodging standards. One commenter stated that it did
not agree that the standards for residential coverage would serve persons with
disabilities as well as the 1991 transient lodging standards. This commenter
expressed concern that the Department had eliminated guidance for social
service agencies and that the rule should be put on hold until those
safeguards are restored. Another commenter argued that the rule that would
provide the greatest access for persons with disabilities should prevail.
Several commenters argued for the application of the transient lodging
standards to all social service center establishments except those that were
“intended as a person's place of abode,” referencing the Department's question
related to the definition of “place of lodging” in the title III NPRM. One
commenter stated that the International Building Code requires accessible
units in all transient facilities. The commenter expressed concern that group
homes should be built to be accessible, rather than adaptable. The Department
continues to be concerned about alleviating the challenges for social service
providers that are also subject to section 504 and would likely be subject to
conflicting requirements if the transient lodging standards were applied.
Thus, the Department has retained the requirement that social service center
establishments comply with the residential dwelling standards. The Department
believes, however, that social service center establishments that provide
emergency shelter to large transient populations should be able to provide
bathing facilities that are accessible to persons with mobility disabilities
who need roll-in showers. Because of the transient nature of the population of
these large shelters, it will not be feasible to modify bathing facilities in
a timely manner when faced with a need to provide a roll-in shower with a seat
when requested by an overnight visitor. As a result, the Department has added
a requirement that social service center establishments with sleeping
accommodations for more than 50 individuals must provide at least one roll-in
shower with a seat that complies with the relevant provisions of section 608
of the 2010 Standards. Transfer-type showers are not permitted in lieu of a
roll-in shower with a seat and the exceptions in sections 608.3 and 608.4 for
residential dwelling units are not permitted. When separate shower facilities
are provided for men and for women, at least one roll-in shower shall be
provided for each group. This supplemental requirement to the residential
facilities standards is in addition to the supplemental requirement that was
proposed in the NPRM for clear floor space in sleeping rooms with more than 25
beds. The Department also notes that while dwelling units at some social
service center establishments are also subject to the Fair Housing Act (FHAct)
design and construction requirements that require certain features of
adaptable and accessible design, FHAct units do not provide the same level of
accessibility that is required for residential facilities under the 2010
Standards. The FHAct requirements, where also applicable, should not be
considered a substitute for the 2010 Standards. Rather, the 2010 Standards
must be followed in addition to the FHAct requirements. The Department also
notes that whereas the NPRM used the term “social service establishment,” the
final rule uses the term “social service center establishment.” The Department
has made this editorial change so that the final rule is consistent with the
terminology used in the ADA. See 42 U.S.C. 12181(7)(k).
§ 35.151(f) Housing at a place of education
The Department of Justice and the Department of Education share responsibility
for regulation and enforcement of the ADA in postsecondary educational
settings, including its requirements for architectural features. In addition,
the Department of Housing and Urban Development (HUD) has enforcement
responsibility for housing subject to title II of the ADA. Housing facilities
in educational settings range from traditional residence halls and dormitories
to apartment or townhouse-style residences. In addition to title II of the
ADA, public universities and schools that receive Federal financial assistance
are also subject to section 504, which contains its own accessibility
requirements through the application of UFAS. Residential housing in an
educational setting is also covered by the FHAct, which requires newly
constructed multifamily housing to include certain features of accessible and
adaptable design. Covered entities subject to the ADA must always be aware of,
and comply with, any other Federal statutes or regulations that govern the
operation of residential properties. Although the 1991 Standards mention
dormitories as a form of transient lodging, they do not specifically address
how the ADA applies to dormitories or other types of residential housing
provided in an educational setting. The 1991 Standards also do not contain any
specific provisions for residential facilities, allowing covered entities to
elect to follow the residential standards contained in UFAS. Although the 2004
ADAAG contains provisions for both residential facilities and transient
lodging, the guidelines do not indicate which requirements apply to housing
provided in an educational setting, leaving it to the adopting agencies to
make that choice. After evaluating both sets of standards, the Department
concluded that the benefits of applying the transient lodging standards
outweighed the benefits of applying the residential facilities standards.
Consequently, in the NPRM, the Department proposed a new Sec. 35.151(f) that
provided that residence halls or dormitories operated by or on behalf of
places of education shall comply with the provisions of the proposed standards
for transient lodging, including, but not limited to, the provisions in
sections 224 and 806 of the 2004 ADAAG. Both public and private school housing
facilities have varied characteristics. College and university housing
facilities typically provide housing for up to one academic year, but may be
closed during school vacation periods. In the summer, they are often used for
short-term stays of one to three days, a week, or several months. Graduate and
faculty housing is often provided year-round in the form of apartments, which
may serve individuals or families with children. These housing facilities are
diverse in their layout. Some are double-occupancy rooms with a shared toilet
and bathing room, which may be inside or outside the unit. Others may contain
cluster, suite, or group arrangements where several rooms are located inside a
defined unit with bathing, kitchen, and similar common facilities. In some
cases, these suites are indistinguishable in features from traditional
apartments. Universities may build their own housing facilities or enter into
agreements with private developers to build, own, or lease housing to the
educational institution or to its students. Academic housing may be located on
the campus of the university or may be located in nearby neighborhoods.
Throughout the school year and the summer, academic housing can become program
areas in which small groups meet, receptions and educational sessions are
held, and social activities occur. The ability to move between rooms--both
accessible rooms and standard rooms--in order to socialize, to study, and to
use all public use and common use areas is an essential part of having access
to these educational programs and activities. Academic housing is also used
for short-term transient educational programs during the time students are not
in regular residence and may be rented out to transient visitors in a manner
similar to a hotel for special university functions. The Department was
concerned that applying the new construction requirements for residential
facilities to educational housing facilities could hinder access to
educational programs for students with disabilities. Elevators are not
generally required under the 2004 ADAAG residential facilities standards
unless they are needed to provide an accessible route from accessible units to
public use and common use areas, while under the 2004 ADAAG as it applies to
other types of facilities, multistory public facilities must have elevators
unless they meet very specific exceptions. In addition, the residential
facilities standards do not require accessible roll- in showers in bathrooms,
while the transient lodging requirements require some of the accessible units
to be served by bathrooms with roll-in showers. The transient lodging
standards also require that a greater number of units have accessible features
for persons with communication disabilities. The transient lodging standards
provide for installation of the required accessible features so that they are
available immediately, but the residential facilities standards allow for
certain features of the unit to be adaptable. For example, only reinforcements
for grab bars need to be provided in residential dwellings, but the actual
grab bars must be installed under the transient lodging standards. By
contrast, the residential facilities standards do require certain features
that provide greater accessibility within units, such as more usable kitchens,
and an accessible route throughout the dwelling. The residential facilities
standards also require 5 percent of the units to be accessible to persons with
mobility disabilities, which is a continuation of the same scoping that is
currently required under UFAS, and is therefore applicable to any educational
institution that is covered by section 504. The transient lodging standards
require a lower percentage of accessible sleeping rooms for facilities with
large numbers of rooms than is required by UFAS. For example, if a dormitory
had 150 rooms, the transient lodging standards would require seven accessible
rooms while the residential standards would require eight. In a large
dormitory with 500 rooms, the transient lodging standards would require 13
accessible rooms and the residential facilities standards would require 25.
There are other differences between the two sets of standards as well with
respect to requirements for accessible windows, alterations, kitchens,
accessible route throughout a unit, and clear floor space in bathrooms
allowing for a side transfer. In the NPRM, the Department requested public
comment on how to scope educational housing facilities, asking, “[w]ould the
residential facility requirements or the transient lodging requirements in the
2004 ADAAG be more appropriate for housing at places of education? How would
the different requirements affect the cost when building new dormitories and
other student housing?” 73 FR 34466, 34492 (June 17, 2008). The vast majority
of the comments received by the Department advocated using the residential
facilities standards for housing at a place of education instead of the
transient lodging standards, arguing that housing at places of public
education are in fact homes for the students who live in them. These
commenters argued, however, that the Department should impose a requirement
for a variety of options for accessible bathing and should ensure that all
floors of dormitories be accessible so that students with disabilities have
the same opportunities to participate in the life of the dormitory community
that are provided to students without disabilities. Commenters representing
persons with disabilities and several individuals argued that, although the
transient lodging standards may provide a few more accessible features (such
as roll-in showers), the residential facilities standards would ensure that
students with disabilities have access to all rooms in their assigned unit,
not just to the sleeping room, kitchenette, and wet bar. One commenter stated
that, in its view, the residential facilities standards were congruent with
overlapping requirements from HUD, and that access provided by the residential
facilities requirements within alterations would ensure dispersion of
accessible features more effectively. This commenter also argued that while
the increased number of required accessible units for residential facilities
as compared to transient lodging may increase the cost of construction or
alteration, this cost would be offset by a reduced need to adapt rooms later
if the demand for accessible rooms exceeds the supply. The commenter also
encouraged the Department to impose a visitability (accessible doorways and
necessary clear floor space for turning radius) requirement for both the
residential facilities and transient lodging requirements to allow students
with mobility impairments to interact and socialize in a fully integrated
fashion. Two commenters supported the Department's proposed approach. One
commenter argued that the transient lodging requirements in the 2004 ADAAG
would provide greater accessibility and increase the opportunity of students
with disabilities to participate fully in campus life. A second commenter
generally supported the provision of accessible dwelling units at places of
education, and pointed out that the relevant scoping in the International
Building Code requires accessible units “consistent with hotel
accommodations.” The Department has considered the comments recommending the
use of the residential facilities standards and acknowledges that they require
certain features that are not included in the transient lodging standards and
that should be required for housing provided at a place of education. In
addition, the Department notes that since educational institutions often use
their academic housing facilities as short-term transient lodging in the
summers, it is important that accessible features be installed at the outset.
It is not realistic to expect that the educational institution will be able to
adapt a unit in a timely manner in order to provide accessible accommodations
to someone attending a one-week program during the summer. The Department has
determined that the best approach to this type of housing is to continue to
require the application of transient lodging standards, but at the same time
to add several requirements drawn from the residential facilities standards
related to accessible turning spaces and work surfaces in kitchens, and the
accessible route throughout the unit. This will ensure the maintenance of the
transient lodging standard requirements related to access to all floors of the
facility, roll-in showers in facilities with more than 50 sleeping rooms, and
other important accessibility features not found in the residential facilities
standards, but will also ensure usable kitchens and access to all the rooms in
a suite or apartment. The Department has added a new definition to Sec.
35.104, “Housing at a Place of Education,” and has revised Sec. 35.151(f) to
reflect the accessible features that now will be required in addition to the
requirements set forth under the transient lodging standards. The Department
also recognizes that some educational institutions provide some residential
housing on a year-round basis to graduate students and staff which is
comparable to private rental housing, and which contains no facilities for
educational programming. Section 35.151(f)(3) exempts from the transient
lodging standards apartments or townhouse facilities provided by or on behalf
of a place of education that are leased on a year-round basis exclusively to
graduate students or faculty, and do not contain any public use or common use
areas available for educational programming; instead, such housing shall
comply with the requirements for residential facilities in sections 233 and
809 of the 2010 Standards. Section 35.151(f) uses the term “sleeping room” in
lieu of the term “guest room,” which is the term used in the transient lodging
standards. The Department is using this term because it believes that, for the
most part, it provides a better description of the sleeping facilities used in
a place of education than “guest room.” The final rule states that the
Department intends the terms to be used interchangeably in the application of
the transient lodging standards to housing at a place of education.
§ 35.151(g) Assembly areas
In the NPRM, the Department proposed Sec. 35.151(g) to supplement the assembly
area requirements of the 2004 ADAAG, which the Department is adopting as part
of the 2010 Standards. The NPRM proposed at Sec. 35.151(g)(1) to require
wheelchair spaces and companion seating locations to be dispersed to all
levels of the facility and are served by an accessible route. The Department
received no significant comments on this paragraph and has decided to adopt
the proposed language with minor modifications. The Department has retained
the substance of this section in the final rule but has clarified that the
requirement applies to stadiums, arenas, and grandstands. In addition, the
Department has revised the phrase “wheelchair and companion seating locations”
to “wheelchair spaces and companion seats.” Section 35.151(g)(1) ensures that
there is greater dispersion of wheelchair spaces and companion seats
throughout stadiums, arenas, and grandstands than would otherwise be required
by sections 221 and 802 of the 2004 ADAAG. In some cases, the accessible route
may not be the same route that other individuals use to reach their seats. For
example, if other patrons reach their seats on the field by an inaccessible
route (e.g., by stairs), but there is an accessible route that complies with
section 206.3 of the 2010 Standards that could be connected to seats on the
field, wheelchair spaces and companion seats must be placed on the field even
if that route is not generally available to the public. Regulatory language
that was included in the 2004 ADAAG advisory, but that did not appear in the
NPRM, has been added by the Department in Sec. 35.151(g)(2). Section
35.151(g)(2) now requires an assembly area that has seating encircling, in
whole or in part, a field of play or performance area such as an arena or
stadium, to place wheelchair spaces and companion seats around the entire
facility. This rule, which is designed to prevent a public entity from placing
wheelchair spaces and companion seats on one side of the facility only, is
consistent with the Department's enforcement practices and reflects its
interpretation of section 4.33.3 of the 1991 Standards. In the NPRM, the
Department proposed Sec. 35.151(g)(2) which prohibits wheelchair spaces and
companion seating locations from being “located on, (or obstructed by)
temporary platforms or other moveable structures.” Through its enforcement
actions, the Department discovered that some venues place wheelchair spaces
and companion seats on temporary platforms that, when removed, reveal
conventional seating underneath, or cover the wheelchair spaces and companion
seats with temporary platforms on top of which they place risers of
conventional seating. These platforms cover groups of conventional seats and
are used to provide groups of wheelchair seats and companion seats. Several
commenters requested an exception to the prohibition of the use of temporary
platforms for public entities that sell most of their tickets on a
season-ticket or other multi-event basis. Such commenters argued that they
should be able to use temporary platforms because they know, in advance, that
the patrons sitting in certain areas for the whole season do not need
wheelchair spaces and companion seats. The Department declines to adopt such
an exception. As it explained in detail in the NPRM, the Department believes
that permitting the use of movable platforms that seat four or more wheelchair
users and their companions have the potential to reduce the number of
available wheelchair seating spaces below the level required, thus reducing
the opportunities for persons who need accessible seating to have the same
choice of ticket prices and amenities that are available to other patrons in
the facility. In addition, use of removable platforms may result in instances
where last minute requests for wheelchair and companion seating cannot be met
because entire sections of accessible seating will be lost when a platform is
removed. See 73 FR 34466, 34493 (June 17, 2008). Further, use of temporary
platforms allows facilities to limit persons who need accessible seating to
certain seating areas, and to relegate accessible seating to less desirable
locations. The use of temporary platforms has the effect of neutralizing
dispersion and other seating requirements (e.g., line of sight) for wheelchair
spaces and companion seats. Cf. Independent Living Resources v. Oregon Arena
Corp., 1 F. Supp. 2d 1159, 1171 (D. Or. 1998) (holding that while a public
accommodation may “infill” wheelchair spaces with removable seats when the
wheelchair spaces are not needed to accommodate individuals with disabilities,
under certain circumstances “[s]uch a practice might well violate the rule
that wheelchair spaces must be dispersed throughout the arena in a manner that
is roughly proportionate to the overall distribution of seating”). In
addition, using temporary platforms to convert unsold wheelchair spaces to
conventional seating undermines the flexibility facilities need to accommodate
secondary ticket markets exchanges as required by Sec. 35.138(g) of the final
rule. As the Department explained in the NPRM, however, this provision was not
designed to prohibit temporary seating that increases seating for events
(e.g., placing temporary seating on the floor of a basketball court for a
concert). Consequently, the final rule, at Sec. 35.151(g)(3), has been amended
to clarify that if an entire seating section is on a temporary platform for a
particular event, then wheelchair spaces and companion seats may be in that
seating section. However, adding a temporary platform to create wheelchair
spaces and companion seats that are otherwise dissimilar from nearby fixed
seating and then simply adding a small number of additional seats to the
platform would not qualify as an “entire seating section” on the platform. In
addition, Sec. 35.151(g)(3) clarifies that facilities may fill in wheelchair
spaces with removable seats when the wheelchair spaces are not needed by
persons who use wheelchairs. The Department has been responsive to assembly
areas' concerns about reduced revenues due to unused accessible seating.
Accordingly, the Department has reduced scoping requirements significantly--by
almost half in large assembly areas--and determined that allowing assembly
areas to infill unsold wheelchair spaces with readily removable temporary
individual seats appropriately balances their economic concerns with the
rights of individuals with disabilities. See section 221.2 of the 2010
Standards. For stadium-style movie theaters, in Sec. 35.151(g)(4) of the NPRM
the Department proposed requiring placement of wheelchair seating spaces and
companion seats on a riser or cross-aisle in the stadium section of the
theater and placement of such seating so that it satisfies at least one of the
following criteria: (1) It is located within the rear 60 percent of the seats
provided in the auditorium; or (2) it is located within the area of the
auditorium where the vertical viewing angles are between the 40th to 100th
percentile of vertical viewing angles for all seats in that theater as ranked
from the first row (1st percentile) to the back row (100th percentile). The
vertical viewing angle is the angle between a horizontal line perpendicular to
the seated viewer's eye to the screen and a line from the seated viewer's eye
to the top of the screen. The Department proposed this bright-line rule for
two reasons: (1) The movie theater industry petitioned for such a rule; and
(2) the Department has acquired expertise on the design of stadium style
theaters from litigation against several major movie theater chains. See U.S.
v. AMC Entertainment, 232 F. Supp. 2d 1092 (C.D. Ca. 2002), rev'd in part, 549
F. 3d 760 (9th Cir. 2008); U.S. v. Cinemark USA, Inc., 348 F. 3d 569 (6th Cir.
2003), cert. denied, 542 U.S. 937 (2004). Two industry commenters--at least
one of whom otherwise supported this rule--requested that the Department
explicitly state that this rule does not apply retroactively to existing
theaters. Although this rule on its face applies to new construction and
alterations, these commenters were concerned that the rule could be
interpreted to apply retroactively because of the Department's statement in
the ANPRM that this bright-line rule, although newly- articulated, does not
represent a “substantive change from the existing line-of-sight requirements”
of section 4.33.3 of the 1991 Standards. See 69 FR 58768, 58776 (Sept. 30,
2004). Although the Department intends for Sec. 35.151(g)(4) of this rule to
apply prospectively to new construction and alterations, this rule is not a
departure from, and is consistent with, the line- of-sight requirements in the
1991 Standards. The Department has always interpreted the line-of-sight
requirements in the 1991 Standards to require viewing angles provided to
patrons who use wheelchairs to be comparable to those afforded to other
spectators. Section 35.151(g)(4) merely represents the application of these
requirements to stadium-style movie theaters. One commenter from a trade
association sought clarification whether Sec. 35.151(g)(4) applies to
stadium-style theaters with more than 300 seats, and argued that it should not
since dispersion requirements apply in those theaters. The Department declines
to limit this rule to stadium-style theaters with 300 or fewer seats;
stadium-style theaters of all sizes must comply with this rule. So, for
example, stadium-style theaters that must vertically disperse wheelchair and
companion seats must do so within the parameters of this rule. The NPRM
included a provision that required assembly areas with more than 5,000 seats
to provide at least five wheelchair spaces with at least three companion seats
for each of those five wheelchair spaces. The Department agrees with
commenters who asserted that group seating is better addressed through
ticketing policies rather than design and has deleted that provision from this
section of the final rule.
§ 35.151(h) Medical care facilities
In the 1991 title II regulation, there was no provision addressing the
dispersion of accessible sleeping rooms in medical care facilities. The
Department is aware, however, of problems that individuals with disabilities
face in receiving full and equal medical care when accessible sleeping rooms
are not adequately dispersed. When accessible rooms are not fully dispersed, a
person with a disability is often placed in an accessible room in an area that
is not medically appropriate for his or her condition, and is thus denied
quick access to staff with expertise in that medical specialty and specialized
equipment. While the Access Board did not establish specific design
requirements for dispersion in the 2004 ADAAG, in response to extensive
comments in support of dispersion it added an advisory note, Advisory 223.1
General, encouraging dispersion of accessible rooms within the facility so
that accessible rooms are more likely to be proximate to appropriate qualified
staff and resources. In the NPRM, the Department sought additional comment on
the issue, asking whether it should require medical care facilities, such as
hospitals, to disperse their accessible sleeping rooms, and if so, by what
method (by specialty area, floor, or other criteria). All of the comments the
Department received on this issue supported dispersing accessible sleeping
rooms proportionally by specialty area. These comments, from individuals,
organizations, and a building code association, argued that it would not be
difficult for hospitals to disperse rooms by specialty area, given the high
level of regulation to which hospitals are subject and the planning that
hospitals do based on utilization trends. Further, commenters suggested that
without a requirement, it is unlikely that hospitals would disperse the rooms.
In addition, concentrating accessible rooms in one area perpetuates
segregation of individuals with disabilities, which is counter to the purpose
of the ADA. The Department has decided to require medical care facilities to
disperse their accessible sleeping rooms in a manner that is proportionate by
type of medical specialty. This does not require exact mathematical
proportionality, which at times would be impossible. However, it does require
that medical care facilities disperse their accessible rooms by medical
specialty so that persons with disabilities can, to the extent practical, stay
in an accessible room within the wing or ward that is appropriate for their
medical needs. The language used in this rule (“in a manner that is
proportionate by type of medical specialty”) is more specific than that used
in the NPRM (“in a manner that enables patients with disabilities to have
access to appropriate specialty services”) and adopts the concept of
proportionality proposed by the commenters. Accessible rooms should be
dispersed throughout all medical specialties, such as obstetrics, orthopedics,
pediatrics, and cardiac care.
§ 35.151(i) Curb ramps
Section 35.151(e) on curb ramps in the 1991 rule has been redesignated as Sec.
35.151(i). In the NPRM, the Department proposed making a minor editorial
change to this section, deleting the phrase “other sloped areas” from the two
places in which it appears in the 1991 title II regulation. In the NPRM, the
Department stated that the phrase “other sloped areas” lacks technical
precision. The Department received no significant public comments on this
proposal. Upon further consideration, however, the Department has concluded
that the regulation should acknowledge that there are times when there are
transitions from sidewalk to road surface that do not technically qualify as
“curb ramps” (sloped surfaces that have a running slope that exceed 5
percent). Therefore, the Department has decided not to delete the phrase
“other sloped areas.”
§ 35.151(j) Residential housing for sale to individual owners
Although public entities that operate residential housing programs are subject
to title II of the ADA, and therefore must provide accessible residential
housing, the 1991 Standards did not contain scoping or technical standards
that specifically applied to residential housing units. As a result, under the
Department's title II regulation, these agencies had the choice of complying
with UFAS, which contains specific scoping and technical standards for
residential housing units, or applying the ADAAG transient lodging standards
to their housing. Neither UFAS nor the 1991 Standards distinguish between
residential housing provided for rent and those provided for sale to
individual owners. Thus, under the 1991 title II regulation, public entities
that construct residential housing units to be sold to individual owners must
ensure that some of those units are accessible. This requirement is in
addition to any accessibility requirements imposed on housing programs
operated by public entities that receive Federal financial assistance from
Federal agencies such as HUD. The 2010 Standards contain scoping and technical
standards for residential dwelling units. However, section 233.3.2 of the 2010
Standards specifically defers to the Department and to HUD, the
standard-setting agency under the ABA, to decide the appropriate scoping for
those residential dwelling units built by or on behalf of public entities with
the intent that the finished units will be sold to individual owners. These
programs include, for example, HUD's public housing and HOME programs as well
as State-funded programs to construct units for sale to individuals. In the
NPRM, the Department did not make a specific proposal for this scoping.
Instead, the Department stated that after consultation and coordination with
HUD, the Department would make a determination in the final rule. The
Department also sought public comment on this issue stating that “[t]he
Department would welcome recommendations from individuals with disabilities,
public housing authorities, and other interested parties that have experience
with these programs. Please comment on the appropriate scoping for residential
dwelling units built by or on behalf of public entities with the intent that
the finished units will be sold to individual owners.” 73 FR 34466, 34492
(June 17, 2008). All of the public comments received by the Department in
response to this question were supportive of the Department's ensuring that
the residential standards apply to housing built on behalf of public entities
with the intent that the finished units would be sold to individual owners.
The vast majority of commenters recommended that the Department require that
projects consisting of five or more units, whether or not the units are
located on one or multiple locations, comply with the 2004 ADAAG requirements
for scoping of residential units, which require that 5 percent, and no fewer
than one, of the dwelling units provide mobility features, and that 2 percent,
and no fewer than one, of the dwelling units provide communication features.
See 2004 ADAAG Section 233.3. These commenters argued that the Department
should not defer to HUD because HUD has not yet adopted the 2004 ADAAG and
there is ambiguity on the scope of coverage of pre-built for sale units under
HUD's current section 504 regulations. In addition, these commenters expressed
concern that HUD's current regulation, 24 CFR 8.29, presumes that a
prospective buyer is identified before design and construction begins so that
disability features can be incorporated prior to construction. These
commenters stated that State and Federally funded homeownership programs
typically do not identify prospective buyers before construction has
commenced. One commenter stated that, in its experience, when public entities
build accessible for-sale units, they often sell these units through a lottery
system that does not make any effort to match persons who need the accessible
features with the units that have those features. Thus, accessible units are
often sold to persons without disabilities. This commenter encouraged the
Department to make sure that accessible for-sale units built or funded by
public entities are placed in a separate lottery restricted to income-eligible
persons with disabilities. Two commenters recommended that the Department
develop rules for four types of for-sale projects: single family pre-built
(where buyer selects the unit after construction), single family post-built
(where the buyer chooses the model prior to its construction), multi-family
pre-built, and multi-family post-built. These commenters recommended that the
Department require pre-built units to comply with the 2004 ADAAG 233.1 scoping
requirements. For post- built units, the commenters recommended that the
Department require all models to have an alternate design with mobility
features and an alternate design with communications features in compliance
with 2004 ADAAG. Accessible models should be available at no extra cost to the
buyer. One commenter recommended that, in addition to required fully
accessible units, all ground floor units should be readily convertible for
accessibility or for sensory impairments technology enhancements. The
Department believes that consistent with existing requirements under title II,
housing programs operated by public entities that design and construct or
alter residential units for sale to individual owners should comply with the
2010 Standards, including the requirements for residential facilities in
sections 233 and 809. These requirements will ensure that a minimum of 5
percent of the units, but no fewer than one unit, of the total number of
residential dwelling units will be designed and constructed to be accessible
for persons with mobility disabilities. At least 2 percent, but no fewer than
one unit, of the total number of residential dwelling units shall provide
communication features. The Department recognizes that there are some programs
(such as the one identified by the commenter), in which units are not designed
and constructed until an individual buyer is identified. In such cases, the
public entity is still obligated to comply with the 2010 Standards. In
addition, the public entity must ensure that pre- identified buyers with
mobility disabilities and visual and hearing disabilities are afforded the
opportunity to buy the accessible units. Once the program has identified
buyers who need the number of accessible units mandated by the 2010 Standards,
it may have to make reasonable modifications to its policies, practices, and
procedures in order to provide accessible units to other buyers with
disabilities who request such units. The Department notes that the residential
facilities standards allow for construction of units with certain features of
adaptability. Public entities that are concerned that fully accessible units
are less marketable may choose to build these units to include the allowable
adaptable features, and then adapt them at their own expense for buyers with
mobility disabilities who need accessible units. For example, features such as
grab bars are not required but may be added by the public entity if needed by
the buyer at the time of purchase and cabinets under sinks may be designed to
be removable to allow access to the required knee space for a forward
approach. The Department agrees with the commenters that covered entities may
have to make reasonable modifications to their policies, practices, and
procedures in order to ensure that when they offer pre-built accessible
residential units for sale, the units are offered in a manner that gives
access to those units to persons with disabilities who need the features of
the units and who are otherwise eligible for the housing program. This may be
accomplished, for example, by adopting preferences for accessible units for
persons who need the features of the units, holding separate lotteries for
accessible units, or other suitable methods that result in the sale of
accessible units to persons who need the features of such units. In addition,
the Department believes that units designed and constructed or altered that
comply with the requirements for residential facilities and are offered for
sale to individuals must be provided at the same price as units without such
features.
§ 35.151(k) Detention and correctional facilities
The 1991 Standards did not contain specific accessibility standards applicable
to cells in correctional facilities. However, correctional and detention
facilities operated by or on behalf of public entities have always been
subject to the nondiscrimination and program accessibility requirements of
title II of the ADA. The 2004 ADAAG established specific requirements for the
design and construction and alterations of cells in correctional facilities
for the first time. Based on complaints received by the Department,
investigations, and compliance reviews of jails, prisons, and other detention
and correctional facilities, the Department has determined that many detention
and correctional facilities do not have enough accessible cells, toilets, and
shower facilities to meet the needs of their inmates with mobility
disabilities and some do not have any at all. Inmates are sometimes housed in
medical units or infirmaries separate from the general population simply
because there are no accessible cells. In addition, some inmates have alleged
that they are housed at a more restrictive classification level simply because
no accessible housing exists at the appropriate classification level. The
Department's compliance reviews and investigations have substantiated certain
of these allegations. The Department believes that the insufficient number of
accessible cells is, in part, due to the fact that most jails and prisons were
built long before the ADA became law and, since then, have undergone few
alterations that would trigger the obligation to provide accessible features
in accordance with UFAS or the 1991 Standards. In addition, the Department has
found that even some new correctional facilities lack accessible features. The
Department believes that the unmet demand for accessible cells is also due to
the changing demographics of the inmate population. With thousands of
prisoners serving life sentences without eligibility for parole, prisoners are
aging, and the prison population of individuals with disabilities and elderly
individuals is growing. A Bureau of Justice Statistics study of State and
Federal sentenced inmates (those sentenced to more than one year) shows the
total estimated count of State and Federal prisoners aged 55 and older grew by
36,000 inmates from 2000 (44,200) to 2006 (80,200). William J. Sabol et al.,
Prisoners in 2006, Bureau of Justice Statistics Bulletin, Dec. 2007, at 23
(app. table 7), available at http://bjs.ojp.usdoj.gov/
index.cfm?ty=pbdetail&iid=908 (last visited July 16, 2008); Allen J. Beck
et al., Prisoners in 2000, Bureau of Justice Statistics Bulletin, Aug. 2001,
at 10 (Aug. 2001) (Table 14), available at
bjs.ojp.usdoj.gov/index.cfm?ty=pbdetail&iid=927 (last visited July 16,
2008). This jump constitutes an increase of 81 percent in prisoners aged 55
and older during this period. In the NPRM, the Department proposed a new
section, Sec. 35.152, which combined a range of provisions relating to both
program accessibility and application of the proposed standards to detention
and correctional facilities. In the final rule, the Department is placing
those provisions that refer to design, construction, and alteration of
detention and correction facilities in a new paragraph (k) of Sec. 35.151, the
section of the rule that addresses new construction and alterations for
covered entities. Those portions of the final rule that address other issues,
such as placement policies and program accessibility, are placed in the new
Sec. 35.152. In the NPRM, the Department also sought input on how best to meet
the needs of inmates with mobility disabilities in the design, construction,
and alteration of detention and correctional facilities. The Department
received a number of comments in response to this question.
New Construction. The NPRM did not expressly propose that new
construction of correctional and detention facilities shall comply with the
proposed standards because the Department assumed it would be clear that the
requirements of Sec. 35.151 would apply to new construction of correctional
and detention facilities in the same manner that they apply to other
facilities constructed by covered entities. The Department has decided to
create a new section, Sec. 35.151(k)(1), which clarifies that new construction
of jails, prisons, and other detention facilities shall comply with the
requirements of 2010 Standards. Section 35.151(k)(1) also increases the
scoping for accessible cells from the 2 percent specified in the 2004 ADAAG to
3 percent.
Alterations. Although the 2010 Standards contain specifications for
alterations in existing detention and correctional facilities, section 232.2
defers to the Attorney General the decision as to the extent these
requirements will apply to alterations of cells. The NPRM proposed at Sec.
35.152(c) that “[a]lterations to jails, prisons, and other detention and
correctional facilities will comply with the requirements of Sec. 35.151(b).”
73 FR 34466, 34507 (June 17, 2008). The final rule retains that requirement at
Sec. 35.151(k)(2), but increases the scoping for accessible cells from the 2
percent specified in the 2004 ADAAG to 3 percent.
Substitute cells. In the ANPRM, the Department sought public comment
about the most effective means to ensure that existing correctional facilities
are made accessible to prisoners with disabilities and presented three
options: (1) Require all altered elements to be accessible, which would
maintain the current policy that applies to other ADA alteration requirements;
(2) permit substitute cells to be made accessible within the same facility,
which would permit correctional authorities to meet their obligation by
providing the required accessible features in cells within the same facility,
other than those specific cells in which alterations are planned; or (3)
permit substitute cells to be made accessible within a prison system, which
would focus on ensuring that prisoners with disabilities are housed in
facilities that best meet their needs, as alterations within a prison
environment often result in piecemeal accessibility. In Sec. 35.152(c) of the
NPRM, the Department proposed language based on Option 2, providing that when
cells are altered, a covered entity may satisfy its obligation to provide the
required number of cells with mobility features by providing the required
mobility features in substitute cells (i.e., cells other than those where
alterations are originally planned), provided that each substitute cell is
located within the same facility, is integrated with other cells to the
maximum extent feasible, and has, at a minimum, physical access equal to that
of the original cells to areas used by inmates or detainees for visitation,
dining, recreation, educational programs, medical services, work programs,
religious services, and participation in other programs that the facility
offers to inmates or detainees. The Department received few comments on this
proposal. The majority who chose to comment supported an approach that allowed
substitute cells to be made accessible within the same facility. In their
view, such an approach balanced administrators' needs, cost considerations,
and the needs of inmates with disabilities. One commenter noted, however, that
with older facilities, required modifications may be inordinately costly and
technically infeasible. A large county jail system supported the proposed
approach as the most viable option allowing modification or alteration of
existing cells based on need and providing a flexible approach to provide
program and mobility accessibility. It noted, as an alternative, that
permitting substitute cells to be made accessible within a prison system would
also be a viable option since such an approach could create a centralized
location for accessibility needs and, because that jail system's facilities
were in close proximity, it would have little impact on families for
visitation or on accessible programming. A large State department of
corrections objected to the Department's proposal. The commenter stated that
some very old prison buildings have thick walls of concrete and reinforced
steel that are difficult, if not impossible to retrofit, and to do so would be
very expensive. This State system approaches accessibility by looking at its
system as a whole and providing access to programs for inmates with
disabilities at selected prisons. This commenter explained that not all of its
facilities offer the same programs or the same levels of medical or mental
health services. An inmate, for example, who needs education, substance abuse
treatment, and sex offender counseling may be transferred between facilities
in order to meet his needs. The inmate population is always in flux and there
are not always beds or program availability for every inmate at his security
level. This commenter stated that the Department's proposed language would put
the State in the position of choosing between adding accessible cells and
modifying paths of travel to programs and services at great expense or not
altering old facilities, causing them to become in states of disrepair and
obsolescent, which would be fiscally irresponsible. The Department is
persuaded by these comments and has modified the alterations requirement in
Sec. 35.151(k)(2)(iv) in the final rule to allow that if it is technically
infeasible to provide substitute cells in the same facility, cells can be
provided elsewhere within the corrections system.
Number of accessible cells. Section 232.2.1 of the 2004 ADAAG
requires at least 2 percent, but no fewer than one, of the cells in newly
constructed detention and correctional facilities to have accessibility
features for individuals with mobility disabilities. Section 232.3 provides
that, where special holding cells or special housing cells are provided, at
least one cell serving each purpose shall have mobility features. The
Department sought input on whether these 2004 ADAAG requirements are
sufficient to meet the needs of inmates with mobility disabilities. A major
association representing county jails throughout the country stated that the
2004 ADAAG 2 percent requirement for accessible cells is sufficient to meet
the needs of county jails. Similarly, a large county sheriff's department
advised that the 2 percent requirement far exceeds the need at its detention
facility, where the average age of the population is 32. This commenter
stressed that the regulations need to address the differences between a local
detention facility with low average lengths of stay as opposed to a State
prison housing inmates for lengthy periods. This commenter asserted that more
stringent requirements will raise construction costs by requiring
modifications that are not needed. If more stringent requirements are adopted,
the commenter suggested that they apply only to State and Federal prisons that
house prisoners sentenced to long terms. The Department notes that a prisoner
with a mobility disability needs a cell with mobility features regardless of
the length of incarceration. However, the length of incarceration is most
relevant in addressing the needs of an aging population. The overwhelming
majority of commenters responded that the 2 percent ADAAG requirement is
inadequate to meet the needs of the incarcerated. Many commenters suggested
that the requirement be expanded to apply to each area, type, use, and class
of cells in a facility. They asserted that if a facility has separate areas
for specific programs, such as a dog training program or a substance abuse
unit, each of these areas should also have 2 percent accessible cells but not
less than one. These same commenters suggested that 5-7 percent of cells
should be accessible to meet the needs of both an aging population and the
larger number of inmates with mobility disabilities. One organization
recommended that the requirement be increased to 5 percent overall, and that
at least 2 percent of each type and use of cell be accessible. Another
commenter recommended that 10 percent of cells be accessible. An organization
with extensive corrections experience noted that the integration mandate
requires a sufficient number and distribution of accessible cells so as to
provide distribution of locations relevant to programs to ensure that persons
with disabilities have access to the programs. Through its investigations and
compliance reviews, the Department has found that in most detention and
correctional facilities, a 2 percent accessible cell requirement is inadequate
to meet the needs of the inmate population with disabilities. That finding is
supported by the majority of the commenters that recommended a 5-7 percent
requirement. Indeed, the Department itself requires more than 2 percent of the
cells to be accessible at its own corrections facilities. The Federal Bureau
of Prisons is subject to the requirements of the 2004 ADAAG through the
General Services Administration's adoption of the 2004 ADAAG as the
enforceable accessibility standard for Federal facilities under the
Architectural Barriers Act of 1968. 70 FR 67786, 67846-47 (Nov. 8, 2005).
However, in order to meet the needs of inmates with mobility disabilities, the
Bureau of Prisons has elected to increase that percentage and require that 3
percent of inmate housing at its facilities be accessible. Bureau of Prisons,
Design Construction Branch, Design Guidelines, Attachment A: Accessibility
Guidelines for Design, Construction, and Alteration of Federal Bureau of
Prisons (Oct. 31, 2006). The Department believes that a 3 percent accessible
requirement is reasonable. Moreover, it does not believe it should impose a
higher percentage on detention and corrections facilities than it utilizes for
its own facilities. Thus, the Department has adopted a 3 percent requirement
in Sec. 35.151(k) for both new construction and alterations. The Department
notes that the 3 percent requirement is a minimum. As corrections systems plan
for new facilities or alterations, the Department urges planners to include
numbers of inmates with disabilities in their population projections in order
to take the necessary steps to provide a sufficient number of accessible cells
to meet inmate needs.
Dispersion of Cells. The NPRM did not contain express language
addressing dispersion of cells in a facility. However, Advisory 232.2 of the
2004 ADAAG recommends that “[a]ccessible cells or rooms should be dispersed
among different levels of security, housing categories, and holding
classifications (e.g., male/female and adult/juvenile) to facilitate access.”
In explaining the basis for recommending, but not requiring, this type of
dispersal, the Access Board stated that “[m]any detention and correctional
facilities are designed so that certain areas (e.g., `shift' areas) can be
adapted to serve as different types of housing according to need” and that
“[p]lacement of accessible cells or rooms in shift areas may allow additional
flexibility in meeting requirements for dispersion of accessible cells or
rooms.” The Department notes that inmates are typically housed in separate
areas of detention and correctional facilities based on a number of factors,
including their classification level. In many instances, detention and
correctional facilities have housed inmates in inaccessible cells, even though
accessible cells were available elsewhere in the facility, because there were
no cells in the areas where they needed to be housed, such as in
administrative or disciplinary segregation, the women's section of the
facility, or in a particular security classification area. The Department
received a number of comments stating that dispersal of accessible cells
together with an adequate number of accessible cells is necessary to prevent
inmates with disabilities from placement in improper security classification
and to ensure integration. Commenters recommended modification of the scoping
requirements to require a percentage of accessible cells in each program,
classification, use or service area. The Department is persuaded by these
comments. Accordingly, Sec. 35.151(k)(1) and (k)(2) of the final rule require
accessible cells in each classification area.
Medical facilities. The NPRM also did not propose language addressing
the application of the 2004 ADAAG to medical and long- term care facilities in
correctional and detention facilities. The provisions of the 2004 ADAAG
contain requirements for licensed medical and long-term care facilities, but
not those that are unlicensed. A disability advocacy group and a number of
other commenters recommended that the Department expand the application of
section 232.4 to apply to all such facilities in detention and correctional
facilities, regardless of licensure. They recommended that whenever a
correctional facility has a program that is addressed specifically in the 2004
ADAAG, such as a long-term care facility, the 2004 ADAAG scoping and design
features should apply for those elements. Similarly, a building code
organization noted that its percentage requirements for accessible units is
based on what occurs in the space, not on the building type. The Department is
persuaded by these comments and has added Sec. 35.151(k)(3), which states that
“[w]ith respect to medical and long-term care facilities in jails, prisons,
and other detention and correctional facilities, public entities shall apply
the 2010 Standards technical and scoping requirements for those facilities
irrespective of whether those facilities are licensed.”
Public Accommodations and Commercial
Facilities: Guidance on the Revisions to 28 CFR part 36, subpart D
Guidance on the Revisions to 28 CFR part 36, subpart D
Subpart D establishes the title III requirements applicable to new
construction and alterations. The Department has amended this subpart to adopt
the 2004 ADAAG, set forth the effective dates for implementation of the 2010
Standards, and make related revisions as described below.
§ 36.403 Alterations: Path of Travel
In the NPRM, the Department proposed one change to Sec. 36.403 on alterations
and path of travel by adding a path of travel safe harbor. Proposed Sec.
36.403(a)(1) stated that if a private entity has constructed or altered
required elements of a path of travel in accordance with the 1991 Standards,
the private entity is not required to retrofit such elements to reflect
incremental changes in the 2010 Standards solely because of an alteration to a
primary function area served by that path of travel. A substantial number of
commenters objected to the Department's creation of a safe harbor for
alterations to required elements of a path of travel that comply with the
current 1991 Standards. These commenters argued that if a public accommodation
already is in the process of altering its facility, there should be a legal
requirement that individuals with disabilities are entitled to increased
accessibility provided by the 2004 ADAAG for path of travel work. These
commenters also stated that they did not believe there was a statutory basis
for “grandfathering” facilities that comply with the 1991 Standards. Another
commenter argued that the updates incorporated into the 2004 ADAAG provide
very substantial improvements for access, and that since there already is a 20
percent cost limit on the amount that can be expended on path of travel
alterations, there is no need for a further limitation. Some commenters
supported the safe harbor as lessening the economic costs of implementing the
2004 ADAAG for existing facilities. One commenter also stated that without the
safe harbor, entities that already have complied with the 1991 Standards will
have to make and pay for compliance twice, as compared to those entities that
made no effort to comply in the first place. Another commenter asked that the
safe harbor be revised to include pre-ADA facilities that have been made
compliant with the 1991 Standards to the extent “readily achievable” or, in
the case of alterations, “to the maximum extent feasible,” but that are not in
full compliance with the 1991 Standards. The final rule retains the safe
harbor for required elements of a path of travel to altered primary function
areas for private entities that already have complied with the 1991 Standards
with respect to those required elements. As discussed with respect to Sec.
36.304, the Department believes that this safe harbor strikes an appropriate
balance between ensuring that individuals with disabilities are provided
access to buildings and facilities and mitigating potential financial burdens
on existing places of public accommodation that are undertaking alterations
subject to the 2010 Standards. This safe harbor is not a blanket exemption for
facilities. If a private entity undertakes an alteration to a primary function
area, only the required elements of a path of travel to that area that already
comply with the 1991 Standards are subject to the safe harbor. If a private
entity undertakes an alteration to a primary function area and the required
elements of a path of travel to the altered area do not comply with the 1991
Standards, then the private entity must bring those elements into compliance
with the 2010 Standards.
§ 36.405 Alterations: Historic Preservation
In the 1991 rule, the Department provided guidance on making alterations to
buildings or facilities that are eligible for listing in the National Register
of Historic Places under the National Historic Preservation Act or that are
designated as historic under State or local law. That provision referenced the
1991 Standards. Because those cross-references to the 1991 Standards are no
longer applicable, it is necessary in this final rule to provide new
regulatory text. No substantive change in the Department's approach in this
area is intended by this revision.
§ 36.406 Standards for New Construction and Alterations
Applicable standards. Section 306 of the ADA, 42 U.S.C. 12186, directs the
Attorney General to issue regulations to implement title III that are
consistent with the guidelines published by the Access Board. As described in
greater detail elsewhere in this Appendix, the Department is a statutory
member of the Access Board and was involved significantly in the development
of the 2004 ADAAG. Nonetheless, the Department has reviewed the standards and
has determined that additional regulatory provisions are necessary to clarify
how the Department will apply the 2010 Standards to places of lodging, social
service center establishments, housing at a place of education, assembly
areas, and medical care facilities. Those provisions are contained in Sec.
36.406(c)-(g). Each of these provisions is discussed below. Section 36.406(a)
adopts the 2004 ADAAG as part of the 2010 Standards and establishes the
compliance date and triggering events for the application of those standards
to both new construction and alterations. Appendix B of this final rule
(Analysis and Commentary on the 2010 ADA Standards for Accessible Design)
provides a description of the major changes in the 2010 Standards (as compared
to the 1991 ADAAG) and a discussion of the public comments that the Department
received on specific sections of the 2004 ADAAG. A number of commenters asked
the Department to revise certain provisions in the 2004 ADAAG in a manner that
would reduce either the required scoping or specific technical accessibility
requirements. As previously stated, the ADA requires the Department to adopt
standards consistent with the guidelines adopted by the Access Board. The
Department will not adopt any standards that provide less accessibility than
is provided under the guidelines contained in the 2004 ADAAG because the
guidelines adopted by the Access Board are “minimum guidelines.” 42 U.S.C.
12186(c). In the NPRM, the Department specifically proposed amending Sec.
36.406(a) by dividing it into two sections. Proposed Sec. 36.406(a)(1)
specified that new construction and alterations subject to this part shall
comply with the 1991 Standards if physical construction of the property
commences less than six months after the effective date of the rule. Proposed
Sec. 36.406(a)(2) specified that new construction and alterations subject to
this part shall comply with the proposed standards if physical construction of
the property commences six months or more after the effective date of the
rule. The Department also proposed deleting the advisory information now
published in a table at Sec. 36.406(b).
Compliance date. When the ADA was enacted, the compliance dates for
various provisions were delayed in order to provide time for covered entities
to become familiar with their new obligations. Titles II and III of the ADA
generally became effective on January 26, 1992, six months after the
regulations were published. See 42 U.S.C. 12131 note; 42 U.S.C. 12181 note.
New construction under title II and alterations under either title II or title
III had to comply with the design standards on that date. See 42 U.S.C. 12131
note; 42 U.S.C. 12183(a)(2). For new construction under title III, the
requirements applied to facilities designed and constructed for first
occupancy after January 26, 1993--18 months after the 1991 Standards were
published by the Department. See 42 U.S.C. 12183(a)(1). The Department
received numerous comments on the issue of effective date, many of them
similar to those received in response to the ANPRM. A substantial number of
commenters advocated a minimum of 18 months from publication of the final rule
to the effective date for application of the standards to new construction,
consistent with the time period used for implementation of the 1991 Standards.
Many of these commenters argued that the 18-month period was necessary to
minimize the likelihood of having to redesign projects already in the design
and permitting stages at the time that the final rule is published. According
to these commenters, large projects take several years from design to
occupancy, and can be subject to delays from obtaining zoning, site approval,
third- party design approval (i.e., architectural review), and governmental
permits. To the extent the new standards necessitate changes in any previous
submissions or permits already issued, businesses might have to expend
significant funds and incur delays due to redesign and resubmission. Some
commenters also expressed concern that a six-month period would be hard to
implement given that many renovations are planned around retail selling
periods, holidays, and other seasonal concerns. For example, hotels plan
renovations during their slow periods, retail establishments avoid renovations
during the major holiday selling periods, and businesses in certain parts of
the country cannot do any major construction during parts of the winter. Some
commenters argued that chain establishments need additional time to redesign
their “master facility” designs for replication at multiple locations, taking
into account both the new standards and applicable State and local
accessibility requirements. Other commenters argued for extending the
effective date from six months to a minimum of 12 months for many of the same
reasons, and one commenter argued that there should be a tolling of the
effective date for those businesses that are in the midst of the permitting
process if the necessary permits are delayed due to legal challenges or other
circumstances outside the business's control. Several commenters took issue
with the Department's characterization of the 2004 ADAAG and the 1991
Standards as two similar rules. These commenters argued that many provisions
in the 2004 ADAAG represent a “substantial and significant” departure from the
1991 Standards and that it will take a great deal of time and money to
identify all the changes and implement them. In particular, they were
concerned that small businesses lacked the internal resources to respond
quickly to the new changes and that they would have to hire outside experts to
assist them. One commenter expressed concern that regardless of familiarity
with the 2004 ADAAG, since the 2004 ADAAG standards are organized in an
entirely different manner from the 1991 Standards, and contain, in the
commenter's view, extensive changes, it will make the shift from the old to
the new standards quite complicated. Several commenters also took issue with
the Department's proffered rationale that by adopting a six-month effective
date, the Department was following the precedent of other Federal agencies
that have adopted the 2004 ADAAG for facilities whose accessibility they
regulate. These commenters argued that the Department's title III regulation
applies to a much broader range and number of facilities and programs than the
other Federal agencies (i.e., Department of Transportation and the General
Services Administration) and that those agencies regulate accessibility
primarily in either governmental facilities or facilities operated by
quasi-governmental authorities. Several commenters representing the travel,
vacation, and golf industries argued that the Department should adopt a
two-year effective date for new construction. In addition to many of the
arguments made by commenters in support of an 18-month effective date, these
commenters also argued that a two-year time frame would allow States with
DOJ-certified building codes to have the time to amend their codes to meet the
2004 ADAAG so that design professionals can work from compatible codes and
standards. Several commenters recommended treating alterations differently
than new construction, arguing for a one-year effective date for alterations.
Another commenter representing building officials argued that a minimum of a
six-month phase-in for alterations was sufficient, since a very large
percentage of alteration projects “are of a scale that they should be able to
accommodate the phase- in.” In contrast, many commenters argued that the
proposed six-month effective date should be retained in the final rule. The
Department has been persuaded by concerns raised by some of the commenters
that the six month compliance date proposed in the NPRM for application of the
2010 Standards may be too short for certain projects that are already in the
midst of the design and permitting process. The Department has determined that
for new construction and alterations, compliance with the 2010 Standards will
not be required until 18 months from the date the final rule is published.
This is consistent with the amount of time given when the 1991 regulation was
published. Since many State and local building codes contain provisions that
are consistent with 2004 ADAAG, the Department has decided that public
accommodations that choose to comply with the 2010 Standards as defined in
Sec. 36.104 before the compliance date will still be considered in compliance
with the ADA. However, public accommodations that choose to comply with the
2010 Standards in lieu of the 1991 Standards prior to the compliance date
described in this rule must choose one or the other standard, and may not rely
on some of the requirements contained in one standard and some of the
requirements contained in the other standard.
Triggering event. In the NPRM, the Department proposed using the
start of physical construction as the triggering event for applying the
proposed standards to new construction under title III. This triggering event
parallels that for the alterations provisions (i.e., the date on which
construction begins), and would apply clearly across all types of covered
public accommodations. The Department also proposed that for prefabricated
elements, such as modular buildings and amusement park rides and attractions,
or installed equipment, such as ATMs, the start of construction means the date
on which the site preparation begins. Site preparation includes providing an
accessible route to the element. The Department's NPRM sought public comment
on how to define the start of construction and the practicality of applying
commencement of construction as a triggering event. The Department also
requested input on whether the proposed definition of the start of
construction was sufficiently clear and inclusive of different types of
facilities. The Department also sought input about facilities subject to title
III for which commencement of construction would be ambiguous or problematic.
The Department received numerous comments recommending that the Department
adopt a two-pronged approach to defining the triggering event. In those cases
where permits are required, the Department should use “date of permit
application” as the effective date triggering event, and if no permit is
required, the Department should use “start of construction.” A number of these
commenters argued that the date of permit application is appropriate because
the applicant would have to consider the applicable State and Federal
accessibility standards in order to submit the designs usually required with
the application. Moreover, the date of permit application is a typical
triggering event in other code contexts, such as when jurisdictions introduce
an updated building code. Some commenters expressed concern that using the
date of “start of construction” was problematic because the date can be
affected by factors that are outside the control of the owner. For example, an
owner can plan construction to start before the new standards take effect and
therefore use the 1991 Standards in the design. If permits are not issued in a
timely manner, then the construction could be delayed until after the
effective date, and then the project would have to be redesigned. This problem
would be avoided if the permit application date was the triggering event. Two
commenters expressed concern that the term “start of construction” is
ambiguous, because it is unclear whether start of construction means the
razing of structures on the site to make way for a new facility or means site
preparation, such as regrading or laying the foundation. One commenter
recommended using the “signing date of a construction contract,” and an
additional commenter recommended that the new standards apply only to
“buildings permitted after the effective date of the regulations.” One
commenter stated that for facilities that fall outside the building permit
requirements (ATMs, prefabricated saunas, small sheds), the triggering event
should be the date of installation, rather than the date the space for the
facility is constructed. The Department is persuaded by the comments to adopt
a two- pronged approach to defining the triggering event for new construction
and alterations. The final rule states that in those cases where permits are
required, the triggering event shall be the date when the last application for
a building permit application or permit extension is certified to be complete
by a State, county, or local government, or in those jurisdictions where the
government does not certify completion of applications, the date when the last
application for a building permit or permit extension is received by the
State, county, or local government. If no permits are required, then the
triggering event shall be the “start of physical construction or alterations.”
The Department has also added clarifying language related to the term “start
of physical construction or alterations” to make it clear that “start of
physical construction or alterations” is not intended to mean the date of
ceremonial groundbreaking or the date a structure is razed to make it possible
for construction of a facility to take place.
Amusement rides. Section 234 of the 2010 Standards provides
accessibility guidelines for newly designed and constructed amusement rides.
The amusement ride provisions do not provide a “triggering event” for new
construction or alteration of an amusement ride. An industry commenter
requested that the triggering event of “first use” as noted in the Advisory
note to section 234.1 of the 2004 ADAAG be included in the final rule. The
Advisory note provides that “[a] custom designed and constructed ride is new
upon its first use, which is the first time amusement park patrons take the
ride.” The Department declines to treat amusement rides differently than other
types of new construction and alterations and under the final rule, they are
subject to Sec. 36.406(a)(3). Thus, newly constructed and altered amusement
rides shall comply with the 2010 Standards if the start of physical
construction or the alteration is on or after 18 months from the publication
date of this rule. The Department also notes that section 234.4.2 of the 2010
Standards only applies where the structural or operational characteristics of
an amusement ride are altered. It does not apply in cases where the only
change to a ride is the theme. Noncomplying new construction and alterations.
The element-by- element safe harbor referenced in Sec. 36.304(d)(2) has no
effect on new or altered elements in existing facilities that were subject to
the 1991 Standards on the date that they were constructed or altered, but do
not comply with the technical and scoping specifications for those elements in
the 1991 Standards. Section 36.406(a)(5) of the final rule sets forth the
rules for noncompliant new construction or alterations in facilities that were
subject to the requirements of this part. Under those provisions, noncomplying
new construction and alterations constructed or altered after the effective
date of the applicable ADA requirements and before March 15, 2012 shall,
before March 15, 2012, be made accessible in accordance with either the 1991
Standards or the 2010 Standards. Noncomplying new construction and alterations
constructed or altered after the effective date of the applicable ADA
requirements and before March 15, 2012, shall, on or after March 15, 2012, be
made accessible in accordance with the 2010 Standards.
§ 36.406(b) Application of Standards to Fixed Elements
The final rule contains a new Sec. 36.406(b) that clarifies that the
requirements established by this section, including those contained in the
2004 ADAAG, prescribe the requirements necessary to ensure that fixed or
built-in elements in new or altered facilities are accessible to individuals
with disabilities. Once the construction or alteration of a facility has been
completed, all other aspects of programs, services, and activities conducted
in that facility are subject to the operational requirements established
elsewhere in this final rule. Although the Department has often chosen to use
the requirements of the 1991 Standards as a guide to determining when and how
to make equipment and furnishings accessible, those coverage determinations
fall within the discretionary authority of the Department. The Department is
also clarifying that the advisory notes, appendix notes, and figures that
accompany the 1991 and 2010 Standards do not establish separately enforceable
requirements unless otherwise specified in the text of the standards. This
clarification has been made to address concerns expressed by ANPRM commenters
who mistakenly believed that the advisory notes in the 2004 ADAAG established
requirements beyond those established in the text of the guidelines (e.g.,
Advisory 504.4 suggests, but does not require, that covered entities provide
visual contrast on stair tread nosings to make them more visible to
individuals with low vision). The Department received no comments on this
provision in the NPRM.
§ 36.406(c) Places of Lodging
In the NPRM, the Department proposed a new definition for public
accommodations that are “places of lodging” and a new Sec. 36.406(c) to
clarify the scope of coverage for places of public accommodation that meet
this definition. For many years the Department has received inquiries from
members of the public seeking clarification of ADA coverage of rental
accommodations in timeshares, condominium hotels, and mixed-use and corporate
hotel facilities that operate as places of public accommodation (as that term
is now defined in Sec. 36.104). These facilities, which have attributes of
both residential dwellings and transient lodging facilities, have become
increasingly popular since the ADA's enactment in 1990 and make up the
majority of new hotel construction in some vacation destinations. The hybrid
residential and lodging characteristics of these new types of facilities, as
well as their ownership characteristics, complicate determinations of ADA
coverage, prompting questions from both industry and individuals with
disabilities. While the Department has interpreted the ADA to encompass these
hotel-like facilities when they are used to provide transient lodging, the
regulation previously has specifically not addressed them. In the NPRM, the
Department proposed a new Sec. 36.406(c), entitled “Places of Lodging,” which
was intended to clarify that places of lodging, including certain timeshares,
condominium hotels, and mixed-use and corporate hotel facilities, shall comply
with the provisions of the proposed standards, including, but not limited to,
the requirements for transient lodging in sections 224 and 806 of the 2004
ADAAG. The Department's NPRM sought public input on this proposal. The
Department received a substantial number of comments on these issues from
industry representatives, advocates for persons with disabilities, and
individuals. A significant focus of these comments was on how the Department
should define and regulate vacation rental units in timeshares, vacation
communities, and condo-hotels where the units are owned and controlled by
individual owners and rented out some portion of time to the public, as
compared to traditional hotels and motels that are owned, controlled, and
rented to the public by one entity. Scoping and technical requirements
applicable to “places of lodging.” In the NPRM, the Department asked for
public comment on its proposal in Sec. 36.406(c) to apply to places of lodging
the scoping and technical requirements for transient lodging, rather than the
scoping and technical requirements for residential dwelling units. Commenters
generally agreed that the transient lodging requirements should apply to
places of lodging. Several commenters stated that the determination as to
which requirements apply should be made based on the intention for use at the
time of design and construction. According to these commenters, if units are
intended for transient rentals, then the transient lodging standards should
apply, and if they are intended to be used for residential purposes, the
residential standards should apply. Some commenters agreed with the
application of transient lodging standards to places of lodging in general,
but disagreed about the characterization of certain types of facilities as
covered places of lodging. The Department agrees that the scoping and
technical standards applicable to transient lodging should apply to facilities
that contain units that meet the definition of “places of lodging.” Scoping
for timeshare or condominium hotels. In the NPRM, the Department sought
comment on the appropriate basis for determining scoping for a timeshare or
condominium-hotel. A number of commenters indicated that scoping should be
based on the usage of the facility. Only those units used for short-term stays
should be counted for application of the transient lodging standards, while
units sold as residential properties should be treated as residential units
not subject to the ADA. One commenter stated that scoping should be based on
the maximum number of sleeping units available for public rental. Another
commenter pointed out that unlike traditional hotels and motels, the number of
units available for rental in a facility or development containing
individually owned units is not fixed over time. Owners have the right to
participate in a public rental program some, all, or none of the time, and
individual owner participation changes from year to year. The Department
believes that the determination for scoping should be based on the number of
units in the project that are designed and constructed with the intention that
their owners may participate in a transient lodging rental program. The
Department cautions that it is not the number of owners that actually exercise
their right to participate in the program that determines the scoping. Rather
it is the units that could be placed into an on-site or off-site transient
lodging rental program. In the final rule, the Department has added a
provision to Sec. 36.406(c)(3), which states that units intended to be used
exclusively for residential purposes that are contained in facilities that
also meet the definition of place of lodging are not covered by the transient
lodging standards. Title III of the ADA does not apply to units designed and
constructed with the intention that they be rented or sold as exclusively
residential units. Such units are covered by the Fair Housing Act (FHAct),
which contains requirements for certain features of accessible and adaptable
design both for units and for public and common use areas. All units designed
and constructed with the intention that they may be used for both residential
and transient lodging purposes are covered by the ADA and must be counted for
determining the required number of units that must meet the transient lodging
standards in the 2010 Standards. Public use and common use areas in facilities
containing units subject to the ADA also must meet the 2010 Standards. In some
developments, units that may serve as residential units some of the time and
rental units some of the time will have to meet both the FHAct and the ADA
requirements. For example, all of the units in a vacation condominium facility
whose owners choose to rent to the public when they are not using the units
themselves would be counted for the purposes of determining the appropriate
number of units that must comply with the 2010 Standards. In a newly
constructed condominium that has three floors with units dedicated to be sold
solely as residential housing and three floors with units that may be used as
residences or hotel units, only the units on the three latter floors would be
counted for applying the 2010 Standards. In a newly constructed timeshare
development containing 100 units, all of which may be made available to the
public through an exchange or rental program, all 100 units would be counted
for purposes of applying the 2010 Standards. One commenter also asked the
Department for clarification of how to count individually owned “lock-off
units.” Lock-off units are units that are multi-bedroom but can be “locked
off” into two separate units, each having individual external access. This
commenter requested that the Department state in the final rule that
individually owned lock-off units do not constitute multiple guest rooms for
purposes of calculating compliance with the scoping requirements for
accessible units, since for the most part the lock- off units are used as part
of a larger accessible unit, and portions of a unit not locked off would
constitute both an accessible one- bedroom unit or an accessible two-bedroom
unit with the lock-off unit. It is the Department's view that lock-off units
that are individually owned that can be temporarily converted into two units
do not constitute two separate guest rooms for purposes of calculating
compliance with the scoping requirements. One commenter asked the Department
how developers should scope units where buildings are constructed in phases
over a span of years, recommending that the scoping be based on the total
number of units expected to be constructed at the project and not on a
building-by-building basis or on a phase-by-phase basis. The Department does
not think scoping should be based on planned number of units, which may or may
not be actually constructed over a period of years. However, the Department
recognizes that resort developments may contain buildings and facilities that
are of all sizes from single-unit cottages to facilities with hundreds of
units. The Department believes it would be appropriate to allow designers,
builders, and developers to aggregate the units in facilities with 50 or fewer
units that are subject to a single permit application and that are on a common
site or that are constructed at the same time for the purposes of applying the
scoping requirements in table 224.2. Facilities with more than 50 units should
be scoped individually in accordance with the table. The regulation has been
revised to reflect this application of the scoping requirements. One commenter
also asked the Department to use the title III regulation to declare that
timeshares subject to the transient lodging standards are exempt from the
design and construction requirements of the FHAct. The coverage of the FHAct
is set by Congress and interpreted by regulations issued by the Department of
Housing and Urban Development. The Department has no authority to exempt
anyone from coverage of the FHAct. Application of ADA to places of lodging
that contain individually owned units. The Department believes that regardless
of ownership structure for individual units, rental programs (whether they are
on- or off-site) that make transient lodging guest rooms available to the
public must comply with the general nondiscrimination requirements of the ADA.
In addition, as provided in Sec. 36.406(c), newly constructed facilities that
contain accommodations intended to be used for transient lodging purposes must
comply with the 2010 Standards. In the NPRM, the Department asked for public
comment on several issues related to ensuring the availability of accessible
units in a rental program operated by a place of lodging. The Department
sought input on how it could address a situation in which a new or converted
facility constructs the required number of accessible units, but the owners of
those units choose not to participate in the rental program; whether the
facility has an obligation to encourage or require owners of accessible units
to participate in the rental program; and whether the facility developer, the
condominium association, or the hotel operator has an obligation to retain
ownership or control over a certain number of accessible units to avoid this
problem. In the NPRM, the Department sought public input on how to regulate
scoping for a timeshare or condominium-rental facility that decides, after the
sale of units to individual owners, to begin a rental program that qualifies
the facility as a place of lodging, and how the condominium association,
operator, or developer should determine which units to make accessible. A
number of commenters expressed concerns about the ability of the Department to
require owners of accessible units to participate in the rental program, to
require developers, condo associations, or homeowners associations to retain
ownership of accessible units, and to impose accessibility requirements on
individual owners who choose to place inaccessible units into a rental program
after purchase. These commenters stated that individuals who purchase
accessible vacation units in condominiums, individual vacation homes, and
timeshares have ownership rights in their units and may choose lawfully to
make their units available to the public some, all, or none of the time.
Commenters advised the Department that the Securities and Exchange Commission
takes the position that if condominium units are offered in connection with
participation in a required rental program for any part of the year, require
the use of an exclusive rental agent, or impose conditions otherwise
restricting the occupancy or rental of the unit, then that offering will be
viewed as an offering of securities in the form of an investment (rather than
a real estate offering). SEC Release No. 33- 5347, Guidelines as to the
Applicability of the Federal Securities Laws to Offers and Sales of
Condominiums or Units in a Real Estate Development (Jan. 4, 1973).
Consequently, most condominium developers do not impose such restrictions at
the time of sale. Moreover, owners who choose to rent their units as a
short-term vacation rental can select any rental or management company to
lease and manage their unit, or they may rent them out on their own. They also
may choose never to lease those units. Thus, there are no guarantees that at
any particular time, accessible units will be available for rental by the
public. According to this commenter, providing incentives for owners of
accessible units to place their units in the rental program will not work,
because it does not guarantee the availability of the requisite number of
rooms dispersed across the development, and there is not any reasonable,
identifiable source of funds to cover the costs of such incentives. A number
of commenters also indicated that it potentially is discriminatory as well as
economically infeasible to require that a developer hold back the accessible
units so that the units can be maintained in the rental program year-round.
One commenter pointed out that if a developer did not sell the accessible
condominiums or timeshares in the building inventory, the developer would be
subject to a potential ADA or FHAct complaint because persons with
disabilities who wanted to buy accessible units rather than rent them each
year would not have the option to purchase them. In addition, if a developer
held back accessible units, the cost of those units would have to be spread
across all the buyers of the inaccessible units, and in many cases would make
the project financially infeasible. This would be especially true for smaller
projects. Finally, this commenter argued that requiring units to be part of
the common elements that are owned by all of the individual unit owners is
infeasible because the common ownership would result in pooled rental income,
which would transform the owners into participants in a rental pool, and thus
turn the sale of the condominiums into the sale of securities under SEC
Release 33-5347. Several commenters noted that requiring the operator of the
rental program to own the accessible units is not feasible either because the
operator of the rental program would have to have the funds to invest in the
purchase of all of the accessible units, and it would not have a means of
recouping its investment. One commenter stated that in Texas, it is illegal
for on-site rental programs to own condominium units. Another commenter noted
that such a requirement might lead to the loss of on-site rental programs,
leaving owners to use individual third-party brokers, or rent the units
privately. One commenter acknowledged that individual owners cannot be
required to place their units in a rental pool simply to offer an accessible
unit to the public, since the owners may be purchasing units for their own
use. However, this commenter recommended that owners who choose to place their
units in a rental pool be required to contribute to a fund that would be used
to renovate units that are placed in the rental pool to increase the
availability of accessible units. One commenter argued that the legal entity
running the place of lodging has an obligation to retain control over the
required number of accessible units to ensure that they are available in
accordance with title III. A number of commenters also argued that the
Department has no legal authority to require individual owners to engage in
barrier removal where an existing development adds a rental program. One
commenter stated that Texas law prohibits the operator of on-site rental
program from demanding that alterations be made to a particular unit. In
addition, under Texas law, condominium declarations may not require some units
and not others to make changes, because that would lead to unequal treatment
of units and owners, which is not permissible. One commenter stated that since
it was not possible for operators of rental programs offering privately owned
condominiums to comply with accessible scoping, the Department should create
exemptions from the accessible scoping, especially for existing facilities. In
addition, this commenter stated that if an operator of an on-site rental
program were to require renovations as a condition of participation in the
rental program, unit owners might just rent their units through a different
broker or on their own, in which case such requirements would not apply. A
number of commenters argued that if a development decides to create a rental
program, it must provide accessible units. Otherwise the development would
have to ensure that units are retrofitted. A commenter argued that if an
existing building is being converted, the Department should require that if
alterations of the units are performed by an owner or developer prior to sale
of the units, then the alterations requirements should apply, in order to
ensure that there are some accessible units in the rental pool. This commenter
stated that because of the proliferation of these type of developments in
Hawaii, mandatory alteration is the only way to guarantee the availability of
accessible units in the long run. In this commenter's view, since conversions
almost always require makeover of existing buildings, this will not lead to a
significant expense. The Department agrees with the commenters that it would
not be feasible to require developers to hold back or purchase accessible
units for the purposes of making them available to the public in a transient
lodging rental program, nor would it be feasible to require individual owners
of accessible units to participate in transient lodging rental programs. The
Department recognizes that places of lodging are developed and financed under
myriad ownership and management structures and agrees that there will be
circumstances where there are legal barriers to requiring compliance with
either the alterations requirements or the requirements related to barrier
removal. The Department has added an exception to Sec. 36.406(c), providing
that in existing facilities that meet the definition of places of lodging,
where the guest rooms are not owned or substantially controlled by the entity
that owns, leases, or operates the overall facility and the physical features
of the guest room interiors are controlled by their individual owners, the
units are not subject to the alterations requirement, even where the owner
rents the unit out to the public through a transient lodging rental program.
In addition, the Department has added an exception to the barrier removal
requirements at Sec. 36.304(g) providing that in existing facilities that meet
the definition of places of lodging, where the guest rooms are not owned or
substantially controlled by the entity that owns, leases, or operates the
overall facility and the physical features of the guest room interiors are
controlled by their individual owners, the units are not subject to the
barrier removal requirement. The Department notes, however, that there are
legal relationships for some timeshares and cooperatives where the ownership
interests do not convey control over the physical features of units. In those
cases, it may be the case that the facility has an obligation to meet the
alterations or barrier removal requirements or to maintain accessible
features.
§ 36.406(d) Social Service Center Establishments
In the NPRM, the Department proposed a new Sec. 36.406(d) requiring group
homes, halfway houses, shelters, or similar social service center
establishments that provide temporary sleeping accommodations or residential
dwelling units to comply with the provisions of the 2004 ADAAG that apply to
residential facilities, including, but not limited to, the provisions in
sections 233 and 809. The NPRM explained that this proposal was based on two
important changes in the 2004 ADAAG. First, for the first time, residential
dwelling units are explicitly covered in the 2004 ADAAG in section 233.
Second, the 2004 ADAAG eliminates the language contained in the 1991 Standards
addressing scoping and technical requirements for homeless shelters, group
homes, and similar social service center establishments. Currently, such
establishments are covered in section 9.5 of the transient lodging section of
the 1991 Standards. The deletion of section 9.5 creates an ambiguity of
coverage that must be addressed. The NPRM explained the Department's belief
that transferring coverage of social service center establishments from the
transient lodging standards to the residential facilities standards would
alleviate conflicting requirements for social service providers. The
Department believes that a substantial percentage of social service providers
are recipients of Federal financial assistance from the Department of Housing
and Urban Development (HUD). The Department of Health and Human Services (HHS)
also provides financial assistance for the operation of shelters through the
Administration for Children and Families programs. As such, they are covered
both by the ADA and section 504. UFAS is currently the design standard for new
construction and alterations for entities subject to section 504. The two
design standards for accessibility--the 1991 Standards and UFAS--have
confronted many social service providers with separate, and sometimes
conflicting, requirements for design and construction of facilities. To
resolve these conflicts, the residential facilities standards in the 2004
ADAAG have been coordinated with the section 504 requirements. The transient
lodging standards, however, are not similarly coordinated. The deletion of
section 9.5 of the 1991 Standards from the 2004 ADAAG presented two options:
(1) Require coverage under the transient lodging standards, and subject such
facilities to separate, conflicting requirements for design and construction;
or (2) require coverage under the residential facilities standards, which
would harmonizes the regulatory requirements under the ADA and section 504.
The Department chose the option that harmonizes the regulatory requirements:
coverage under the residential facilities standards. In the NPRM, the
Department expressed concern that the residential facilities standards do not
include a requirement for clear floor space next to beds similar to the
requirement in the transient lodging standards; as a result, the Department
proposed adding a provision that would require certain social service center
establishments that provide sleeping rooms with more than 25 beds to ensure
that a minimum of 5 percent of the beds have clear floor space in accordance
with section 806.2.3 of the 2004 ADAAG. The Department requested information
from providers who operate homeless shelters, transient group homes, halfway
houses, and other social service center establishments, and from the clients
of these facilities who would be affected by this proposed change. In the
NPRM, the Department asked to what extent conflicts between the ADA and
section 504 have affected these facilities and what the effect would be of
applying the residential dwelling unit requirements to these facilities,
rather than the requirements for transient lodging guest rooms. Many of the
commenters supported applying the residential facilities requirements to
social service center establishments stating that even though the residential
facilities requirements are less demanding, in some instances, the existence
of one clear standard will result in an overall increased level of
accessibility by eliminating the confusion and inaction that are sometimes
caused by the current existence of multiple requirements. One commenter stated
that the residential facilities guidelines were more appropriate because
individuals housed in social service center establishments typically stay for
a prolonged period of time, and guests of a transient lodging facility
typically are not housed to participate in a program or receive services. One
commenter opposed to the proposed section argued for the application of the
transient lodging standards to all social service center establishments except
those that were “intended as a person's place of abode,” referencing the
Department's question related to the definition of place of lodging in the
title III NPRM. A second commenter stated that the use of transient lodging
guidelines would lead to greater accessibility. The Department continues to be
concerned about alleviating the challenges for social service providers that
are also subject to section 504 and that would likely be subject to
conflicting requirements if the transient lodging standard were applied. Thus,
the Department has retained the requirement that social service center
establishments comply with the residential dwelling standards. The Department
did not receive comments regarding adding a requirement for bathing options,
such as a roll-in shower, in social service center establishments operated by
public accommodations. The Department did, however, receive comments in
support of adding such a requirement regarding public entities under title II.
The Department believes that social service center establishments that provide
emergency shelter to large transient populations should be able to provide
bathing facilities that are accessible to persons with mobility disabilities
who need roll-in showers. Because of the transient nature of the population of
these large shelters, it will not be feasible to modify bathing facilities in
a timely manner when faced with a need to provide a roll-in shower with a seat
when requested by an overnight visitor. As a result, the Department has added
a requirement that social service center establishments with sleeping
accommodations for more than 50 individuals must provide at least one roll-in
shower with a seat that complies with the relevant provisions of section 608
of the 2010 Standards. Transfer-type showers are not permitted in lieu of a
roll-in shower with a seat, and the exceptions in sections 608.3 and 608.4 for
residential dwelling units are not permitted. When separate shower facilities
are provided for men and for women, at least one roll-in shower must be
provided for each group. This supplemental requirement to the residential
facilities standards is in addition to the supplemental requirement that was
proposed in the NPRM for clear floor space in sleeping rooms with more than 25
beds. The Department also notes that while dwelling units at some social
service center establishments are also subject to FHAct design and
construction requirements that require certain features of adaptable and
accessible design, FHAct units do not provide the same level of accessibility
that is required for residential facilities under the 2010 Standards. The
FHAct requirements, where also applicable, should not be considered a
substitute for the 2010 Standards. Rather, the 2010 Standards must be followed
in addition to the FHAct requirements. The Department also notes that while in
the NPRM the Department used the term “social service establishment,” the
final rule uses the term “social service center establishment.” The Department
has made this editorial change so that the final rule is consistent with the
terminology used in the ADA. See 42 U.S.C. 12181(7)(K).
§ 36.406(e) Housing at a Place of Education
The Department of Justice and the Department of Education share responsibility
for regulation and enforcement of the ADA in postsecondary educational
settings, including architectural features. Housing types in educational
settings range from traditional residence halls and dormitories to apartment
or townhouse-style residences. In addition to title III of the ADA,
universities and schools that are recipients of Federal financial assistance
also are subject to section 504, which contains its own accessibility
requirements currently through the application of UFAS. Residential housing,
including housing in an educational setting, is also covered by the FHAct,
which requires newly constructed multifamily housing to include certain
features of accessible and adaptable design. Covered entities subject to the
ADA must always be aware of, and comply with, any other Federal statutes or
regulations that govern the operation of residential properties. Although the
1991 Standards mention dormitories as a form of transient lodging, they do not
specifically address how the ADA applies to dormitories and other types of
residential housing provided in an educational setting. The 1991 Standards
also do not contain any specific provisions for residential facilities,
allowing covered entities to elect to follow the residential standards
contained in UFAS. Although the 2004 ADAAG contains provisions for both
residential facilities and transient lodging, the guidelines do not indicate
which requirements apply to housing provided in an educational setting,
leaving it to the adopting agencies to make that choice. After evaluating both
sets of standards, the Department concluded that the benefits of applying the
transient lodging standards outweighed the benefits of applying the
residential facilities standards. Consequently, in the NPRM, the Department
proposed a new Sec. 36.406(e) that provided that residence halls or
dormitories operated by or on behalf of places of education shall comply with
the provisions of the proposed standards for transient lodging, including, but
not limited to, the provisions in sections 224 and 806 of the 2004 ADAAG.
Private universities and schools covered by title III as public accommodations
are required to make their programs and activities accessible to persons with
disabilities. The housing facilities that they provide have varied
characteristics. College and university housing facilities typically provide
housing for up to one academic year, but may be closed during school vacation
periods. In the summer, they often are used for short-term stays of one to
three days, a week, or several months. Graduate and faculty housing often is
provided year-round in the form of apartments, which may serve individuals or
families with children. These housing facilities are diverse in their layout.
Some are double-occupancy rooms with a shared toilet and bathing room, which
may be inside or outside the unit. Others may contain cluster, suite, or group
arrangements where several rooms are located inside a defined unit with
bathing, kitchen, and similar common facilities. In some cases, these suites
are indistinguishable in features from traditional apartments. Universities
may build their own housing facilities or enter into agreements with private
developers to build, own, or lease housing to the educational institution or
to its students. Academic housing may be located on the campus of the
university or may be located in nearby neighborhoods. Throughout the school
year and the summer, academic housing can become program areas in which small
groups meet, receptions and educational sessions are held, and social
activities occur. The ability to move between rooms--both accessible rooms and
standard rooms--in order to socialize, to study, and to use all public use and
common use areas is an essential part of having access to these educational
programs and activities. Academic housing also is used for short-term
transient educational programs during the time students are not in regular
residence and may be rented out to transient visitors in a manner similar to a
hotel for special university functions. The Department was concerned that
applying the new construction requirements for residential facilities to
educational housing facilities could hinder access to educational programs for
students with disabilities. Elevators generally are not required under the
2004 ADAAG residential facilities standards unless they are needed to provide
an accessible route from accessible units to public use and common use areas,
while under the 2004 ADAAG as it applies to other types of facilities,
multistory private facilities must have elevators unless they meet very
specific exceptions. In addition, the residential facilities standards do not
require accessible roll- in showers in bathrooms, while the transient lodging
requirements require some of the accessible units to be served by bathrooms
with roll-in showers. The transient lodging standards also require that a
greater number of units have accessible features for persons with
communication disabilities. The transient lodging standards provide for
installation of the required accessible features so that they are available
immediately, but the residential facilities standards allow for certain
features of the unit to be adaptable. For example, only reinforcements for
grab bars need to be provided in residential dwellings, but the actual grab
bars must be installed under the transient lodging standards. By contrast, the
residential facilities standards do require certain features that provide
greater accessibility within units, such as usable kitchens and an accessible
route throughout the dwelling. The residential facilities standards also
require 5 percent of the units to be accessible to persons with mobility
disabilities, which is a continuation of the same scoping that is currently
required under UFAS and is therefore applicable to any educational institution
that is covered by section 504. The transient lodging standards require a
lower percentage of accessible sleeping rooms for facilities with large
numbers of rooms than is required by UFAS. For example, if a dormitory has 150
rooms, the transient lodging standards would require 7 accessible rooms, while
the residential standards would require 8. In a large dormitory with 500
rooms, the transient lodging standards would require 13 accessible rooms, and
the residential facilities standards would require 25. There are other
differences between the two sets of standards, including requirements for
accessible windows, alterations, kitchens, an accessible route throughout a
unit, and clear floor space in bathrooms allowing for a side transfer. In the
NPRM, the Department requested public comment on how to scope educational
housing facilities, and it asked whether the residential facilities
requirements or the transient lodging requirements in the 2004 ADAAG would be
more appropriate for housing at places of education and asked how the
different requirements would affect the cost of building new dormitories and
other student housing. See 73 FR 34508, 34545 (June 17, 2008). The Department
received several comments on this issue under title III. One commenter stated
that the Department should adopt the residential facilities standards for
housing at a place of education. In the commenter's view, the residential
facilities standards are congruent with overlapping requirements imposed by
HUD, and the residential facilities requirements would ensure dispersion of
accessible features more effectively. This commenter also argued that while
the increased number of required accessible units for residential facilities
as compared to transient lodging may increase the cost of construction or
alteration, this cost would be offset by a reduced need later to adapt rooms
if the demand for accessible rooms exceeds the supply. The commenter also
encouraged the Department to impose a visitability (accessible doorways and
necessary clear floor space for turning radius) requirement for both the
residential facilities and transient lodging requirements to allow students
with mobility impairments to interact and socialize in a fully integrated
fashion. Another commenter stated that while dormitories should be treated
like residences as opposed to transient lodging, the Department should ensure
that “all floors are accessible,” thus ensuring community integration and
visitability. Another commenter argued that housing at a place of education is
comparable to residential housing, and that most of the housing types used by
schools do not have the same amenities and services or function like transient
lodging and should not be treated as such. Several commenters focused on the
length of stay at this type of housing and suggested that if the facilities
are subject to occupancy for greater than 30 days, the residential standards
should apply. Another commenter supported the Department's adoption of the
transient lodging standards, arguing this will provide greater accessibility
and therefore increase opportunities for students with disabilities to
participate. One commenter, while supporting the use of transient lodging
standards in this area, argued that the Department also should develop
regulations relating to the usability of equipment in housing facilities by
persons who are blind or visually impaired. Another commenter argued that the
Department should not impose the transient lodging requirements on K-12
schools because the cost of adding elevators can be prohibitive, and because
there are safety concerns related to evacuating students in wheelchairs living
on floors above the ground floor in emergencies causing elevator failures. The
Department has considered the comments recommending the use of the residential
facilities standards and acknowledges that they require certain features that
are not included in the transient lodging standards and that should be
required for housing provided at a place of education. In addition, the
Department notes that since educational institutions often use their academic
housing facilities as short-term transient lodging in the summers, it is
important that accessible features be installed at the outset. It is not
realistic to expect that the educational institution will be able to adapt a
unit in a timely manner in order to provide accessible accommodations to
someone attending a one-week program during the summer. The Department has
determined that the best approach to this type of housing is to continue to
require the application of transient lodging standards but, at the same time,
to add several requirements drawn from the residential facilities standards
related to accessible turning spaces and work surfaces in kitchens, and the
accessible route throughout the unit. This will ensure the maintenance of the
transient lodging standard requirements related to access to all floors of the
facility, roll-in showers in facilities with more than 50 sleeping rooms, and
other important accessibility features not found in the residential facilities
standards, but also will ensure usable kitchens and access to all the rooms in
a suite or apartment. The Department has added a new definition to Sec.
36.104, “Housing at a Place of Education,” and has revised Sec. 36.406(e) to
reflect the accessible features that now will be required in addition to the
requirements set forth under the transient lodging standards. The Department
also recognizes that some educational institutions provide some residential
housing on a year-round basis to graduate students and staff that is
comparable to private rental housing but contains no facilities for
educational programming. Section 36.406(e)(3) exempts from the transient
lodging standards apartments or townhouse facilities that are provided with a
lease on a year-round basis exclusively to graduate students or faculty and
that do not contain any public use or common use areas available for
educational programming; instead, such housing must comply with the
requirements for residential facilities in sections 233 and 809 of the 2010
Standards. The regulatory text uses the term “sleeping room” in lieu of the
term “guest room,” which is the term used in the transient lodging standards.
The Department is using this term because it believes that for the most part,
it provides a better description of the sleeping facilities used in a place of
education than “guest room.” The final rule states in Sec. 36.406(e) that the
Department intends the terms to be used interchangeably in the application of
the transient lodging standards to housing at a place of education.
§ 36.406(f) Assembly Areas
In the NPRM, the Department proposed Sec. 36.406(f) to supplement the assembly
area requirements of the 2004 ADAAG, which the Department is adopting as part
of the 2010 Standards. The NPRM proposed at Sec. 36.406(f)(1) to require
wheelchair spaces and companion seating locations to be dispersed to all
levels of the facility that are served by an accessible route. The Department
received no significant comments on this paragraph and has decided to adopt
the proposed language with minor modifications. Section 36.406(f)(1) ensures
that there is greater dispersion of wheelchair spaces and companion seats
throughout stadiums, arenas, and grandstands than would otherwise be required
by sections 221 and 802 of the 2004 ADAAG. In some cases, the accessible route
may not be the same route that other individuals use to reach their seats. For
example, if other patrons reach their seats on the field by an inaccessible
route (e.g., by stairs), but there is an accessible route that complies with
section 206.3 of the 2004 ADAAG that could be connected to seats on the field,
wheelchair spaces and companion seats must be placed on the field even if that
route is not generally available to the public. Regulatory language that was
included in the 2004 ADAAG advisory, but that did not appear in the NPRM, has
been added by the Department in Sec. 36.406(f)(2). Section 36.406(f)(2) now
requires an assembly area that has seating encircling, in whole or in part, a
field of play or performance area, such as an arena or stadium, to place
wheelchair spaces and companion seats around the entire facility. This rule,
which is designed to prevent a public accommodation from placing wheelchair
spaces and companion seats on one side of the facility only, is consistent
with the Department's enforcement practices and reflects its interpretation of
section 4.33.3 of the 1991 Standards. In the NPRM, the Department proposed
Sec. 36.406(f)(2), which prohibits wheelchair spaces and companion seating
locations from being “located on (or obstructed by) temporary platforms * *
*.” 73 FR 34508, 34557 (June 17, 2008). Through its enforcement actions, the
Department discovered that some venues place wheelchair spaces and companion
seats on temporary platforms that, when removed, reveal conventional seating
underneath, or cover the wheelchair spaces and companion seats with temporary
platforms on top of which they place risers of conventional seating. These
platforms cover groups of conventional seats and are used to provide groups of
wheelchair seats and companion seats. Several commenters requested an
exception to the prohibition of the use of temporary platforms for public
accommodations that sell most of their tickets on a season-ticket or other
multi-event basis. Such commenters argued that they should be able to use
temporary platforms because they know, in advance, that the patrons sitting in
certain areas for the whole season do not need wheelchair spaces and companion
seats. The Department declines to adopt such an exception. As it explained in
detail in the NPRM, the Department believes that permitting the use of movable
platforms that seat four or more wheelchair users and their companions have
the potential to reduce the number of available wheelchair seating spaces
below the level required, thus reducing the opportunities for persons who need
accessible seating to have the same choice of ticket prices and amenities that
are available to other patrons in the facility. In addition, use of removable
platforms may result in instances where last minute requests for wheelchair
and companion seating cannot be met because entire sections of accessible
seating will be lost when a platform is removed. See 73 FR 34508, 34546 (June
17, 2008). Further, use of temporary platforms allows facilities to limit
persons who need accessible seating to certain seating areas, and to relegate
accessible seating to less desirable locations. The use of temporary platforms
has the effect of neutralizing dispersion and other seating requirements
(e.g., line of sight) for wheelchair spaces and companion seats. Cf.
Independent Living Resources v. Oregon Arena Corp., 1 F. Supp. 2d 1159, 1171
(D. Or. 1998) (holding that while a public accommodation may “infill”
wheelchair spaces with removable seats when the wheelchair spaces are not
needed to accommodate individuals with disabilities, under certain
circumstances “[s]uch a practice might well violate the rule that wheelchair
spaces must be dispersed throughout the arena in a manner that is roughly
proportionate to the overall distribution of seating”). In addition, using
temporary platforms to convert unsold wheelchair spaces to conventional
seating undermines the flexibility facilities need to accommodate secondary
ticket market exchanges as required by Sec. 36.302(f)(7) of the final rule. As
the Department explained in the NPRM, however, this provision was not designed
to prohibit temporary seating that increases seating for events (e.g., placing
temporary seating on the floor of a basketball court for a concert).
Consequently, the final rule, at Sec. 36.406(f)(3), has been amended to
clarify that if an entire seating section is on a temporary platform for a
particular event, then wheelchair spaces and companion seats may also be in
that seating section. However, adding a temporary platform to create
wheelchair spaces and companion seats that are otherwise dissimilar from
nearby fixed seating and then simply adding a small number of additional seats
to the platform would not qualify as an “entire seating section” on the
platform. In addition, Sec. 36.406(f)(3) clarifies that facilities may fill in
wheelchair spaces with removable seats when the wheelchair spaces are not
needed by persons who use wheelchairs. The Department has been responsive to
assembly areas' concerns about reduced revenues due to unused accessible
seating. Accordingly, the Department has reduced scoping requirements
significantly--by almost half in large assembly areas--and determined that
allowing assembly areas to in-fill unsold wheelchair spaces with readily
removable temporary individual seats appropriately balances their economic
concerns with the rights of individuals with disabilities. See section 221.1
of the 2010 Standards. For stadium-style movie theaters, in Sec. 36.406(f)(4)
of the NPRM the Department proposed requiring placement of wheelchair seating
spaces and companion seats on a riser or cross-aisle in the stadium section of
the theater that satisfies at least one of the following criteria: (1) It is
located within the rear 60 percent of the seats provided in the auditorium; or
(2) It is located within the area of the auditorium where the vertical viewing
angles are between the 40th and 100th percentile of vertical viewing angles
for all seats in that theater as ranked from the first row (1st percentile) to
the back row (100th percentile). The vertical viewing angle is the angle
between a horizontal line perpendicular to the seated viewer's eye to the
screen and a line from the seated viewer's eye to the top of the screen. The
Department proposed this bright-line rule for two reasons: (1) the movie
theater industry petitioned for such a rule; and (2) the Department has
acquired expertise in the design of stadium-style theaters during its
litigation with several major movie theater chains. See United States. v. AMC
Entertainment, Inc., 232 F. Supp.2d 1092 (C.D. Cal. 2002), rev'd in part, 549
F.3d 760 (9th Cir. 2008); United States v. Cinemark USA, Inc., 348 F.3d 569
(6th Cir. 2003). Two industry commenters--at least one of whom otherwise
supported this rule--requested that the Department explicitly state that this
rule does not apply retroactively to existing theaters. Although this
provision on its face applies to new construction and alterations, these
commenters were concerned that the rule could be interpreted to apply
retroactively because of the Department's statements in the NPRM and ANPRM
that this bright line rule, although newly articulated, is not a new standard
but “merely codifi[es] longstanding Department requirement[s],” 73 FR 34508,
34534 (June 17, 2008), and does not represent a “substantive change from the
existing line-of-sight requirements” of section 4.33.3 of the 1991 Standards,
69 FR 58768, 58776 (Sept. 30, 2004). Although the Department intends for Sec.
36.406(f)(4) of this rule to apply prospectively to new construction and
alterations, this rule is not a departure from, and is consistent with, the
line- of-sight requirements in the 1991 Standards. The Department has always
interpreted the line-of-sight requirements in the 1991 Standards to require
viewing angles provided to patrons who use wheelchairs to be comparable to
those afforded to other spectators. Section 36.406(f)(4) merely represents the
application of these requirements to stadium-style movie theaters. One
commenter from a trade association sought clarification whether Sec.
36.406(f)(4) applies to stadium-style theaters with more than 300 seats, and
argued that it should not since dispersion requirements apply in those
theaters. The Department declines to limit this rule to stadium-style theaters
with 300 or fewer seats; stadium-style theaters of all sizes must comply with
this rule. So, for example, stadium-style theaters that must vertically
disperse wheelchair spaces and companion seats must do so within the
parameters of this rule. The NPRM included a provision that required assembly
areas with more than 5,000 seats to provide at least five wheelchair spaces
with at least three companion seats for each of those five wheelchair spaces.
The Department agrees with commenters who asserted that group seating is
better addressed through ticketing policies rather than design and has deleted
that provision from this section of the final rule.
§ 36.406(g) Medical Care Facilities
In the 1991 title III regulation, there was no provision addressing the
dispersion of accessible sleeping rooms in medical care facilities. The
Department is aware, however, of problems that individuals with disabilities
face in receiving full and equal medical care when accessible sleeping rooms
are not adequately dispersed. When accessible rooms are not fully dispersed, a
person with a disability is often placed in an accessible room in an area that
is not medically appropriate for his or her condition, and is thus denied
quick access to staff with expertise in that medical specialty and specialized
equipment. While the Access Board did not establish specific design
requirements for dispersion in the 2004 ADAAG, in response to extensive
comments in support of dispersion it added an advisory note, Advisory 223.1
General, encouraging dispersion of accessible rooms within the facility so
that accessible rooms are more likely to be proximate to appropriate qualified
staff and resources. In the NPRM, the Department sought additional comment on
the issue, asking whether it should require medical care facilities, such as
hospitals, to disperse their accessible sleeping rooms, and if so, by what
method (by specialty area, floor, or other criteria). All of the comments the
Department received on this issue supported dispersing accessible sleeping
rooms proportionally by specialty area. These comments from individuals,
organizations, and a building code association, argued that it would not be
difficult for hospitals to disperse rooms by specialty area, given the high
level of regulation to which hospitals are subject and the planning that
hospitals do based on utilization trends. Further, comments suggest that
without a requirement, it is unlikely that hospitals would disperse the rooms.
In addition, concentrating accessible rooms in one area perpetuates
segregation of individuals with disabilities, which is counter to the purpose
of the ADA. The Department has decided to require medical care facilities to
disperse their accessible sleeping rooms in a manner that is proportionate by
type of medical specialty. This does not require exact mathematical
proportionality, which at times would be impossible. However, it does require
that medical care facilities disperse their accessible rooms by medical
specialty so that persons with disabilities can, to the extent practical, stay
in an accessible room within the wing or ward that is appropriate for their
medical needs. The language used in this rule (“in a manner that is
proportionate by type of medical specialty”) is more specific than that used
in the NPRM (“in a manner that enables patients with disabilities to have
access to appropriate specialty services”) and adopts the concept of
proportionality proposed by the commenters. Accessible rooms should be
dispersed throughout all medical specialties, such as obstetrics, orthopedics,
pediatrics, and cardiac care.
Analysis and Commentary on the 2010
ADA Standards for Accessible Design
Appendix B to part 36: Analysis and Commentary on the 2010 ADA Standards for
Accessible Design
The following is a discussion of substantive changes in the scoping and
technical requirements for new construction and alterations resulting from the
adoption of new ADA Standards for Accessible Design (2010 Standards) in the
final rules for title II (28 CFR part 35) and title III (28 CFR part 36) of
the Americans with Disabilities Act (ADA). The full text of the 2010 Standards
is available for review at
www.ada.gov. In the Department´s revised ADA title II regulation, 28 CFR 35.104
Definitions, the Department defines the term "2010 Standards" to mean the 2010
ADA Standards for Accessible Design. The 2010 Standards consist of the 2004
ADA Accessibility Guidelines (ADAAG) and the requirements contained in 28 CFR
35.151. In the Department´s revised ADA title III regulation, 28 CFR 36.104
Definitions, the Department defines the term "2010 Standards" to mean the 2010
ADA Standards for Accessible Design. The 2010 Standards consist of the 2004
ADA Accessibility Guidelines (ADAAG) and the requirements contained in 28 CFR
part 36 subpart D. This summary addresses selected substantive changes between
the 1991 ADA Standards for Accessible Design (1991 Standards) codified at 28
CFR part 36, app. A (2009) and the 2010 Standards. Editorial changes are not
discussed. Scoping and technical requirements are discussed together, where
appropriate, for ease of understanding the requirements. In addition, this
document addresses selected public comments received by the Department in
response to its September 2004 Advance Notice of Proposed Rulemaking (ANPRM)
and its June 2008 Notice of Proposed Rulemaking (NPRM). The ANPRM and NPRM
issued by the Department concerning the proposed 2010 Standards stated that
comments received by the Access Board in response to its development of the
ADAAG upon which the 2010 Standards are based would be considered in the
development of the final Standards. Therefore, the Department will not restate
here all of the comments and responses to them issued by the Access Board. The
Department is supplementing the Access Board´s comments and responses with
substantive comments and responses here. Comments and responses addressed by
the Access Board that also were separately submitted to the Department will
not be restated in their entirety here.
Section-by-Section Analysis with Public Comments
Application and Administration
102 Dimensions for Adults and Children
Section 2.1 of the 1991 Standards stated that the specifications were based
upon adult dimensions and anthropometrics. The 1991 Standards did not provide
specific requirements for children´s elements or facilities. Section 102 of
the 2010 Standards states that the technical requirements are based on adult
dimensions and anthropometrics. In addition, technical requirements are also
provided based on children´s dimensions and anthropometrics for drinking
fountains, water closets and other elements located in toilet compartments,
lavatories and sinks, dining surfaces, and work surfaces.
103 Equivalent Facilitation
This section acknowledges that nothing in these requirements prevents the use
of designs, products, or technologies as alternatives to those prescribed,
provided that the alternatives result in substantially equivalent or greater
accessibility and usability. A commenter encouraged the Department to include
a procedure for determining equivalent facilitation. The Department believes
that the responsibility for determining and demonstrating equivalent
facilitation properly rests with the covered entity. The purpose of allowing
for equivalent facilitation is to encourage flexibility and innovation while
still ensuring access. The Department believes that establishing potentially
cumbersome bureaucratic provisions for reviewing requests for equivalent
facilitation is inappropriate.
104 Conventions
Dimensions. Section 104.1 of the 2010 Standards notes that
dimensions not stated as a "maximum" or "minimum" are absolute. Section
104.1.1 of the 2010 Standards provides that all dimensions are subject to
conventional industry tolerances except where the requirement is stated as a
range with specific minimum and maximum end points. A commenter stated that
the 2010 Standards restrict the application of construction tolerances only to
those few requirements that are expressed as an absolute dimension. This is an
incorrect interpretation of sections 104.1 and 104.1.1 of the 2010 Standards.
Construction and manufacturing tolerances apply to absolute dimensions as well
as to dimensions expressed as a maximum or minimum. When the requirement
states a specified range, such as in section 609.4 where grab bars must be
installed between 33 inches and 36 inches above the finished floor, that range
provides an adequate tolerance. Advisory 104.1.1 gives further guidance about
tolerances. Section 104.2 of the 2010 Standards provides that where the
required number of elements or facilities to be provided is determined by
calculations of ratios or percentages and remainders or fractions result, the
next greater whole number of such elements or facilities shall be provided.
Where the determination of the required size or dimension of an element or
facility involves ratios or percentages, rounding down for values less than
one-half is permissible. A commenter stated that it is customary in the
building code industry to round up rather than down for values less than
one-half. As noted here, where the 2010 Standards provide for scoping, any
resulting fractional calculations will be rounded to the next whole number.
The Department is retaining the portion of section 104.2 that permits rounding
down for values less than one-half where the determination of the required
size or dimension of an element or facility involves ratios or percentages.
Such practice is standard with the industry, and is in keeping with model
building codes.
105 Referenced Standards
Section 105 lists the industry requirements that are referenced in the 2010
Standards. This section also clarifies that where there is a difference
between a provision of the 2010 Standards and the referenced requirements, the
provision of the 2010 Standards applies.
106 Definitions
Various definitions have been added to the 2010 Standards and some definitions
have been deleted. One commenter asked that the term public right-of-way be
defined; others asked that various terms and words defined by the 1991
Standards, but which were eliminated from the 2010 Standards, plus other words
and terms used in the 2010 Standards, be defined. The Department believes that
it is not necessary to add definitions to this text because section 106.3 of
the 2010 Standards provides that the meanings of terms not specifically
defined in the 2010 Standards, in the Department´s ADA regulations, or in
referenced standards are to be defined by collegiate dictionaries in the sense
that the context implies. The Department believes that this provision
adequately addresses these commenters´ concerns.
Scoping and Technical Requirements
202 Existing Buildings and Facilities
Alterations. Under section 4.1.6(1)(c) of the 1991 Standards
if alterations to single elements, when considered together, amount to an
alteration of a room or space in a building or facility, the entire room or
space would have to be made accessible. This requirement was interpreted to
mean that if a covered entity chose to alter several elements in a room there
would come a point when so much work had been done that it would be considered
that the entire room or space would have to be made accessible. Under section
202.3 of the 2010 Standards entities can alter as many elements within a room
or space as they like without triggering a requirement to make the entire room
or space accessible based on the alteration of individual elements. This does
not, however, change the requirement that if the intent was to alter the
entire room or space, the entire room or space must be made accessible and
comply with the applicable requirements of Chapter 2 of the 2010 Standards.
Alterations to Primary Function Areas. Section 202.4 restates
a current requirement under title III, and therefore represents no change for
title III facilities or for those title II facilities that have elected to
comply with the 1991 Standards. However, under the revised title II
regulation, state and local government facilities that have previously elected
to comply with the Uniform Federal Accessibility Standards (UFAS) instead of
the 1991 Standards will no longer have that option, and thus will now be
subject to the path of travel requirement. The path of travel requirement
provides that when a primary function area of an existing facility is altered,
the path of travel to that area (including restrooms, telephones, and drinking
fountains serving the area) must also be made accessible, but only to the
extent that the cost of doing so does not exceed twenty percent (20%) of the
cost of the alterations to the primary function area. The UFAS requirements
for a substantial alteration, though different, may have covered some of the
items that will now be covered by the path of travel requirement.
Visible Alarms in Alterations to Existing Facilities. The
1991 Standards, at sections 4.1.3(14) and 4.1.6(1)(b), and sections 202.3 and
215.1 of the 2010 Standards require that when existing elements and spaces of
a facility are altered, the alterations must comply with new construction
requirements. Section 215.1 of the 2010 Standards adds a new exception to the
scoping requirement for visible alarms in existing facilities so that visible
alarms must be installed only when an existing fire alarm system is upgraded
or replaced, or a new fire alarm system is installed. Some commenters urged
the Department not to include the exception and to make visible alarms a
mandatory requirement for all spaces, both existing and new. Other commenters
said that the exception will make the safety of individuals with disabilities
dependent upon the varying age of existing fire alarm systems. Other
commenters suggested that including this requirement, even with the exception,
will result in significant cost to building owners and operators. The
Department believes that the language of the exception to section 215.1 of the
2010 Standards strikes a reasonable balance between the interests of
individuals with disabilities and those of the business community. If
undertaken at the time a system is installed, whether in a new facility or in
a planned system upgrade, the cost of adding visible alarms is reasonable.
Over time, existing facilities will become fully accessible to individuals who
are deaf or hard of hearing, and will add minimal costs to owners and
operators.
203 General Exceptions
Limited Access Spaces and Machinery Spaces. The 1991
Standards, at section 4.1.1, contain an exception that exempts
"non-occupiable" spaces that have limited means of access, such as ladders or
very narrow passageways, and that are visited only by service personnel for
maintenance, repair, or occasional monitoring of equipment, from all
accessibility requirements. Sections 203.4 and 203.5 of the 2010 Standards
expand this exception by removing the condition that the exempt spaces be
"non-occupiable," and by separating the other conditions into two independent
exceptions: one for spaces with limited means of access, and the other for
machinery spaces. More spaces are exempted by the exception in the 2010
Standards.
203, 206 and 215 Employee Work Areas
Common Use Circulation Paths in Employee Work Areas. The 1991
Standards at section 4.1.1(3), and the 2010 Standards at section 203.9,
require employee work areas in new construction and alterations
only to
be designed and constructed so that individuals with disabilities can
approach, enter, and exit the areas. Section 206.2.8 of the 2010 Standards
requires accessible common use circulation paths within employee work areas
unless they are subject to exceptions in sections 206.2.8, 403.5, 405.5, and
405.8. The ADA, 42 U.S.C. 12112 (b)(5)(A) and (B), requires employers to make
reasonable accommodations in the workplace for individuals with disabilities,
which may include modifications to work areas when needed. Providing increased
access in the facility at the time of construction or alteration will simplify
the process of providing reasonable accommodations when they are needed. The
requirement for accessible common use circulation paths will not apply to
existing facilities pursuant to the readily achievable barrier removal
requirement. The Department has consistently taken the position that barrier
removal requirements do not apply to areas used exclusively by employees
because the purpose of title III is to ensure that access is provided to
clients and customers. See Appendix B to the 1991 regulation implementing
title III, 28 CFR part 36. Several exceptions to section 206.2.8 of the 2010
Standards exempt common use circulation paths in employee work areas from the
requirements of section 402 where it may be difficult to comply with the
technical requirements for accessible routes due to the size or function of
the area:
-
Employee work areas, or portions of employee work areas, that are less
than 300 square feet and are elevated 7 inches or more above the ground or
finish floor, where elevation is essential to the function of the space,
are exempt.
-
Common use circulation paths within employee work areas that are less than
1,000 square feet and are defined by permanently installed partitions,
counters, casework, or furnishings are exempt. Kitchens in quick service
restaurants, cocktail bars, and the employee side of service counters are
frequently covered by this exception.
-
Common use circulation paths within employee work areas that are an
integral component of equipment are exempt. Common use circulation paths
within large pieces of equipment in factories, electric power plants, and
amusement rides are covered by this exception.
-
Common use circulation paths within exterior employee work areas that are
fully exposed to the weather are exempt. Farms, ranches, and outdoor
maintenance facilities are covered by this exception.
The 2010 Standards in sections 403.5 and 405.8 also contain exceptions to the
technical requirements for accessible routes for circulation paths in employee
work areas:
-
Machinery and equipment are permitted to reduce the clear width of common
use circulation paths where the reduction is essential to the function of
the work performed. Machinery and equipment that must be placed a certain
way to work properly, or for ergonomics or to prevent workplace injuries
are covered by this exception.
-
Handrails are not required on ramps, provided that they can be added in
the future.
Commenters stated that the requirements set out in the 2010 Standards for
accessible common use circulation paths in employee work areas are
inappropriate, particularly in commercial kitchens, storerooms, and behind
cocktail bars where wheelchairs would not be easily accommodated. These
commenters further urged the Department not to adopt a requirement that
circulation paths in employee work areas be at least 36 inches wide, including
those at emergency exits. These commenters misunderstand the scope of the
provision. Nothing in the 2010 Standards requires all circulation paths in
non-exempt areas to be accessible. The Department recognizes that building
codes and fire and life safety codes, which are adopted by all of the states,
require
primary circulation paths in facilities, including employee
work areas, to be at least 36 inches wide for purposes of emergency egress.
Accessible routes also are at least 36 inches wide. Therefore, the Department
anticipates that covered entities will be able to satisfy the requirement to
provide accessible circulation paths by ensuring that their required
primary circulation paths are accessible. Individual employee work
stations, such as a grocery checkout counter or an automobile service bay
designed for use by one person, do not contain common use circulation paths
and are not required to comply. Other work areas, such as stockrooms that
typically have narrow pathways between shelves, would be required to design
only one accessible circulation path into the stockroom. It would not be
necessary to make each circulation path in the room accessible. In alterations
it may be technically infeasible to provide accessible common use circulation
paths in some employee work areas. For example, in a stock room of a
department store significant existing physical constraints, such as having to
move walls to avoid the loss of space to store inventory, may mean that it is
technically infeasible (
see section 106.5 "Defined Terms" of the 2010
Standards) to make even the primary common use circulation path in that stock
room wide enough to be accessible. In addition, the 2010 Standards include
exceptions for common use circulation paths in employee work areas where it
may be difficult to comply with the technical requirements for accessible
routes due to the size or function of the areas. The Department believes that
these exceptions will provide the flexibility necessary to ensure that this
requirement does not interfere with legitimate business operations.
Visible Alarms. Section 215.3 of the 2010 Standards provides
that where employee work areas in newly constructed facilities have audible
alarm coverage they are required to have wiring systems that are capable of
supporting visible alarms that comply with section 702 of the 2010 Standards.
The 1991 Standards, at section 4.1.1(3), require visible alarms to be provided
where audible fire alarm systems are provided, but do not require areas used
only by employees as work areas to be equipped with accessibility features. As
applied to office buildings, the 1991 Standards require visible alarms to be
provided in public and common use areas such as hallways, conference rooms,
break rooms, and restrooms, where audible fire alarm systems are provided.
Commenters asserted that the requirements of section 215.3 of the 2010
Standards would be burdensome to meet. These commenters also raised concerns
that all employee work areas within existing buildings and facilities must be
equipped with accessibility features. The commenters´ concerns about section
215.3 of the 2010 Standards represent a misunderstanding of the requirements
applicable to employee work areas. Newly constructed buildings and facilities
merely are required to provide wiring so that visible alarm systems can be
added as needed to accommodate employees who are deaf or hard of hearing. This
is a minimal requirement without significant impact. The other issue in the
comments represents a misunderstanding of the Department´s existing regulatory
requirements. Employee common use areas in covered facilities (e.g
.,
locker rooms, break rooms, cafeterias, toilet rooms, corridors to exits, and
other common use spaces) were required to be accessible under the 1991
Standards; areas in which employees actually perform their jobs are required
to enable a person using a wheelchair or mobility device to approach, enter,
and exit the area. The 2010 Standards require increased access through the
accessible
common use circulation path requirement, but neither the
1991 Standards nor the 2010 Standards require employee work stations to be
accessible. Access to specific employee
work stations is governed by
title I of the ADA.
205 and 309 Operable Parts
Section 4.1.3, and more specifically sections 4.1.3(13), 4.27.3, and 4.27.4 of
the 1991 Standards, require operable parts on accessible elements, along
accessible routes, and in accessible rooms and spaces to comply with the
technical requirements for operable parts, including height and operation. The
1991 Standards, at section 4.27.3, contain an exception, " * * * where the use
of special equipment dictates otherwise or where electrical and communications
systems receptacles are not normally intended for use by building occupants,"
from the technical requirement for the height of operable parts. Section 205.1
of the 2010 Standards divides this exception into three exceptions covering
operable parts intended only for use by service or maintenance personnel,
electrical or communication receptacles serving a dedicated use, and floor
electrical receptacles. Operable parts covered by these new exceptions are
exempt from all of the technical requirements for operable parts in section
309. The 2010 Standards also add exceptions that exempt certain outlets at
kitchen counters; heating, ventilating and air conditioning diffusers;
redundant controls provided for a single element, other than light switches;
and exercise machines and equipment from all of the technical requirements for
operable parts. Exception 7, in section 205.1 of the 2010 Standards, exempts
cleats and other boat securement devices from the accessible height
requirement. Similarly, section 309.4 of the 2010 Standards exempts gas pump
nozzles, but only from the technical requirement for activating force.
Reach Ranges. The 1991 Standards set the maximum height for
side reach at 54 inches above the floor. The 2010 Standards, at section 308.3,
lower that maximum height to 48 inches above the finish floor or ground. The
2010 Standards also add exceptions, as discussed above, to the scoping
requirement for operable parts for certain elements that, among other things,
will exempt them from the reach range requirements in section 308. The 1991
Standards, at sections 4.1.3, 4.27.3, and 4.2.6, and the 2010 Standards, at
sections 205.1, 228.1, 228.2, 308.3, and 309.3, require operable parts of
accessible elements, along accessible routes, and in accessible rooms and
spaces to be placed within the forward or side-reach ranges specified in
section 308. The 2010 Standards also require at least five percent (5%) of
mailboxes provided in an interior location and at least one of each type of
depository, vending machine, change machine, and gas pump to meet the
technical requirements for a forward or a side reach. Section 4.2.6 of the
1991 Standards specifies a maximum 54-inch high side reach and a minimum
9-inch low side reach for an unobstructed reach depth of 10 inches maximum.
Section 308.3.1 of the 2010 Standards specifies a maximum 48-inch high side
reach and a minimum 15-inch low side reach where the element being reached for
is unobstructed. Section 308.3.1, Exception 1, permits an obstruction that is
no deeper than 10 inches between the edge of the clear floor or ground space
and the element that the individual with a disability is trying to reach.
Changes in the side-reach range for new construction and alterations in the
2010 Standards will affect a variety of building elements such as light
switches, electrical outlets, thermostats, fire alarm pull stations, card
readers, and keypads. Commenters were divided in their views about the changes
to the unobstructed side-reach range. Disability advocacy groups and others,
including individuals of short stature, supported the modifications to the
proposed reach range requirements. Other commenters stated that the new reach
range requirements will be burdensome for small businesses to comply with.
These comments argued that the new reach range requirements restrict design
options, especially in residential housing. The Department continues to
believe that data submitted by advocacy groups and others provides compelling
evidence that lowered reach range requirements will better serve significantly
greater numbers of individuals with disabilities, including individuals of
short stature, persons with limited upper body strength, and others with
limited use of their arms and fingers. The change to the side-reach range was
developed by the Access Board over a prolonged period in which there was
extensive public participation. This process did not produce any significant
data to indicate that applying the new unobstructed side-reach range
requirement in new construction or during alterations would impose a
significant burden.
206 and Chapter 4 Accessible Routes
Slope. The 2010 Standards provide, at section 403.3, that the
cross slope of walking surfaces not be steeper than 1:48. The 1991 Standards´
cross slope requirement was that it not exceed 1:50. A commenter recommended
increasing the cross slope requirement to allow a maximum of 1/2 inch per foot
(1:24) to prevent imperfections in concrete surfaces from ponding water. The
Department continues to believe that the requirement that a cross slope not be
steeper than 1:48 adequately provides for water drainage in most situations.
The suggested changes would double the allowable cross slope and create a
significant impediment for many wheelchair users and others with a mobility
disability.
Accessible Routes from Site Arrival Points and Within Sites. The 1991 Standards, at sections 4.1.2(1) and (2), and the 2010 Standards, at
sections 206.2.1 and 206.2.2, require that at least one accessible route be
provided within the site from site arrival points to an accessible building
entrance and that at least one accessible route connect accessible facilities
on the same site. The 2010 Standards also add two exceptions that exempt site
arrival points and accessible facilities within a site from the accessible
route requirements where the only means of access between them is a vehicular
way that does not provide pedestrian access. Commenters urged the Department
to eliminate the exception that exempts site arrival points and accessible
facilities from the accessible route requirements where the only means of
access between them is a vehicular way not providing pedestrian access. The
Department declines to accept this recommendation because the Department
believes that its use will be limited. If it can be reasonably anticipated
that the route between the site arrival point and the accessible facilities
will be used by pedestrians, regardless of whether a pedestrian route is
provided, then this exception will not apply. It will apply only in the
relatively rare situations where the route between the site arrival point and
the accessible facility dictates vehicular access – for example, an office
complex on an isolated site that has a private access road, or a self-service
storage facility where all users are expected to drive to their storage units.
Another commenter suggested that the language of section 406.1 of the 2010
Standards is confusing because it states that curb ramps on accessible routes
shall comply with 406, 405.2 through 405.5, and 405.10. The 1991 Standards
require that curb ramps be provided wherever an accessible route crosses a
curb. The Department declines to change this language because the change is
purely editorial, resulting from the overall changes in the format of the 2010
Standards. It does not change the substantive requirement. In the 2010
Standards all elements on a required accessible route must be accessible;
therefore, if the accessible route crosses a curb, a curb ramp must be
provided.
Areas of Sport Activity. Section 206.2.2 of the 2010
Standards requires at least one accessible route to connect accessible
buildings, facilities, elements, and spaces on the same site. Advisory section
206.2.2 adds the explanation that an accessible route must connect the
boundary of each area of sport activity (e.g., courts and playing fields,
whether indoor or outdoor). Section 206.2.12 of the 2010 Standards further
requires that in court sports the accessible route must directly connect both
sides of the court.
Limited-Use/Limited-Application Elevators, Destination-Oriented Elevators
and Private Residence Elevators.
The 1991 Standards, at section 4.1.3(5), and the 2010 Standards, at sections
206.2 and 206.6, include exceptions to the scoping requirement for accessible
routes that exempt certain facilities from connecting each story with an
elevator. If a facility is exempt from the scoping requirement, but
nonetheless installs an elevator, the 1991 Standards require the elevator to
comply with the technical requirements for elevators. The 2010 Standards add a
new exception that allows a facility that is exempt from the scoping
requirement to install a limited-use/limited-application (LULA) elevator. LULA
elevators are also permitted in the 1991 Standards and the 2010 Standards as
an alternative to platform lifts. The 2010 Standards also add a new exception
that permits private residence elevators in multi-story dwelling and transient
lodging units. The 2010 Standards contain technical requirements for LULA
elevators at section 408 and private residence elevators at section 409.
Section 407.2.1.4 of the 2010 Standards includes an exception to the technical
requirements for locating elevator call buttons for destination-oriented
elevators. The advisory at section 407.2.1.4 describes lobby controls for
destination-oriented elevator systems. Many elevator manufacturers have
recently developed these new "buttonless" elevator control systems. These new,
more efficient elevators are usually found in high-rise buildings that have
several elevators. They require passengers to enter their destination floor on
an entry device, usually a keypad, in the elevator lobby. The system then
sends the most efficient car available to take all of the passengers going to
the sixth floor, for example, only to the sixth floor, without making stops at
the third, fourth, and fifth floors on the way to the sixth floor. The
challenge for individuals who are blind or have low vision is how to know
which elevator car to enter, after they have entered their destination floor
into the keypad. Commenters requested that the Department impose a moratorium
on the installation of destination-oriented elevators arguing that this new
technology presents wayfinding challenges for persons who are blind or have
low vision. Section 407.2.1.5 of the 2010 Standards allows
destination-oriented elevators to not provide call buttons with visible
signals to indicate when each call is registered and when each call is
answered
provided that visible and audible signals, compliant with
407.2.2 of the 2010 Standards, indicating which elevator car to enter, are
provided. This will require the responding elevator car to automatically
provide audible and visible communication so that the system will always
verbally and visually indicate which elevator car to enter. As with any new
technology, all users must have time to become acquainted with how to use
destination-oriented elevators. The Department will monitor the use of this
new technology and work with the Access Board so that there is not a decrease
in accessibility as a result of permitting this new technology to be
installed.
Accessible Routes to Tiered Dining Areas in Sports Facilities.
The 1991 Standards, at sections 4.1.3(1) and 5.4, and section 206.2.5 of the
2010 Standards require an accessible route to be provided to all dining areas
in new construction, including raised or sunken dining areas. The 2010
Standards add a new exception for tiered dining areas in sports facilities.
Dining areas in sports facilities are typically integrated into the seating
bowl and are tiered to provide adequate lines of sight for individuals with
disabilities. The new exception requires accessible routes to be provided to
at least 25 percent (25%) of the tiered dining areas in sports facilities.
Each tier must have the same services and the accessible routes must serve the
accessible seating.
Accessible Routes to Press Boxes. The 1991 Standards, at
sections 4.1.1(1) and 4.1.3(1), cover all areas of newly constructed
facilities required to be accessible, and require an accessible route to
connect accessible entrances with all accessible spaces and elements within
the facility. Section 201.1 of the 2010 Standards requires that all areas of
newly designed and constructed buildings and facilities and altered portions
of existing buildings and facilities be accessible. Sections 206.2.7(1) and
(2) of the 2010 Standards add two exceptions that exempt small press boxes
that are located in bleachers with entrances on only one level, and small
press boxes that are free-standing structures elevated 12 feet or more above
grade, from the accessible route requirement when the aggregate area of all
press boxes in a sports facility does not exceed 500 square feet. The
Department anticipates that this change will significantly reduce the economic
impact on smaller sports facilities, such as those associated with high
schools or community colleges.
Public Entrances. The 1991 Standards, at sections 4.1.3(8)
and 4.1.6(1)(h), require at least fifty percent (50%) of public entrances to
be accessible. Additionally, the 1991 Standards require the number of
accessible public entrances to be equivalent to the number of exits required
by applicable building and fire codes. With very few exceptions, building and
fire codes require at least two exits to be provided from spaces within a
building and from the building itself. Therefore, under the 1991 Standards
where two public entrances are planned in a newly constructed facility, both
entrances are required to be accessible. Instead of requiring accessible
entrances based on the number of public entrances provided or the number of
exits required (whichever is greater), section 206.4.1 of the 2010 Standards
requires at least sixty percent (60%) of public entrances to be accessible.
The revision is intended to achieve the same result as the 1991 Standards.
Thus, under the 2010 Standards where two public entrances are planned in a
newly constructed facility, both entrances must be accessible. Where multiple
public entrances are planned to serve different site arrival points, the 1991
Standards, at section 4.1.2(1), and section 206.2.1 of the 2010 Standards
require at least one accessible route to be provided from each type of site
arrival point provided, including accessible parking spaces, accessible
passenger loading zones, public streets and sidewalks, and public
transportation stops, to an accessible public entrance that serves the site
arrival point. Commenters representing small businesses recommended retaining
the 1991 requirement for fifty percent (50%) of public entrances of covered
entities to be accessible. These commenters also raised concerns about the
impact upon existing facilities of the new sixty percent (60%) requirement.
The Department believes that these commenters misunderstand the 1991
Standards. As explained above, the requirements of the 1991 Standards
generally require more than fifty percent (50%) of entrances in small
facilities to be accessible. Model codes require that most buildings have more
than one means of egress. Most buildings have more than one entrance, and the
requirements of the 1991 Standards typically resulted in these buildings
having more than one accessible entrance. Requiring at least sixty percent
(60%) of public entrances to be accessible is not expected to result in a
substantial increase in the number of accessible entrances compared to the
requirements of the 1991 Standards. In some very large facilities this change
may result in fewer accessible entrances being required by the 2010 Standards.
However, the Department believes that the realities of good commercial design
will result in more accessible entrances being provided for the convenience of
all users. The 1991 Standards and the 2010 Standards also contain exceptions
that limit the number of accessible entrances required in alterations to
existing facilities. When entrances to an existing facility are altered and
the facility has an accessible entrance, the entrance being altered is not
required to be accessible, unless a primary function area also is altered and
then an accessible path of travel must be provided to the primary function
area to the extent that the cost to do so is not disproportionate to the
overall cost of the alteration.
Alterations to Existing Elevators. When a single space or
element is altered, the 1991 Standards, at sections 4.1.6(1)(a) and (b),
require the space or element to be made accessible. When an element in one
elevator is altered, the 2010 Standards, at section 206.6.1, require the same
element to be altered in all elevators that are programmed to respond to the
same call button as the altered elevator. The 2010 Standards, at sections
407.2.1 - 407.4.7.1.2, also contain exceptions to the technical requirements
for elevators when existing elevators are altered that minimize the impact of
this change. Commenters expressed concerns about the requirement that when an
element in one elevator is altered, the 2010 Standards, at section 206.6.1,
will require the same element to be altered in all elevators that are
programmed to respond to the same call button as the altered elevator.
Commenters noted that such a requirement is burdensome and will result in
costly efforts without significant benefit to individuals with disabilities.
The Department believes that this requirement is necessary to ensure that when
an individual with a disability presses a call button, an accessible elevator
will arrive. Without this requirement, individuals with disabilities would
have to wait unnecessarily for an accessible elevator to make its way to them
arbitrarily. The Department also believes that the effort required to meet
this provision is minimal in the majority of situations because it is typical
to upgrade all of the elevators in a bank at the same time.
Accessible Routes in Dwelling Units with Mobility Features.
Sections 4.34.1 and 4.34.2 of the UFAS require the living area, kitchen and
dining area, bedroom, bathroom, and laundry area, where provided, in covered
dwelling units with mobility features to be on an accessible route. Where
covered dwelling units have two or more bedrooms, at least two bedrooms are
required to be on an accessible route. The 2010 Standards at sections
233.3.1.1, 809.1, 809.2, 809.2.1, and 809.4 will require all spaces and
elements within dwelling units with mobility features to be on an accessible
route. These changes exempt unfinished attics and unfinished basements from
the accessible route requirement. Section 233.3.5 of the 2010 Standards also
includes an exception to the dispersion requirement that permits accessible
single-story dwelling units to be constructed, where multi-story dwelling
units are one of the types of units provided.
Location of Accessible Routes. Section 4.3.2(1) of the 1991
Standards requires accessible routes connecting site arrival points and
accessible building entrances to coincide with general circulation paths, to
the maximum extent feasible. The 2010 Standards require all accessible routes
to coincide with or be located in the same general area as general circulation
paths. Additionally, a new provision specifies that where a circulation path
is interior, the required accessible route must also be located in the
interior of the facility. The change affects a limited number of buildings.
Section 206.3 of the 2010 Standards requires all accessible routes to coincide
with or be located in the same general area as general circulation paths.
Designing newly constructed interior accessible routes to coincide with or to
be located in the same area as general circulation paths will not typically
present a difficult design challenge and is expected to impose limited design
constraints. The change will have no impact on exterior accessible routes. The
1991 Standards and the 2010 Standards also require accessible routes to be
located in the interior of the facility where general circulation paths are
located in the interior of the facility. The revision affects a limited number
of buildings.
Location of Accessible Routes to Stages. The 1991 Standards
at section 4.33.5 require an accessible route to connect the accessible
seating and the performing area. Section 206.2.6 of the 2010 Standards
requires the accessible route to directly connect the seating area and the
accessible seating, stage, and all areas of the stage, where a circulation
path directly connects the seating area and the stage. Both the 1991 Standards
and the 2010 Standards also require an accessible route to connect the stage
and ancillary areas, such as dressing rooms, used by performers. The 2010
Standards do not require an additional accessible route to be provided to the
stage. Rather, the changes specify where the accessible route to the stage,
which is required by the 1991 Standards, must be located.
207 Accessible Means of Egress
General. The 1991 Standards at sections 4.1.3(9);
4.1.6(1)(g); and 4.3.10 establish scoping and technical requirements for
accessible means of egress. Section 207.1 of the 2010 Standards reference the
International Building Code (IBC) for scoping and technical requirements for
accessible means of egress. The 1991 Standards require the same number of
accessible means of egress to be provided as the number of exits required by
applicable building and fire codes. The IBC requires at least one accessible
means of egress and at least two accessible means of egress where more than
one means of egress is required by other sections of the building code. The
changes in the 2010 Standards are expected to have minimal impact since the
model fire and life safety codes, which are adopted by all of the states,
contain equivalent requirements with respect to the number of accessible means
of egress. The 1991 Standards require areas of rescue assistance or horizontal
exits in facilities with levels above or below the level of exit discharge.
Areas of rescue assistance are spaces that have direct access to an exit,
stair, or enclosure where individuals who are unable to use stairs can go to
call for assistance and wait for evacuation. The 2010 Standards incorporate
the requirements established by the IBC. The IBC requires an evacuation
elevator designed with standby power and other safety features that can be
used for emergency evacuation of individuals with disabilities in facilities
with four or more stories above or below the exit discharge level, and allows
exit stairways and evacuation elevators to be used as an accessible means of
egress in conjunction with areas of refuge or horizontal exits. The change is
expected to have minimal impact since the model fire and life safety codes,
adopted by most states, already contain parallel requirements with respect to
evacuation elevators. The 1991 Standards exempt facilities equipped with a
supervised automatic sprinkler system from providing areas of rescue
assistance, and also exempt alterations to existing facilities from providing
an accessible means of egress. The IBC exempts buildings equipped with a
supervised automatic sprinkler system from certain technical requirements for
areas of refuge, and also exempts alterations to existing facilities from
providing an accessible means of egress. The 1991 and 2010 Standards require
signs that provide direction to or information about functional spaces to meet
certain technical requirements. The 2010 Standards, at section 216.4, address
exit signs. This section is consistent with the requirements of the IBC. Signs
used for means of egress are covered by this scoping requirement. The
requirements in the 2010 Standards require tactile signs complying with
sections 703.1, 703.2 and 703.5 at doors at exit passageways, exit discharge,
and at exit stairways. Directional exit signs and signs at areas of refuge
required by section 216.4.3 must have visual characters and features complying
with section 703.5.
Standby Power for Platform Lifts. The 2010 Standards at
section 207.2 require standby power to be provided for platform lifts that are
permitted to serve as part of an accessible means of egress by the IBC. The
IBC permits platform lifts to serve as part of an accessible means of egress
in a limited number of places where platform lifts are allowed in new
construction. The 1991 Standards, at 4.1.3 (5) Exception 4 (a) through (d),
and the 2010 Standards, at sections 206.7.1 through 206.7.10, similarly limit
the places where platform lifts are allowed in new construction. Commenters
urged the Department to reconsider provisions that would require standby power
to be provided for platform lifts. Concerns were raised that ensuring standby
power would be too burdensome. The Department views this issue as a
fundamental life safety issue. Lift users face the prospect of being trapped
on the lift in the event of a power failure if standby power is not provided.
The lack of standby power could be life-threatening in situations where the
power failure is associated with a fire or other emergency. The use of a
platform lift is generally only one of the options available to covered
entities. Covered entities that are concerned about the costs associated with
maintaining standby power for a lift may wish to explore design options that
would incorporate the use of a ramp.
208 and 502 Parking Spaces
General. Where parking spaces are provided, the 1991
Standards, at sections 4.1.2 (5)(a) and (7) and 7(a), and the 2010 Standards,
at section 208.1, require a specified number of the parking spaces to be
accessible. The 2010 Standards, at section 208, include an exception that
exempts parking spaces used exclusively for buses, trucks, delivery vehicles,
law enforcement vehicles, or for purposes of vehicular impound, from the
scoping requirement for parking spaces, provided that when these lots are
accessed by the public the lot has an accessible passenger loading zone. The
2010 Standards require accessible parking spaces to be identified by signs
that display the International Symbol of Accessibility. Section 216.5,
Exceptions 1 and 2, of the 2010 Standards exempt certain accessible parking
spaces from this signage requirement. The first exception exempts sites that
have four or fewer parking spaces from the signage requirement. Residential
facilities where parking spaces are assigned to specific dwelling units are
also exempted from the signage requirement. Commenters stated that the first
exception, by allowing a small parking lot with four or fewer spaces not to
post a sign at its one accessible space, is problematic because it could allow
all drivers to park in accessible parking spaces. The Department believes that
this exception provides necessary relief for small business entities that may
otherwise face the prospect of having between twenty-five percent (25%) and
one hundred percent (100%) of their limited parking area unavailable to their
customers because they are reserved for the exclusive use of persons whose
vehicles display accessible tags or parking placards. The 2010 Standards still
require these businesses to ensure that at least one of their available
parking spaces is designed to be accessible. A commenter stated that
accessible parking spaces must be clearly marked. The Department notes that
section 502.6 of the 2010 Standards provides that accessible parking spaces
must be identified by signs that include the International Symbol of
Accessibility. Also, section 502.3.3 of the 2010 Standards requires that
access aisles be marked so as to discourage parking in them.
Access Aisle. Section 502.3 of the 2010 Standards requires
that an accessible route adjoin each access aisle serving accessible parking
spaces. The accessible route connects each access aisle to accessible
entrances. Commenters questioned why the 2010 Standards would permit an
accessible route used by individuals with disabilities to coincide with the
path of moving vehicles. The Department believes that the 2010 Standards
appropriately recognize that not all parking facilities provide separate
pedestrian routes. Section 502.3 of the 2010 Standards provides the
flexibility necessary to permit designers and others to determine the most
appropriate location of the accessible route to the accessible entrances. If
all pedestrians using the parking facility are expected to share the vehicular
lanes, then the ADA permits covered entities to use the vehicular lanes as
part of the accessible route. The advisory note in section 502.3 of the 2010
Standards, however, calls attention to the fact that this practice, while
permitted, is not ideal. Accessible parking spaces must be located on the
shortest accessible route of travel to an accessible entrance. Accessible
parking spaces and the required accessible route should be located where
individuals with disabilities do not have to cross vehicular lanes or pass
behind parked vehicles to have access to an accessible entrance. If it is
necessary to cross a vehicular lane because, for example, local fire engine
access requirements prohibit parking immediately adjacent to a building, then
a marked crossing running perpendicular to the vehicular route should be
included as part of the accessible route to an accessible entrance.
Van Accessible Parking Spaces. The 1991 Standards, at
sections 4.1.2 (5)(b), 4.6.3, 4.6.4, and 4.6.5, require one in every eight
accessible parking spaces to be van accessible. Section 208.2.4 of the 2010
Standards requires one in every six accessible parking spaces to be van
accessible. A commenter asked whether automobiles other than vans may park in
van accessible parking spaces. The 2010 Standards do not prohibit automobiles
other than vans from using van accessible parking spaces. The Department does
not distinguish between vehicles that are actual "vans" versus other vehicles
such as trucks, station wagons, sport utility vehicles, etc. since many
vehicles other than vans may be used by individuals with disabilities to
transport mobility devices. Commenters´ opinions were divided on this point.
Facility operators and others asked for a reduction in the number of required
accessible parking spaces, especially the number of van accessible parking
spaces, because they claimed these spaces often are not used. Individuals with
disabilities, however, requested an increase in the scoping requirements for
these parking spaces. The Department is aware that a strong difference of
opinion exists between those who use such spaces and those who must provide or
maintain them. Therefore, the Department did not increase the total number of
accessible spaces required. The only change was to increase the proportion of
spaces that must be accessible to vans and other vehicles equipped to
transport mobility devices.
Direct Access Entrances from Parking Structures. Where levels
in a parking garage have direct connections for pedestrians to another
facility, the 1991 Standards, at section 4.1.3(8)(b)(i), require at least one
of the direct connections to be accessible. The 2010 Standards, at section
206.4.2, require all of these direct connections to be accessible.
209 and 503 Passenger Loading Zones and Bus Stops
Passenger Loading Zones at Medical Care and Long-Term Care
Facilities.
Sections 6.1 and 6.2 of the 1991 Standards and section 209.3 of the 2010
Standards require medical care and long-term care facilities, where the period
of stay exceeds 24 hours, to provide at least one accessible passenger loading
zone at an accessible entrance. The 1991 Standards also require a canopy or
roof overhang at this passenger loading zone. The 2010 Standards do not
require a canopy or roof overhang. Commenters urged the Department to
reinstate the requirement for a canopy or roof overhang at accessible
passenger loading zones at medical care and long-term care facilities. While
the Department recognizes that a canopy or roof overhang may afford useful
protection from inclement weather conditions to everyone using a facility, it
is not clear that the absence of such protection would impede access by
individuals with disabilities. Therefore, the Department declined to reinstate
that requirement.
Passenger Loading Zones. Where passenger loading zones are
provided, the 1991 Standards, at sections 4.1.2(5) and 4.6.6, require at least
one passenger loading zone to be accessible. Sections 209.2.1 and 503 of the
2010 Standards, require facilities such as airport passenger terminals that
have long, continuous passenger loading zones to provide one accessible
passenger loading zone in every continuous 100 linear feet of loading zone
space. The 1991 Standards and the 2010 Standards both include technical
requirements for the vehicle pull-up space (96 inches wide minimum and 20 feet
long minimum). Accessible passenger loading zones must have an access aisle
that is 60 inches wide minimum and extends the full length of the vehicle
pull-up space. The 1991 Standards permit the access aisle to be on the same
level as the vehicle pull-up space, or on the sidewalk. The 2010 Standards
require the access aisle to be on the same level as the vehicle pull-up space
and to be marked so as to discourage parking in the access aisle. Commenters
expressed concern that certain covered entities, particularly airports, cannot
accommodate the requirements of the 2010 Standards to provide passenger
loading zones, and urged a revision that would require one accessible
passenger loading zone located in reasonable proximity to each building
entrance served by the curb. Commenters raised a variety of issues about the
requirements at section 503 of the 2010 Standards stating that the
requirements for an access aisle, width, length, and marking of passenger
loading zones are not clear, do not fully meet the needs of individuals with
disabilities, may run afoul of state or local requirements, or may not be
needed because many passenger loading zones are typically staffed by doormen
or valet parkers. The wide range of opinions expressed in these comments
indicates that this provision is controversial. However, none of these
comments provided sufficient data to enable the Department to determine that
the requirement is not appropriate.
Valet Parking and Mechanical Access Parking Garages. The 1991
Standards, at sections 4.1.2(5)(a) and (e), and sections 208.2, 209.4, and
209.5 of the 2010 Standards require parking facilities that provide valet
parking services to have an accessible passenger loading zone. The 2010
Standards extend this requirement to mechanical access parking garages. The
1991 Standards contained an exception that exempted valet parking facilities
from providing accessible parking spaces. The 2010 Standards eliminate this
exception. The reason for not retaining the provision is that valet parking is
a service, not a facility type. Commenters questioned why the exception for
valet parking facilities from providing accessible parking spaces was
eliminated. The provision was eliminated because valet parkers may not have
the skills necessary to drive a vehicle that is equipped to be accessible,
including use of hand controls, or when a seat is not present to accommodate a
driver using a wheelchair. In that case, permitting the individual with a
disability to self-park may be a required reasonable modification of policy by
a covered entity.
210 and 504 Stairways
The 1991 Standards require stairs to be accessible only when they provide
access to floor levels not otherwise connected by an accessible route
(e.g
., where the accessible route is provided by an elevator, lift, or
ramp). The 2010 Standards, at sections 210.1 and 504, require all
newly constructed stairs that are part of a
means of egress to
comply with the requirements for accessible stairs, which include requirements
for accessible treads, risers, and handrails. In existing facilities, where
floor levels are connected by an accessible route, only the handrail
requirement will apply when the stairs are altered. Exception 2 to section
210.1 of the 2010 Standards permits altered stairs to not comply with the
requirements for accessible treads and risers where there is an accessible
route between floors served by the stairs. Most commenters were in favor of
this requirement for handrails in alterations and stated that adding handrails
to stairs during alterations would be feasible and not costly while providing
important safety benefits. The Department believes that it strikes an
appropriate balance by focusing the expanded requirements on new construction.
The 2010 Standards apply to stairs which are part of a required means of
egress. Few stairways are not part of a means of egress. The 2010 Standards
are consistent with most building codes which do not exempt stairways when the
route is also served by a ramp or elevator.
211 and 602 Drinking Fountains
Sections 4.1.3(10) and 4.15 of the 1991 Standards and sections 211 and 602 of
the 2010 Standards require drinking fountains to be provided for persons who
use wheelchairs and for others who stand. The 1991 Standards require wall and
post-mounted cantilevered drinking fountains mounted at a height for
wheelchair users to provide clear floor space for a forward approach with knee
and toe clearance and free standing or built-in drinking fountains to provide
clear floor space for a parallel approach. The 2010 Standards require drinking
fountains mounted at a height for wheelchair users to provide clear floor
space for a forward approach with knee and toe clearance, and include an
exception for a parallel approach for drinking fountains installed at a height
to accommodate very small children. The 2010 Standards also include a
technical requirement for drinking fountains for standing persons.
212 and 606 Kitchens, Kitchenettes, Lavatories, and Sinks
The 1991 Standards, at sections 4.24, and 9.2.2(7), contain technical
requirements for sinks and only have specific scoping requirements for sinks
in transient lodging. Section 212.3 of the 2010 Standards requires at least
five percent (5%) of sinks in each accessible space to comply with the
technical requirements for sinks. The technical requirements address clear
floor space, height, faucets, and exposed pipes and surfaces. The 1991
Standards, at section 4.24, and the 2010 Standards, at section 606, both
require the clear floor space at sinks to be positioned for a forward approach
and knee and toe clearance to be provided under the sink. The 1991 Standards,
at section 9.2.2(7), allow the clear floor space at kitchen sinks and wet bars
in transient lodging guest rooms with mobility features to be positioned for
either a forward approach with knee and toe clearance or for a parallel
approach. The 2010 Standards include an exception that permits the clear floor
space to be positioned for a parallel approach at kitchen sinks in any space
where a cook top or conventional range is not provided, and at a wet bar. A
commenter stated that it is unclear what the difference is between a sink and
a lavatory, and that this is complicated by requirements that apply to sinks
(five percent (5%) accessible) and lavatories (at least one accessible). The
term "lavatory" generally refers to the specific type of plumbing fixture
required for hand washing in toilet and bathing facilities. The more generic
term "sink" applies to all other types of sinks located in covered facilities.
A commenter recommended that the mounting height of sinks and lavatories
should take into consideration the increased use of three-wheeled scooters and
some larger wheelchairs. The Department is aware that the use of three-wheeled
scooters and larger wheelchairs may be increasing and that some of these
devices may require changes in space requirements in the future. The Access
Board is funding research to obtain data that may be used to develop design
guidelines that provide access to individuals using these mobility devices.
213, 603, 604, and 608 Toilet and Bathing Facilities, Rooms, and
Compartments
General. Where toilet facilities and bathing facilities are
provided, they must comply with section 213 of the 2010 Standards. A commenter
recommended that all accessible toilet facilities, toilet rooms, and
compartments should be required to have signage indicating that such spaces
are restricted solely for the use of individuals with disabilities. The
Department believes that it is neither necessary nor appropriate to restrict
the use of accessible toilet facilities. Like many other facilities designed
to be accessible, accessible toilet facilities can and do serve a wide range
of individuals with and without disabilities. A commenter recommended that
more than one wheelchair accessible compartment be provided in toilet rooms
serving airports and train stations because these compartments are likely to
be occupied by individuals with luggage and persons with disabilities often
take longer to use them. The Access Board is examining airport terminal
accessibility as part of an ongoing effort to facilitate accessibility and
promote effective design. As part of these efforts, the Access Board will
examine requirements for accessible toilet compartments in larger airport
restrooms. The Department declines to change the scoping for accessible toilet
compartments at this time.
Ambulatory Accessible Toilet Compartments. Section 213.3.1 of
the 2010 Standards requires multi-user men´s toilet rooms, where the total of
toilet compartments and urinals is six or more, to contain at least one
ambulatory accessible compartment. The 1991 Standards count only toilet stalls
(compartments) for this purpose. The 2010 Standards establish parity between
multi-user women´s toilet rooms and multi-user men´s toilet rooms with respect
to ambulatory accessible toilet compartments.
Urinals. Men´s toilet rooms with only one urinal will no
longer be required to provide an accessible urinal under the 2010 Standards.
Such toilet rooms will still be required to provide an accessible toilet
compartment. Commenters urged that the exception be eliminated. The Department
believes that this change will provide flexibility to many small businesses
and it does not alter the requirement that all common use restrooms must be
accessible.
Multiple Single-User Toilet Rooms. Where multiple single-user
toilet rooms are clustered in a single location, fifty percent (50%), rather
than the one hundred percent (100%) required by the 1991 Standards, are
required to be accessible by section 213.2, Exception 4 of the 2010 Standards.
Section 216.8 of the 2010 Standards requires that accessible single-user
toilet rooms must be identified by the International Symbol of Accessibility
where all single-user toilet rooms are not accessible.
Hospital Patient Toilet Rooms. An exception was added in
section 223.1 of the 2010 Standards to allow toilet rooms that are part of
critical or intensive care patient sleeping rooms to no longer be required to
provide mobility features.
Water Closet Location and Rear Grab Bar. Section 604.2 of the
2010 Standards allows greater flexibility for the placement of the centerline
of wheelchair accessible and ambulatory accessible water closets. Section
604.5.2, Exception 1 permits a shorter grab bar on the rear wall where there
is not enough wall space due to special circumstances (e.g., when a lavatory
or other recessed fixture is located next to the water closet and the wall
behind the lavatory is recessed so that the lavatory does not overlap the
required clear floor space at the water closet). The 1991 Standards contain no
exception for grab bar length, and require the water closet centerline to be
exactly 18 inches from the side wall, while the 2010 Standards requirement
allows the centerline to be between 16 and 18 inches from the side wall in
wheelchair accessible toilet compartments and 17 to 19 inches in ambulatory
accessible toilet compartments.
Water Closet Clearance. Section 604.3 of the 2010 Standards
represents a change in the accessibility requirements where a lavatory is
installed adjacent to the water closet. The 1991 Standards allow the nearest
side of a lavatory to be placed 18 inches minimum from the water closet
centerline and 36 inches minimum from the side wall adjacent to the water
closet. However, locating the lavatory so close to the water closet prohibits
many individuals with disabilities from using a side transfer. To allow
greater transfer options, including side transfers, the 2010 Standards
prohibit lavatories from overlapping the clear floor space at water closets,
except in covered residential dwelling units. A majority of commenters,
including persons who use wheelchairs, strongly agreed with the requirement to
provide enough space for a side transfer. These commenters believed that the
requirement will increase the usability of accessible single-user toilet rooms
by making side transfers possible for many individuals who use wheelchairs and
would have been unable to transfer to a water closet using a side transfer
even if the water closet complied with the 1991 Standards. In addition, many
commenters noted that the additional clear floor space at the side of the
water closet is also critical for those providing assistance with transfers
and personal care for persons with disabilities. Numerous comments noted that
this requirement is already included in other model accessibility standards
and many state and local building codes and its adoption in the 2010 Standards
is a important part of harmonization efforts. The Department agrees that the
provision of enough clear floor space to permit side transfers at water
closets is an important feature that must be provided to ensure access for
persons with disabilities in toilet and bathing facilities. Furthermore, the
adoption of this requirement closely harmonizes with the model codes and many
state and local building codes. Other commenters urged the Department not to
adopt section 604.3 of the 2010 Standards claiming that it will require
single-user toilet rooms to be two feet wider than the 1991 Standards require,
and this additional requirement will be difficult to meet. Multiple
commentators also expressed concern that the size of single-user toilet rooms
would be increased but they did not specify how much larger such toilet rooms
would have to be in their estimation. In response to these concerns, the
Department developed a series of single-user toilet room floor plans
demonstrating that the total square footage between representative layouts
complying with the 1991 Standards and the 2010 Standards are comparable. The
Department believes the floor plan comparisons clearly show that size
differences between the two Standards are not substantial and several of the
2010 Standards-compliant plans do not require additional square footage
compared to the 1991 Standards plans. These single-user toilet room floor
plans are shown below. Several commenters concluded that alterations of
single-user toilet rooms should be exempt from the requirements of section
604.3 of the 2010 Standards because of the significant reconfiguration and
reconstruction that would be required, such as moving plumbing fixtures,
walls, and/or doors at significant additional expense. The Department
disagrees with this conclusion since it fails to take into account several key
points. The 2010 Standards contain provisions for in-swinging doors, 603.2.3,
Exception 2, and recessed fixtures adjacent to water closets, 604.5.2,
Exception 1. These provisions give flexibility to create more compact room
designs and maintain required clearances around fixtures. As with the 1991
Standards, any alterations must comply to the extent that it is technically
feasible to do so. The requirements at section 604.3.2 of the 2010 Standards
specify how required clearance around the water closet can overlap with
specific elements and spaces. An exception that applies only to covered
residential dwelling units permits a lavatory to be located no closer than 18
inches from the centerline of the water closet. The requirements at section
604.3.2 of the 2010 Standards increase accessibility for individuals with
disabilities. One commenter expressed concern about other items that might
overlap the clear floor space, such as dispensers, shelves, and coat hooks on
the side of the water closet where a wheelchair would be positioned for a
transfer. Section 604.3.2 of the 2010 Standards allows items such as
associated grab bars, dispensers, sanitary napkin disposal units, coat hooks,
and shelves to overlap the clear floor space. These are items that typically
do not affect the usability of the clear floor space.
Toilet Room Doors. Sections 4.22.2 and 4.22.3 of the 1991
Standards and Section 603.2.3 of the 2010 Standards permit the doors of all
toilet or bathing rooms with in-swinging doors to swing into the required
turning space, but not into the clear floor space required at any fixture. In
single-user toilet rooms or bathing rooms, Section 603.2.3 Exception 2 of the
2010 Standards permits the door to swing into the clear floor space of an
accessible fixture if a clear floor space that measures at least 30 inches by
48 inches is provided outside of the door swing. Several commenters expressed
reservations about Exception 2 of Section 603.2.3. Concerns were raised that
permitting doors of single-user toilet or bathing rooms with in-swinging doors
to swing into the clearance around any fixture will result in inaccessibility
to individuals using larger wheelchairs and scooters. Additionally, a
commenter stated that the exception would require an unacceptable amount of
precision maneuvering by individuals who use standard size wheelchairs. The
Department believes that this provision achieves necessary flexibility while
providing a minimum standard for maneuvering space. The standard does permit
additional maneuvering space to be provided, if needed. In the NPRM, the
Department provided a series of plan drawings illustrating comparisons of the
minimum size single-user toilet rooms. These floor plans showed typical
examples that met the
minimum requirements of the proposed ADA
Standards. A commenter was of the opinion that the single-user toilet plans
shown in the NPRM demonstrated that the new requirements will not result in a
substantial increase in room size. Several other commenters representing
industry offered criticisms of the single-user toilet floor plans to support
their assertion that a 2010 Standards-compliant single-user toilet room will
never be smaller and will likely be larger than such a toilet room required
under the 1991 Standards. Commenters also asserted that the floor plans
prepared by the Department were of a very basic design which could be
accommodated in a minimal sized space whereas the types of facilities their
customers demand would require additional space to be added to the rooms shown
in the floor plans. The Department recognizes that there are many design
choices that can affect the size of a room or space. Choices to install
additional features may result in more space being needed to provide
sufficient clear floor space for that additional feature to comply. However,
many facilities that have these extra features also tend to have ample space
to meet accessibility requirements. Other commenters asserted that public
single-user toilet rooms always include a closer and a latch on the entry
door, requiring a larger clear floor space than shown on the push side of the
door shown in Plan 1B. The Department acknowledges that in instances where a
latch is provided and a closer is required by other regulations or codes, the
minimum size of a room with an out-swinging door may be slightly larger than
as shown in Plan 1C. Additional floor plans of single-user toilet rooms are
now included in further response to the commentary received.
| Comparison of Single-User Toilet Room Layouts |
1991 Standards
Plan-1A: 1991 Standards Minimum with Out-Swinging Door
5’-0” x 7’-3” 36.25 Square Feet
This plan shows a typical example of a single-user toilet room that
meets the minimum requirements of the 1991 Standards. The size of this
space is determined by the minimum width required for the water closet
and lavatory between the side walls, the minimum wheelchair turning
space, and the space required for the out-swinging door. A lavatory
with knee space can overlap the clear floor space required for the
water closet provided that at least 36 inches of clearance is
maintained between the side wall next to the water closet and the
lavatory (see section 4.16.2 and Fig. 28 of the 1991 Standards). A
wheelchair turning space meeting section 4.2.3 of the 1991 Standards
must be provided. The size of this room requires that the entry door
swing out. The room would be larger if the door were in-swinging.
|
2010 Standards
Plan-1B: 2010 Standards Minimum with Out-Swinging Door
7’-0” x 5’-0” • 35.00 Square Feet
This plan shows a typical example of a single-user toilet room that
meets the minimum requirements of the 2010 Standards. Features
include: five-foot minimum width between the side wall of the water
closet and the lavatory; 60-inch minimum circular wheelchair turning
space; and 36-inch by 48-inch clear maneuvering space for the
out-swinging entry door. Section 604.3.1 of the 2010 Standards
requires a floor clearance at a water closet that is a minimum of 60
inches wide by 56 inches deep regardless of approach. Section 604.3.2
prohibits any other plumbing fixtures from being located in this clear
space, except in residential dwelling units. The 2010 Standards, at
section 304.3, allows the turning space to extend into toe and knee
space provided beneath fixtures and other elements. Required
maneuvering space for the entry door (inside the room) must be clear
of all fixtures. If the door had both a closer and latch, section
404.2.4.1 and Figure 404.2.4.1(c) require additional space on the
latch side. This layout is three point five percent (3.5%) smaller
than the accompanying Plan-1A: 1991 Standards Minimum with
Out-Swinging Door example.
|
| Comparison of Single-User Toilet Room Layouts |
|
2010 Standards
Plan-1C: 2010 Standards Minimum with Out-Swinging Door
(entry door has both closer and latch)
7’-0” x 5’-6” 38.50 Square Feet
This plan shows the same typical features of a single-user toilet room
that meets the minimum requirements of the 2010 Standards as Plan-1B
does except the entry door has both a closer and latch. Because the
door has both a closer and latch, a minimum additional foot of
maneuvering space is required on the latch side (see section 404.2.4.1
and Figure 404.2.4.1(c) of the 2010 Standards). This layout is six
point two percent (6.2%) larger than the accompanying Plan-1A: 1991
Standards Minimum with Out-Swinging Door example.
|
| Comparison of Single-User Toilet Room Layouts |
1991 Standards
Plan-2A: 1991 Standards Minimum with In-Swinging Door
5’-0” x 8’-6” 42.50 Square Feet
This plan shows a typical example of a single-user toilet room that
meets the minimum requirements of the 1991 Standards. Depending on the
width of the hallway and other circulation issues, it can be
preferable to swing the entry door into the toilet room. Businesses
and public entities typically prefer to have an in-swinging door. The
in-swinging door increases overall room size because it cannot swing
over the required clear floor space at any accessible fixture, (see
section 4.22.2 of the 1991 Standards). This increases the room depth
from Plan-1A. The door is permitted to swing over the required turning
space shown as a 60-inch circle.
|
2010 Standards
Plan-2B: 2010 Standards Minimum with In-Swinging Door
7’-0” x 6’-6” 45.50 Square Feet
This plan shows a typical example of a single-user toilet room that
meets the minimum requirements of the 2010 Standards when the entry
door swings into the room. In the 2010 Standards an exception allows
the entry door to swing over the clear floor spaces and clearances
required at the fixtures if a clear floor space complying with section
305.3 (minimum 30 inches by 48 inches) is provided outside the arc of
the door swing, section 603.2.3 exception 2. The required maneuvering
space for the door, section 404.2.4.1 and Figure 404.2.4.1(a), also is
a factor in room size. This clear space cannot be obstructed by the
plumbing fixtures. Note that this layout provides more space for
turning when the door is closed than Plan-1B. This layout is seven
percent (7%) larger than the accompanying Plan-2A: 1991 Standards
Minimum with In-Swinging Door example.
|
| Comparison of Single-User Toilet Room Layouts |
|
2010 Standards
Plan-2C: 2010 Standards Minimum with In-Swinging Door
7’-0” x 6’-6” 40.00 Square Feet
(plumbing chase not included)
This plan shows the same typical features of a single-user toilet room
that meets the minimum requirements of the 2010 Standards as Plan-2B
when the entry door swings into the room. Note that this layout also
provides more space for turning when the door is closed than Plan-1B.
This layout is six point two five percent (6.25%) smaller than the
accompanying Plan-2A: 1991 Standards Minimum with In-Swinging Door
example.
|
| Comparison of Single-User Toilet Room Layouts |
|
1991 Standards and 2010 Standards
Plan-3: Meets Both 1991 Standards and 2010 Standards
7’-0” x 5’-9” 40.25 Square Feet
This plan shows an example of a single-user toilet room that meets the
minimum requirements of both the 1991 Standards and 2010 Standards. A
T-shaped turning space has been used (see Fig. 3(a) of the 1991
Standards and Figure 304.3.2 of the 2010 Standards) to maintain a
compact room size. An out-swinging door also minimizes the overall
layout depth and cannot swing over the required clear floor space or
clearance at any accessible plumbing fixture. This layout is eleven
percent (11%) larger than the Plan-1A: 1991 Standards Minimum with
Out-Swinging Door example shown at the beginning of these plan
comparisons.
|
|
Comparison of Single-User Toilet Room “Pairs” With Fixtures
Side-by-Side
|
1991 Standards
Plan-1A Pair: 1991 Standards with Out-Swinging Doors Two 5’-0” x 7’-3”
Rooms– 72.50 Square Feet Total
|
2010 Standards
Plan-1B Pair: 2010 Standards with Out-Swinging Doors Two 7’-0” x 5’-0”
Rooms- 70.00 Square Feet Total
|
|
These plans show men’s/women’s room configurations using Plans 1A
and 1B.
|
|
Comparison of Single-User Toilet Room “Pairs” With Fixtures
Side-by-Side
|
1991 Standards
|
2010 Standards
Plan-2C Pair: 2010 Standards with In-Swinging Doors
Two 7’-2” x 6’-6” Rooms - 82.00 Square Feet Total
This plan shows a men’s/women’s room configuration using Plan 2C.
|
Toilet Paper Dispensers. The provisions for toilet paper
dispensers at section 604.7 of the 2010 Standards require the dispenser to be
located seven inches minimum and nine inches maximum in front of the water
closet measured to the centerline of the dispenser. The paper outlet of the
dispenser must be located 15 inches minimum and 48 inches maximum above the
finish floor. In the 1991 Standards the location of the toilet paper dispenser
is determined by the centerline and forward edge of the dispenser. In the 2010
Standards the mounting location of the toilet paper dispenser is determined by
the centerline of the dispenser and the location of the outlet for the toilet
paper. One commenter discussed the difficulty of using large roll toilet paper
dispensers and dispensers with two standard size rolls stacked on top of each
other. The size of the large dispensers can block access to the grab bar and
the outlet for the toilet paper can be too low or too high to be usable. Some
dispensers also control the delivery of the toilet paper which can make it
impossible to get the toilet paper. Toilet paper dispensers that control
delivery or do not allow continuous paper flow are not permitted by the 1991
Standards or the 2010 Standards. Also, many of the large roll toilet paper
dispensers do not comply with the 2010 Standards since their large size does
not allow them to be mounted 12 inches above or 1 1/2 inches below the side
grab bar as required by section 609.3.
Shower Spray Controls. In accessible bathtubs and shower
compartments, sections 607.6 and 608.6 of the 2010 Standards require shower
spray controls to have an on/off control and to deliver water that is 120¡F
(49¡C) maximum. Neither feature was required by the 1991 Standards, but may be
required by plumbing codes. Delivering water that is no hotter than 120¡F
(49¡C) will require controlling the maximum temperature at each accessible
shower spray unit.
Shower Compartments. The 1991 Standards at sections 4.21 and
9.1.2 and the 2010 Standards at section 608 contain technical requirements for
transfer-type and roll-in shower compartments. The 2010 Standards provide more
flexibility than the 1991 Standards as follows:
- Transfer-type showers are exactly 36 inches wide by 36 inches long.
-
The 1991 Standards and the 2010 Standards permit a 1/2-inch maximum curb
in transfer-type showers. The 2010 Standards add a new exception that
permits a 2-inch maximum curb in transfer-type showers in alterations to
existing facilities, where recessing the compartment to achieve a 1/2-inch
curb will disturb the structural reinforcement of the floor slab.
-
Roll-in showers are 30 inches wide minimum by 60 inches long minimum.
Alternate roll-in showers are 36 inches wide by 60 inches long minimum,
and have a 36-inch minimum wide opening on the long side of the
compartment. The 1991 Standards require alternate roll-in showers in a
portion of accessible transient lodging guest rooms, but provision of this
shower type in other facilities is generally permitted as an equivalent
facilitation. The 1991 Standards require a seat to be provided adjacent to
the opening; and require the controls to be located on the side adjacent
to the seat. The 2010 Standards permit alternate roll-in showers to be
used in any facility, only require a seat in transient lodging guest
rooms, and allow location of controls on the back wall opposite the seat
as an alternative.
Commenters raised concerns that adding a new exception that permits a 2-inch
maximum curb in transfer-type showers in alterations to existing facilities,
where recessing the compartment to achieve a 1/2-inch curb will disturb the
structural reinforcement of the floor slab, will impair the ability of
individuals with disabilities to use transfer-type showers. The exception in
section 608.7 of the 2010 Standards permitting a 2-inch maximum curb in
transfer-type showers is allowed only in existing facilities where provision
of a 1/2-inch high threshold would disturb the structural reinforcement of the
floor slab. Whenever this exception is used the least high threshold that can
be used should be provided, up to a maximum height of 2 inches. This exception
is intended to provide some flexibility where the existing structure precludes
full compliance.
Toilet and Bathing Rooms. Section 213 of the 2010 Standards
sets out the scoping requirements for toilet and bathing rooms. Commenters
recommended that section 213, Toilet Facilities and Bathing Facilities, of the
2010 Standards include requirements that unisex toilet and bathing rooms be
provided in certain facilities. These commenters suggested that unisex toilet
and bathing rooms are most useful as companion care facilities. Model plumbing
and building codes require single-user (unisex or family) toilet facilities in
certain occupancies, primarily assembly facilities, covered malls, and
transportation facilities. These types of toilet rooms provide flexibility for
persons needing privacy so that they can obtain assistance from family members
or persons of the opposite sex. When these facilities are provided, both the
1991 Standards and 2010 Standards require that they be accessible. The 2010
Standards do not scope unisex toilet facilities because plumbing codes
generally determine the number and type of plumbing fixtures to be provided in
a particular occupancy and often determine whether an occupancy must provide
separate sex facilities in addition to single-user facilities. However, the
scoping at section 213.2.1 of the 2010 Standards coordinates with model
plumbing and building code requirements which will permit a small toilet room
with two water closets or one water closet and one urinal to be considered a
single-user toilet room provided that the room has a privacy latch. In this
way, a person needing assistance from a person of the opposite sex can lock
the door to use the facility while temporarily inconveniencing only one other
potential user. These provisions strike a reasonable balance and impose less
impact on covered entities. A commenter recommended that in shower
compartments rectangular seats as provided in section 610.3.1 of the 2010
Standards should not be permitted as a substitute for L-shaped seats as
provided in 610.3.2. The 2010 Standards do not indicate a preference for
either rectangular or L-shaped seats in shower compartments. L-shaped seats in
transfer and certain roll-in showers have been used for many years to provide
users with poor balance additional support because they can position
themselves in the corner while showering.
214 and 611 Washing Machines and Clothes Dryers
Sections 214.2 (washing machines) and 214.3 (clothes dryers) of the 2010
Standards specify the number of each type of these machines required to be
accessible (one to two depending upon the total number of machines provided)
and section 611 specifies the technical requirements. An exception will permit
the maximum height for the tops of these machines to be 2 inches higher than
the general requirement for maximum high reach over an obstruction. A
commenter objected to the scoping provision for accessible washing machines
and clothes dryers stating that the probability is low that more than one
accessible machine would be needed at the same time in the laundry facility of
a place of transient lodging. The scoping in this provision is based on the
relative size of the facility. The Department assumes that the size of the
facility (and, therefore, the number of accessible machines provided) will be
determined by the covered entity´s assessment of the demand for laundry
facilities. The Department declines to assume that persons with disabilities
will have less use for accessible facilities in transient lodging than in
other public accommodations.
216 and 703 Signs
The following types of signs, though they are not specifically subject to the
1991 Standards requirement for signs, will now be explicitly exempted by
sections 216 and 703 of the 2010 Standards. These types of signs include: seat
and row designations in assembly areas; occupant names, building addresses;
company names and logos; signs in parking facilities (except those identifying
accessible parking spaces and means of egress); and exterior signs identifying
permanent rooms and spaces that are not located at the door to the space they
serve. This requirement also clarifies that the exception for temporary signs
applies to signs used for seven days or less. The 2010 Standards retain the
option to provide one sign where both visual and tactile characters are
provided or two signs, one with visual, and one with tactile characters.
217 and 704 Telephones
Drive-up Public Telephones. Where public telephones are
provided, the 1991 Standards, at section 4.1.3(17)(a), and section 217.2 of
the 2010 Standards, require a certain number of telephones to be wheelchair
accessible. The 2010 Standards add a new exception that exempts drive-up
public telephones.
Text Telephones (TTY). Section 4.1.3(17) of the 1991
Standards requires a public TTY to be provided if there are four or more
public pay telephones at a site and at least one is in an interior location.
Section 217.4.2 of the 2010 Standards requires that a building or facility
provide a public TTY on each floor that has four or more public telephones,
and in each telephone bank that has four or more telephones. Additionally,
section 217.4.4 of the 2010 Standards requires that at least one public TTY be
installed where four or more public pay telephones are provided on an exterior
site. Section 217.4.5 of the 2010 Standards also requires that a public TTY be
provided where at least one public pay telephone is provided at a public rest
stop, emergency roadside stop, or service plaza. Section 217.4.6 of the 2010
Standards also requires that a public TTY be provided at each location where
at least one public pay telephone is provided serving a hospital emergency
room, a hospital recovery room, or a hospital waiting room. Section 217.4.7 of
the 2010 Standards also requires that, in addition to the requirements for a
public TTY to be provided at each location where at least four or more public
pay telephones are provided at a bank of pay telephones and where at least one
public pay telephone is provided on a floor or in a public building, where at
least one public pay telephone serves a particular entrance to a bus or rail
facility at least one public TTY must serve that entrance. In airports, in
addition to the requirements for the provision of a public TTY at phone banks,
on floors, and in public buildings with pay phones, where four or more public
pay phones are located in a terminal outside the security areas, in a
concourse within the security areas, or a baggage claim area in a terminal at
least one public TTY must be provided. Section 217.4.8 of the 2010 Standards
also requires that a TTY be provided in at least one secured area where at
least one pay telephone is provided in a secured area used only by detainees
or inmates and security personnel in detention and correctional facilities.
Wheelchair Accessible Telephones
Section 217.2 of the 2010 Standards requires that where public telephones are
provided wheelchair accessible telephones complying with section 704.2 must be
provided in accordance with Table 217.2. A commenter stated that requiring
installation of telephones within the proposed reach range requirements would
adversely impact public and telephone owners and operators. According to the
commenter, individuals without disabilities will not use telephones that are
installed within the reach range requirements because they may be
inconvenienced by having to stoop to operate these telephones, and, therefore,
owners and operators will lose revenue due to less use of public telephones.
This comment misunderstands the scoping requirements for wheelchair accessible
telephones. Section 217.2 of the 2010 Standards provides that where one or
more single units are provided, only one unit per floor, level, or exterior
site is required to be wheelchair accessible. However, where banks of
telephones are provided, only one telephone in each bank is required to be
wheelchair accessible. The Department believes these scoping requirements for
wheelchair accessible telephones are reasonable and will not result in
burdensome obligations or lost revenue for owners and operators.
218 and 810 Transportation Facilities
Detectable Warnings. Detectable warnings provide a
distinctively textured surface of truncated domes. The 1991 Standards at
sections 4.1.3(15), 4.7.7, 4.29.2, 4.29.5, 4.29.6, and 10.3.1(8) require
detectable warnings at curb ramps, hazardous vehicular areas, reflecting
pools, and transit platform edges. The 2010 Standards at sections 218, 810.5,
705.1, and 705.2 only require detectable warnings at transit platform edges.
The technical specifications for the diameter and spacing of the truncated
domes have also been changed. The 2010 Standards also delete the requirement
for the material used to contrast in resiliency or sound-on-cane contact from
adjoining walking surfaces at interior locations. The 2010 Standards apply to
detectable warnings on developed sites. They do not apply to the public
right-of-way. Scoping for detectable warnings at all locations other than
transit platform edges has been eliminated from the 2010 Standards. However,
because detectable warnings have been shown to significantly benefit
individuals with disabilities at transit platform edges, the 2010 Standards
provide scoping and technical requirements for detectable warnings at transit
platform edges.
219 and 706 Assistive Listening Systems
Signs. Section 216.10 of the 2010 Standards requires each
covered assembly area to provide signs at each auditorium to inform patrons
that assistive listening systems are available. However, an exception to this
requirement permits assembly areas that have ticket offices or ticket windows
to display the required signs at the ticket window. A commenter recommended
eliminating the exception at 216.10 because, for example, people who buy
tickets through the mail, by subscription, or on-line may not need to stop at
a ticket office or window upon arrival at the assembly area. The Department
believes that an individual´s decision to purchase tickets before arriving at
a performance does not limit the discretion of the assembly operator to use
the ticket window to provide other services to its patrons. The Department
retained the exception at 216.10 to permit the venue operator some flexibility
in determining how to meet the needs of its patrons.
Audible Communication. The 1991 Standards, at section
4.1.3(19)(b), require assembly areas, where audible communication is integral
to the use of the space, to provide an assistive listening system if they have
an audio amplification system or an occupant load of 50 or more people and
have fixed seating. The 2010 Standards at section 219 require assistive
listening systems in spaces where communication is integral to the space and
audio amplification is provided and in courtrooms. The 1991 Standards require
receivers to be provided for at least four percent (4%) of the total number of
fixed seats. The 2010 Standards, at section 219.3, revise the percentage of
receivers required according to a table that correlates the required number of
receivers to the seating capacity of the facility. Small facilities will
continue to provide receivers for four percent (4%) of the seats. The required
percentage declines as the size of the facility increases. The changes also
require at least twenty-five percent (25%), but no fewer than two, of the
receivers to be hearing-aid compatible. Assembly areas served by an induction
loop assistive listening system will not have to provide hearing-aid
compatible receivers. Commenters were divided in their opinion of this change.
The Department believes that the reduction in the required number of assistive
listening systems for larger assembly areas will meet the needs of individuals
with disabilities. The new requirement to provide hearing-aid compatible
receivers should make assistive listening systems more usable for people who
have been underserved until now. Concerns were raised that the requirement to
provide assistive listening systems may have an adverse impact on restaurants.
This comment misunderstands the scope of coverage. The 2010 Standards define
the term "assembly area" to include facilities used for entertainment,
educational, or civic gatherings. A restaurant would fall within this category
only if it is presenting programs to educate or entertain diners, and it
provides an audio amplification system.
Same Management or Building. The 2010 Standards add a new
exception that allows multiple assembly areas that are in the same building
and under the same management, such as theaters in a multiplex cinema and
lecture halls in a college building, to calculate the number of receivers
required based on the total number of seats in all the assembly areas, instead
of each assembly area separately, where the receivers are compatible with the
assistive listening systems used in each of the assembly areas.
Mono Jacks, Sound Pressure, Etc. Section 4.33.7 of the 1991
Standards does not contain specific technical requirements for assistive
listening systems. The 2010 Standards at section 706 require assistive
listening systems to have standard mono jacks and will require hearing-aid
compatible receivers to have neck loops to interface with telecoils in hearing
aids. The 2010 Standards also specify sound pressure level, signal-to-noise
ratio, and peak clipping level. Currently available assistive listening
systems typically meet these technical requirements.
220 and 707 Automatic Teller Machines and Fare Machines
Section 707 of the 2010 Standards adds specific technical requirements for
speech output, privacy, tactilely-discernible input controls, display screens,
and Braille instructions to the general accessibility requirements set out in
the 1991 Standards. Machines shall be speech enabled and exceptions are
provided that cover when audible tones are permitted, when advertisements or
similar information are provided, and where speech synthesis cannot be
supported. The 1991 Standards require these machines to be accessible to and
independently usable by persons with visual impairments, but do not contain
any technical specifications.
221 Assembly Areas
Wheelchair Spaces/Companion Seats. Owners of large assembly
areas have historically complained to the Department that the requirement for
one percent (1%) of seating to be wheelchair seating is excessive and that
wheelchair seats are not being sold. At the same time, advocates have
traditionally argued that persons who use wheelchairs will increasingly
participate in activities at assembly areas once they become accessible and
that at least one percent (1%) of seats should be accessible. The 1991
Standards, at sections 4.1.3(19)(a) and 4.33.3, require assembly areas to
provide wheelchair and companion seats. In assembly areas with a capacity of
more than five hundred seats, accessible seating at a ratio of one percent
(1%) (plus one seat) of the number of traditional fixed seats must be
provided. The 2010 Standards, at section 221.2, require assembly areas with
501 to 5000 seats to provide at least six wheelchair spaces and companion
seats plus one additional wheelchair space for each additional 150 seats (or
fraction thereof) between 501 through 5000. In assembly areas with more than
5000 seats at least 36 wheelchair spaces and companion seats plus one
additional wheelchair space for each 200 seats (or fraction thereof) more than
5000 are required. See sections 221.1 and 221.2 of the 2010 Standards.
Commenters questioned why scoping requirements for large assembly areas are
being reduced. During the development of the 2004 ADAAG, industry providers,
particularly those representing larger stadium-style assembly areas, supplied
data to the Access Board demonstrating the current scoping requirements for
large assembly areas often exceed the demand. Based on the data provided to
the Access Board, the Department believes the reduced scoping requirements
will adequately meet the needs of individuals with disabilities, while
balancing concerns of the industry. Commenters representing assembly areas
supported the reduced scoping. One commenter asked that scoping requirements
for larger assembly areas be reduced even further. Although the commenter
referenced data demonstrating that wheelchair spaces in larger facilities with
seating capacities of 70,000 or more may not be used by individuals with
disabilities, the data was not based on actual results, but was calculated at
least in part based on probability assumptions. The Department is not
convinced that further reductions should be made based upon those projections
and that further reductions would not substantially limit accessibility at
assembly areas for persons who use wheelchairs. Section 221.2.1.3 of the 2010
Standards clarifies that the scoping requirements for wheelchair spaces and
companion seats are to be applied separately to general seating areas and to
each luxury box, club box, and suite in arenas, stadiums, and grandstands. In
assembly areas other than arenas, stadiums, and grandstands, the scoping
requirements will not be applied separately. Thus, in performing arts
facilities with tiered boxes designed for spatial and acoustical purposes, the
scoping requirement is to be applied to the seats in the tiered boxes. The
requisite number of wheelchair spaces and companion seats required in the
tiered boxes are to be dispersed among at least twenty percent (20%) of the
tiered boxes. For example, if a performing arts facility has 20 tiered boxes
with 10 fixed seats in each box, for a total of 200 seats, at least five
wheelchair spaces and companion seats must be provided in the boxes, and they
must be dispersed among at least four of the 20 boxes. Commenters raised
concerns that the 2010 Standards should clarify requirements for scoping of
seating areas and that requiring accessible seating in each luxury box, club
box, and suite in arenas, stadiums and grandstands could result in no
wheelchair and companion spaces available for individuals with disabilities in
the general seating area(s). These comments appear to misunderstand the
requirements. The 2010 Standards require each luxury box, club box, and suite
in an arena, stadium or grandstand to be accessible and to contain wheelchair
spaces and companion seats as required by sections 221.2.1.1, 221.2.1.2 and
221.3. In addition, the remaining seating areas not located in boxes must also
contain the number of wheelchair and companion seating locations specified in
the 2010 Standards based on the total number of seats in the entire facility
excluding luxury boxes, club boxes and suites.
Wheelchair Space Overlap in Assembly Areas. Section 4.33.3
of the 1991 Standards and the 2010 Standards, at sections 402, 403.5.1,
802.1.4, and 802.1.5, require walkways that are part of an accessible route to
have a 36-inch minimum clear width. Section 802.1.5 of the 2010 Standards
specifically prohibits accessible routes from overlapping wheelchair spaces.
This change is consistent with the technical requirements for accessible
routes, since the clear width of accessible routes cannot be obstructed by any
object. The 2010 Standards also specifically prohibit wheelchair spaces from
overlapping circulation paths. An advisory note clarifies that this
prohibition applies only to the circulation path width required by applicable
building codes and fire and life safety codes since the codes prohibit
obstructions in the required width of assembly aisles. Section 802.1.5 of the
2010 Standards provides that where a main circulation path is located in front
of a row of seats that contains a wheelchair space and the circulation path is
wider than required by applicable building codes and fire and life safety
codes, the wheelchair space may overlap the"extra" circulation path width.
Where a main circulation path is located behind a row of seats that contains a
wheelchair space and the wheelchair space is entered from the rear, the aisle
in front of the row may need to be wider in order not to block the required
circulation path to the other seats in the row, or a mid-row opening may need
to be provided to access the required circulation path to the other seats.
Line of Sight and Dispersion of Wheelchair Spaces in Assembly
Areas. Section 4.33.3 of the 1991 Standards requires wheelchair spaces and
companion seats to be an integral part of any fixed seating plan in assembly
areas and to provide individuals with disabilities a choice of admission
prices and lines of sight comparable to those available to other spectators.
Section 4.33.3 also requires wheelchair spaces and companion seats to be
dispersed in assembly areas with more than 300 seats. Under the 1991
Standards, sports facilities typically located some wheelchair spaces and
companion seats on each accessible level of the facility. In 1994, the
Department issued official guidance interpreting the requirement for
comparable lines of sight in the 1991 Standards to mean wheelchair spaces and
companion seats in sports stadia and arenas must provide patrons with
disabilities and their companions with lines of sight over standing spectators
to the playing field or performance area, where spectators were expected to
stand during events. See"Accessible Stadiums," www.ada.gov/stadium.pdf. The
Department also interpreted the section 4.33.3 comparable lines of sight
requirement to mean that wheelchair spaces and companion seats in
stadium-style movie theaters must provide patrons with disabilities and their
companions with viewing angles comparable to those provided to other
spectators. Sections 221.2.3 and 802.2 of the 2010 Standards add specific
technical requirements for providing lines of sight over seated and standing
spectators and also require wheelchair spaces and companion seats (per section
221.3) to provide individuals with disabilities choices of seating locations
and viewing angles that are substantially equivalent to, or better than, the
choices of seating locations and viewing angles available to other spectators.
This applies to all types of assembly areas, including stadium-style movie
theaters, sports arenas, and concert halls. These rules are expected to have
minimal impact since they are consistent with the Department´s longstanding
interpretation of the 1991 Standards and technical assistance. Commenters
stated that the qualitative viewing angle language contained in section
221.2.3 is not appropriate for an enforceable regulatory standard unless the
terms of such language are defined. Other commenters requested definitions for
viewing angles, an explanation for precisely how viewing angles are measured,
and an explanation for precisely how to evaluate whether one viewing angle is
better than another viewing angle. The Department is convinced that the
regulatory language in the 2010 Standards is sufficient to provide a
performance-based standard for designers, architects, and other professionals
to design facilities that provide comparable lines of sight for wheelchair
seating in assembly areas, including viewing angles. The Department believes
that as a general rule, the vast variety of sizes and configurations in
assembly areas requires it to establish a performance standard for designers
to adapt to the specific circumstances of the venue that is being designed.
The Department has implemented more explicit requirements for stadium-style
movie theaters in 28 CFR 36.406(f) and 35.151(g) of the final regulations
based on experience and expertise gained after several major enforcement
actions. Another commenter inquired as to what determines whether a choice of
seating locations or viewing angles is better than that available to all other
spectators. The answer to this question varies according to each assembly area
that is being designed, but designers and venue operators understand which
seats are better and that understanding routinely drives design choices made
to maximize profit and successful operation of the facility, among other
things. For example, an"equivalent or better" line of sight in a major league
football stadium would be different than for a 350-seat lecture hall. This
performance standard is based upon the underlying principle of equal
opportunity for a good viewing experience for everyone, including persons with
disabilities. The Department believes that for each specific facility that is
designed, the owner, operator, and design professionals will be able to
distinguish easily between seating locations and the quality of the associated
lines of sight from those seating locations in order to decide which ones are
better than others. The wheelchair locations do not have to be exclusively
among the seats with the very best lines of sight nor may they be exclusively
among the seats with the worst lines of sight. Rather, wheelchair seating
locations should offer a choice of viewing experiences and be located among
the seats where most of the audience chooses to sit. Section 4.33.3 of the
1991 Standards requires wheelchair spaces and companion seating to be offered
at a choice of admission prices, but section 221.2.3.2 of the 2010 Standards
no longer requires wheelchair spaces and companion seats to be dispersed based
on admission prices. Venue owners and operators commented during the 2004
ADAAG rulemaking process that pricing is not always established at the design
phase and may vary from event to event within the same facility, making it
difficult to determine where to place wheelchair seats during the design and
construction phase. Their concern was that a failure by the venue owner or
operator to provide a choice of ticket prices for wheelchair seating as
required by the 1991 Standards governing new construction could somehow
unfairly subject parties involved in the design and construction to liability
unknowingly. Sections 221.2.3.2 and 221.3 of the 2010 Standards require
wheelchair spaces and companion seats to be vertically dispersed at varying
distances from the screen, performance area, or playing field. The 2010
Standards, at section 221.2.3.2, also require wheelchair spaces and companion
seats to be located in each balcony or mezzanine served by an accessible
route. The final regulations at 28 CFR 35.151(g)(1) and 36.406(f)(1) also
require assembly areas to locate wheelchair spaces and companion seats at all
levels of the facility that include seating and that are served by an
accessible route. The Department interprets that requirement to mean that
wheelchair and companion seating must be provided in a particular area even if
the accessible route may not be the same route that other individuals use to
reach their seats. For example, if other patrons reach their seats on the
field by an inaccessible route (e.g
., by stairs), but there is an
accessible route that complies with section 206.3 that could be connected to
seats on the field, accessible seats must be placed on the field even if that
route is not generally available to the public. The 2010 Standards, at section
221.2.3.2, provide an exception for vertical dispersion in assembly areas with
300 or fewer seats if the wheelchair spaces and companion seats provide
viewing angles that are equivalent to, or better than, the average viewing
angle provided in the facility. Section 221.3 of the 2010 Standards requires
wheelchair spaces and companion seats to be dispersed horizontally. In
addition, 28 CFR 35.151(g)(2) and 36.406(f)(2) require assembly areas that
have seating around the field of play or performance area to place wheelchair
spaces and companion seating all around that field of play or performance
area.
Stadium-Style Movie Theaters
Pursuant to 28 CFR 35.151(g) and 36.406(f), in addition to other obligations,
stadium-style movie theaters must meet horizontal and vertical dispersion
requirements set forth in sections 221.2.3.1 and 221.2.3.2 of the 2010
Standards; placement of wheelchair and companion seating must be on a riser or
cross-aisle in the stadium section of the theater; and placement of such
seating must satisfy at least one of the following criteria: (i) it is located
within the rear sixty percent (60%) of the seats provided in the auditorium;
or (ii) it is located within the area of the auditorium where the vertical
viewing angles are between the 40th and 100th percentile of vertical viewing
angles for all seats in that theater as ranked from the first row (1st
percentile) to the back row (100th percentile). The line-of-sight requirements
recognize the importance to the movie-going experience of viewing angles, and
the final regulations ensure that movie patrons with disabilities are provided
views of the movie screen comparable to other theater patrons. Some commenters
supported regulatory language that would require stadium-style theaters to
meet standards of accessibility equal to those of non-stadium-style theaters,
with larger theaters being required to provide accessible seating locations
and viewing angles equal to those offered to individuals without disabilities.
One commenter noted that stadium-style movie theaters, sports arenas, music
venues, theaters, and concert halls each pose unique conditions that require
separate and specific standards to accommodate patrons with disabilities, and
recommended that the Department provide more specific requirements for sports
arenas, music venues, theaters, and concert halls. The Department has
concluded that the 2010 Standards will provide sufficient flexibility to adapt
to the wide variety of assembly venues covered.
Companion Seats. Section 4.33.3 of the 1991 Standards
required at least one fixed companion seat to be provided next to each
wheelchair space. The 2010 Standards at sections 221.3 and 802.3 permit
companion seats to be movable. Several commenters urged the Department to
ensure that companion seats are positioned in a manner that places the user at
the same shoulder height as their companions using mobility devices. The
Department recognizes that some facilities have created problems by locating
the wheelchair space and companion seat on different floor elevations (often a
difference of one riser height). Section 802.3.1 of the 2010 Standards
addresses this problem by requiring the wheelchair space and the companion
seat to be on the same floor elevation. This solution should prevent any
vertical discrepancies that are not the direct result of differences in the
sizes and configurations of wheelchairs.
Designated Aisle Seats. Section 4.1.3(19)(a) of the 1991
Standards requires one percent (1%) of fixed seats in assembly areas to be
designated aisle seats with either no armrests or folding or retractable
armrests on the aisle side of the seat. The 2010 Standards, at sections 221.4
and 802.4, base the number of required designated aisle seats on the total
number of aisle seats, instead of on all of the seats in an assembly area as
the 1991 Standards require. At least five percent (5%) of the aisle seats are
required to be designated aisle seats and to be located closest to accessible
routes. This option will almost always result in fewer aisle seats being
designated aisle seats compared to the 1991 Standards. The Department is aware
that sports facilities typically locate designated aisle seats on, or as near
to, accessible routes as permitted by the configuration of the facility. One
commenter recommended that section 221.4, Designated Aisle Seats, be changed
to require that aisle seats be on an accessible route, and be integrated and
dispersed throughout an assembly area. Aisle seats, by their nature, typically
are located within the general seating area, and integration occurs almost
automatically. The issue of dispersing aisle seats or locating them on
accessible routes is much more challenging. During the separate rulemaking on
the 2004 ADAAG the Access Board specifically requested public comment on the
question of whether aisle seats should be required to be located on accessible
routes. After reviewing the comments submitted during the 2004 Access Board
rulemaking, the Access Board concluded that this could not be done without
making significant and costly changes in the design of most assembly areas.
However, section 221.4 of the 2004 ADAAG required that designated aisle seats
be the aisle seats closest to accessible routes. The Department proposed the
same provision and concurs in the Access Board´s conclusion and declines to
implement further changes.
Team or Player Seating Areas. Section 221.2.1.4 of the 2010
Standards requires that at least one wheelchair space compliant with section
802.1 be provided in each team or player seating area serving areas of sport
activity. For bowling lanes, the requirement for a wheelchair space in player
seating areas is limited to lanes required to be accessible.
Lawn Seating. The 1991 Standards, at section 4.1.1(1),
require all areas of newly constructed facilities to be accessible, but do not
contain a specific scoping requirement for lawn seating in assembly areas. The
2010 Standards, at section 221.5, specifically require lawn seating areas and
exterior overflow seating areas without fixed seats to connect to an
accessible route.
Aisle Stairs and Ramps in Assembly Areas. Sections 4.1.3 and
4.1.3(4) of the 1991 Standards require that interior and exterior stairs
connecting levels that are not connected by an elevator, ramp, or other
accessible means of vertical access must comply with the technical
requirements for stairs set out in section 4.9 of the 1991 Standards. Section
210.1 of the 2010 Standards requires that stairs that are part of a means of
egress shall comply with section 504´s technical requirements for stairs. The
1991 Standards do not contain any exceptions for aisle stairs in assembly
areas. Section 210.1, Exception 3 of the 2010 Standards adds a new exception
that exempts aisle stairs in assembly areas from section 504´s technical
requirements for stairs, including section 505´s technical requirements for
handrails. Section 4.8.5 of the 1991 Standards exempts aisle ramps that are
part of an accessible route from providing handrails on the side adjacent to
seating. The 2010 Standards, at section 405.1, exempt aisle ramps adjacent to
seating in assembly areas and not serving elements required to be on an
accessible route, from complying with all of section 405´s technical
requirements for ramps. Where aisle ramps in assembly areas serve elements
required to be on an accessible route, the 2010 Standards require that the
aisle ramps comply with section 405´s technical requirements for ramps.
Sections 505.2 and 505.3 of the 2010 Standards provide exceptions for aisle
ramp handrails. Section 505.2 states that in assembly areas, a handrail may be
provided at either side or within the aisle width when handrails are not
provided on both sides of aisle ramps. Section 505.3 states that, in assembly
areas, handrails need not be continuous in aisles serving seating.
222 and 803 Dressing, Fitting, and Locker Rooms
Dressing rooms, fitting rooms, and locker rooms are required to comply with
the accessibility requirements of sections 222 and 803 of the 2010 Standards.
Where these types of rooms are provided in clusters, five percent (5%) but at
least one room in each cluster must comply. Some commenters stated that
clothing and retail stores would have to expand and reconfigure accessible
dressing, fitting and locker rooms to meet the changed provision for clear
floor space alongside the end of the bench. Commenters explained that meeting
the new requirement would result in a loss of sales and inventory space. Other
commenters also expressed opposition to the changed requirement in locker
rooms for similar reasons. The Department reminds the commenters that the
requirements in the 2010 Standards for the clear floor space to be beside the
short axis of the bench in an accessible dressing, fitting, or locker room
apply only to new construction and alterations. The requirements for
alterations in the 2010 Standards at section 202.3 do not include the
requirement from the 1991 Standards at section 4.1.6(1)(c) that if alterations
to single elements, when considered together, amount to an alteration of a
room or space in a building or facility, the entire space shall be made
accessible. Therefore, under the 2010 Standards, the alteration requirements
only apply to specific elements or spaces that are being altered. So providing
the clear floor space at the end of the bench as required by the 2010
Standards instead of in front of the bench as is allowed by the 1991 Standards
would only be required when the bench in the accessible dressing room is
altered or when the entire dressing room area is altered.
224 and 806 Transient Lodging Guest Rooms
Scoping. The minimum number of guest rooms required to be
accessible in transient lodging facilities is covered by section 224 of the
2010 Standards. Scoping requirements for guest rooms with mobility features
and guest rooms with communication features are addressed at section 224.2 and
section 224.4, respectively. Under the 1991 Standards all newly constructed
guest rooms with mobility features must provide communication features. Under
the 2010 Standards, in section 224.5, at least one guest room with mobility
features must also provide communication features. Additionally, not more than
ten percent (10%) of the guest rooms required to provide mobility features and
also equipped with communication features can be used to satisfy the minimum
number of guest rooms required to provide communication features. Some
commenters opposed requirements for guest rooms accessible to individuals with
mobility disabilities stating that statistics provided by the industry
demonstrate that all types of accessible guest rooms are unused. They further
claimed that the requirements of the 2010 Standards are too burdensome to meet
in new construction, and that the requirements will result in a loss of living
space in places of transient lodging. Other commenters urged the Department to
increase the number of guest rooms required to be accessible. The number of
guest rooms accessible to individuals with mobility disabilities and the
number accessible to persons who are deaf or who are hard of hearing in the
2010 Standards are consistent with the 1991 Standards and with the IBC. The
Department continues to receive complaints about the lack of accessible guest
rooms throughout the country. Accessible guest rooms are used not only by
individuals using mobility devices such as wheelchairs and scooters, but also
by individuals with other mobility disabilities including persons who use
walkers, crutches, or canes. Data provided by the Disability Statistics Center
at the University of California, San Francisco demonstrated that the number of
adults who use wheelchairs has been increasing at the rate of six percent (6%)
per year from 1969 to 1999; and by 2010, it was projected that two percent
(2%) of the adult population would use wheelchairs. In addition to persons who
use wheelchairs, three percent (3%) of adults used crutches, canes, walkers,
and other mobility devices in 1999; and the number was projected to increase
to four percent (4%) by 2010. Thus, in 2010, up to six percent (6%) of the
population may need accessible guest rooms.
Dispersion. The 2010 Standards, in section 224.5, set scoping
requirements for dispersion in facilities covered by the transient lodging
provisions. This section covers guest rooms with mobility features and guest
rooms with communication features and applies in new construction and
alterations. The primary requirement is to provide choices of types of guest
rooms, number of beds, and other amenities comparable to the choices provided
to other guests. An advisory in section 224.5 provides guidance that "factors
to be considered in providing an equivalent range of options may include, but
are not limited to, room size, bed size, cost, view, bathroom fixtures such as
hot tubs and spas, smoking and nonsmoking, and the number of rooms provided."
Commenters asked the Department to clarify what is meant by various terms used
in section 224.5 such as "classes," "types," "options," and "amenities." Other
commenters asked the Department to clarify and simplify the dispersion
requirements set forth in section 224.5 of the 2010 Standards, in particular
the scope of the term "amenities." One commenter expressed concern that views,
if considered an amenity, would further complicate room categories and force
owners and operators to make an educated guess. Other commenters stated that
views should only be a dispersion criteria if view is a factor for pricing
room rates. These terms are not to be considered terms of art, but should be
used as in their normal course. For example, "class" is defined by Webster´s
Dictionary as "a division by quality." "Type" is defined as "a group of * * *
things that share common traits or characteristics distinguishing them as an
identifiable group or class." Accordingly, these terms are not intended to
convey different concepts, but are used as synonyms. In the 2010 Standards,
section 224.5 and its advisory require dispersion in such a varied range of
hotels and lodging facilities that the Department believes that the chosen
terms are appropriate to convey what is intended. Dispersion required by this
section is not "one size fits all" and it is imperative that each covered
entity consider its individual circumstance as it applies this requirement.
For example, a facility would consider view as an amenity if some rooms faced
mountains, a beach, a lake, or other scenery that was considered to be a
premium. A facility where view was not marketed or requested by guests would
not factor the view as an amenity for purposes of meeting the dispersion
requirement. Section 224.5 of the 2010 Standards requires that guest rooms
with mobility features and guest rooms with communication features "shall be
dispersed among the various classes of guest rooms, and shall provide choices
of types of guest rooms, number of beds, and other amenities comparable to the
choices provided to other guests. When the minimum number of guest rooms
required is not sufficient to allow for complete dispersion, guest rooms shall
be dispersed in the following priority: guest room type, number of beds and
amenities." This general dispersion requirement is intended to effectuate
Congress´ directive that a percentage of each class of hotel rooms is to be
fully accessible to persons with disabilities. See H.R. Rep. No. 101-485 (II)
at 391. Accordingly, the promise of the ADA in this instance is that persons
with disabilities will have an equal opportunity to benefit from the various
options available to hotel guests without disabilities, from single occupancy
guest rooms with limited features (and accompanying limited price tags) to
luxury suites with lavish features and choices. The inclusion of section 224.5
of the 2010 Standards is not new. Substantially similar language is contained
in section 9.1.4 of the 1991 Standards. Commenters raised concerns that the
factors included in the advisory to section 224.5 of the 2010 Standards have
been expanded. The advisory provides: "[f]actors to be considered in providing
an equivalent range of options may include, but are not limited to, room size,
bed size, cost, view, bathroom fixtures such as hot tubs and spas, smoking and
nonsmoking, and the number of rooms provided." As previously discussed, the
advisory materials provided in the 2010 Standards are meant to be illustrative
and do not set out specific requirements. In this particular instance, the
advisory materials for section 224.5 set out some of the common types of
amenities found at transient lodging facilities, and include common sense
concepts such as view, bathroom fixtures, and smoking status. The intention of
these factors is to indicate to the hospitality industry the sorts of
considerations that the Department, in its enforcement efforts since the
enactment of the ADA, has considered as amenities that should be made
available to persons with disabilities, just as they are made available to
guests without disabilities. Commenters offered several suggestions for
addressing dispersion. One option included the flexibility to use an
equivalent facilitation option similar to that provided in section 9.1.4(2) of
the 1991 Standards. The 2010 Standards eliminated all specific references to
equivalent facilitation. Since Congress made it clear that each class of hotel
room is to be available to individuals with disabilities, the Department
declines to adopt such a specific limitation in favor of the specific
requirement for new construction and alterations found in section 224.5 of the
2010 Standards. In considering the comments of the hospitality industry from
the ANPRM and the Department´s enforcement efforts in this area, the
Department sought comment in the NPRM on whether the dispersion requirements
should be applied proportionally, or whether the requirements of section 224.5
of the 2010 Standards would be complied with if access to at least one guest
room of each type were to be provided. One commenter expressed concern about
requiring different guest room types to be proportionally represented in the
accessible guest room pool as opposed to just having each type represented.
Some commenters also expressed concern about accessible guest rooms created in
pre-1993 facilities and they requested that such accessible guest rooms be
safe harbored just as they are safe harbored under the 1991 Standards. In
addition, one commenter requested that the proposed dispersion requirements in
section 224.5 of the 2010 Standards not be applied to pre-1993 facilities even
when they are altered. Some commenters also offered a suggestion for
limitations to the dispersion requirements as an alternative to safe harboring
pre-1993 facilities. The suggestion included: (1) Guest rooms´ interior or
exterior footprints may remain unchanged in order to meet the dispersion
requirements; (2) Dispersion should only be required among the types of rooms
affected by an alteration; and (3) Subject to (1) and (2) above and technical
feasibility, a facility would need to provide only one guest room in each
guest room type such as single, double and suites. One commenter requested an
exception to the dispersion criteria that applies to both existing and new
multi-story timeshare facilities. This requested exception waives dispersion
based on views to the extent that up to eight units may be vertically stacked
in a single location. Section 224.1.1 of the 2010 Standards sets scoping
requirements for alterations to transient lodging guest rooms. The advisory to
section 224.1.1 further explains that compliance with 224.5 is more likely to
be achieved if all of the accessible guest rooms are not provided in the same
area of the facility, when accessible guest rooms are added as a result of
subsequent alterations. Some commenters requested a specific exemption for
small hotels of 300 or fewer guest rooms from dispersion regarding smoking
rooms. The ADA requires that individuals with disabilities be provided with
the same range of options as persons without disabilities, and, therefore, the
Department declines to add such an exemption. It is noted, however, that the
existence of this language in the advisory does not require a place of
transient lodging that does not offer smoking guest rooms at its facility to
do so only for individuals with disabilities.
Guest Rooms with Mobility Features. Scoping provisions for
guest rooms with mobility features are provided in section 224.2 of the 2010
Standards. Scoping requirements for alterations are included in 224.1.1. These
scoping requirements in the 2010 Standards are consistent with the 1991
Standards. One commenter expressed opposition to the new scoping provisions
for altered guest rooms, which, according to the commenter, require greater
numbers of accessible guest rooms with mobility features. Section 224.1.1 of
the 2010 Standards provides scoping requirements for alterations to guest
rooms in existing facilities. Section 224.1.1 modifies the scoping
requirements for new construction in section 224 by limiting the application
of section 224 requirements only to those guest rooms being altered or added
until the number of such accessible guest rooms complies with the minimum
number required for new construction in section 224.2 of the 2010 Standards.
The minimum required number of accessible guest rooms is based on the total
number of guest rooms altered or added instead of the total number of guest
rooms provided. These requirements are consistent with the requirements in the
1991 Standards. Language in the 2010 Standards clarifies the provision of
section 104.2 of the 2010 Standards which requires rounding up values to the
next whole number for calculations of percentages in scoping.
Guest Rooms with Communication Features. The revisions at
section 224.4 of the 2010 Standards effect no substantive change from the 1991
Standards with respect to the number of guest rooms required to provide
communication features. The scoping requirement is consolidated into a single
table, instead of appearing in three sections as in the 1991 Standards. The
revised provisions also limit the overlap between guest rooms required to
provide mobility features and guest rooms required to provide communication
features. Section 224.5 of the 2010 Standards requires that at least one guest
room providing mobility features must also provide communications features. At
least one, but not more than ten percent (10%), of the guest rooms required to
provide mobility features can also satisfy the minimum number of guest rooms
required to provide communication features. Commenters suggested that the
requirements for scoping and dispersion of guest rooms for persons with
mobility impairments and guest rooms with communication features are too
complex for the industry to effectively implement. The Department believes the
requirements for guest rooms with communications features in the 2010
Standards clarify the requirements necessary to provide equal opportunity for
travelers with disabilities. Additional technical assistance will be made
available to address questions before the rule goes into effect.
Visible Alarms in Guest Rooms with Communication Features. The 1991 Standards at sections 9.3.1 and 4.28.4 require transient lodging
guest rooms with communication features to provide either permanently
installed visible alarms that are connected to the building fire alarm system
or portable visible alarms that are connected to a standard 110-volt
electrical outlet and are both activated by the building fire alarm system and
provide a visible alarm when the single station smoke detector is activated.
Section 215.4 of the 2010 Standards no longer includes the portable visible
alarm option and instead requires that transient lodging guest rooms with
communication features be equipped with a fire alarm system which includes
permanently installed audible and visible alarms in accordance with NFPA 72
National Fire Alarm Code (1999 or 2002 edition). Such guest rooms with
communication features are also required by section 806.3.2 of the 2010
Standards to be equipped with visible notification devices that alert room
occupants of incoming telephone calls and a door knock or bell. The 2010
Standards add a new exception for alterations to existing facilities that
exempts existing fire alarm systems from providing visible alarms, unless the
fire alarm system itself is upgraded or replaced, or a new fire alarm system
is installed. Transient lodging facilities that alter guest rooms are not
required to provide permanently installed visible alarms complying with the
NFPA 72 if the existing fire alarm system has not been upgraded or replaced,
or a new fire alarm system has not been installed. Commenters representing
small providers of transient lodging raised concerns about the proposed
changes to prohibit the use of portable visible alarms used in transient
lodging guest rooms. These commenters recommended retaining requirements that
allow the use of portable visible alarms. Persons who are deaf or hard of
hearing have reported that portable visible alarms used in transient lodging
guest rooms are deficient because the alarms are not activated by the building
fire alarm system, and the alarms do not work when the building power source
goes out in emergencies. The 2010 Standards are consistent with the model
building, fire, and life safety codes as applied to newly constructed
transient lodging facilities. One commenter sought confirmation of its
understanding of visible alarm requirements from the Department. This
commenter interpreted the exception to section 215.1 of the 2010 Standards and
the Department´s commentary to the NPRM to mean that if a transient lodging
facility does not have permanently installed visible alarms in its
communication accessible guest rooms, it will not be required to provide such
alarms until such time that its fire alarm system is upgraded or replaced, or
a new fire alarm system is installed. In addition, this commenter also
understood that, if a hotel already has permanently installed visible alarms
in all of its mobility accessible guest rooms, it would not have to relocate
such visible alarms and other communication features in those rooms to other
guest rooms to comply with the ten percent (10%) overlap requirement until the
alarm system is upgraded or replaced. This commenter´s interpretation and
understanding are consistent with the Department´s position in this matter.
Section 215.4 of the 2010 Standards requires that guest rooms required to have
communication features be equipped with a fire alarm system complying with
section 702. Communication accessible guest rooms are required to have all of
the communication features described in section 806.3 of the 2010 Standards
including a fire alarm system which provides both audible and visible alarms.
The exception to section 215.1 of the 2010 Standards, which applies only to
fire alarm requirements for guest rooms with communication features in
existing facilities, exempts the visible alarm requirement until such time as
the existing fire alarm system is upgraded or replaced, or a new fire alarm
system is installed. If guest rooms in existing facilities are altered and
they are required by section 224 of the 2010 Standards to have communication
features, such guest rooms are required by section 806.3 to have all other
communication features including notification devices.
Vanity Counter Space. Section 806.2.4.1 of the 2010 Standards
requires that if vanity countertop space is provided in inaccessible transient
lodging guest bathrooms, comparable vanity space must be provided in
accessible transient lodging guest bathrooms. A commenter questioned whether
in existing facilities vanity countertop space may be provided through the
addition of a shelf. Another commenter found the term "comparable" vague and
expressed concern about confusion the new requirement would cause. This
commenter suggested that the phrase "equal area in square inches" be used
instead of comparable vanity space. In some circumstances, the addition of a
shelf in an existing facility may be a reasonable way to provide a space for
travelers with disabilities to use their toiletries and other personal items.
However, this is a determination that must be made on a case-by-case basis.
Comparable vanity countertop space need not be one continuous surface and need
not be exactly the same size as the countertops in comparable guest bathrooms.
For example, accessible shelving within reach of the lavatory could be stacked
to provide usable surfaces for toiletries and other personal items.
Shower and Sauna Doors in Transient Lodging Facilities.
Section 9.4 of the 1991 Standards and section 206.5.3 of the 2010 Standards
both require passage doors in transient lodging guest rooms that do not
provide mobility features to provide at least 32 inches of clear width.
Congress directed this requirement to be included so that individuals with
disabilities could visit guests in other rooms.
See H. Rept. 101-485,
pt. 2, at 118 (1990); S. Rept. 101-116, at 70 (1989). Section 224.1.2 of the
2010 Standards adds a new exception to clarify that shower and sauna doors in
such inaccessible guest rooms are exempt from the requirement for passage
doors to provide at least 32 inches of clear width. Two commenters requested
that saunas and steam rooms in existing facilities be exempt from the section
224.1.2 requirement and that the requirement be made applicable to new
construction only. The exemption to the section 224.1.2 requirement for a
32-inch wide clearance at doors to shower and saunas applies only to those
showers and saunas in guest rooms which are not required to have mobility
features. Showers and saunas in other locations, including those in common use
areas and guest rooms with mobility features, are required to comply with the
32-inch clear width standard as well as other applicable accessibility
standards. Saunas come in a variety of types: portable, pre-built, pre-cut,
and custom-made. All saunas except for custom-made saunas are made to
manufacturers´ standard dimensions. The Department is aware that creating the
required 32-inch clearance at existing narrower doorways may not always be
technically feasible. However, the Department believes that owners and
operators will have an opportunity to provide the required doorway clearance,
unless doing so is technically infeasible, when an alteration to an existing
sauna is undertaken. Therefore, the Department has retained these
requirements.
Platform Lifts in Transient Lodging Guest Rooms and Dwelling Units. The 1991 Standards, at section 4.1.3(5), exception 4, and the 2010 Standards,
at sections 206.7 and 206.7.6, both limit the locations where platform lifts
are permitted to be used as part of an accessible route. The 2010 Standards
add a new scoping requirement that permits platform lifts to be used to
connect levels within transient lodging guest rooms and dwelling units with
mobility features.
806 Transient Lodging Guest Rooms
In the NPRM, the Department included floor plans showing examples of
accessible guest rooms and bathrooms designs with mobility features to
illustrate how compliance with the 2010 Standards could be accomplished with
little or no additional space compared to designs that comply with the 1991
Standards. Commenters noted that the Department´s plans showing accessible
transient lodging guest rooms compliant with the 2010 Standards were not
common in the transient lodging industry and also noted that the plans omitted
doors at sleeping room closets. The Department agrees that the configuration
of the accessible bathrooms is somewhat different from past designs used by
the industry, but this was done to meet the requirements of the 2010
Standards. The plans were provided to show that, with some redesign, the 2010
Standards do not normally increase the square footage of an accessible
sleeping room or bathroom with mobility features in new construction. The
Department has also modified several accessible guest room plans to show that
doors can be installed on closets and comply with the 2010 Standards. A
commenter stated that the Department´s drawings suggest that the fan coil
units for heat and air conditioning are overhead, while the typical sleeping
room usually has a vertical unit, or a packaged terminal air conditioning unit
within the room. The Department´s drawings are sample plans, showing the
layout of the space, relationship of elements to each other, and required
clear floor and turning spaces. It was not the intent of the Department to
provide precise locations for all elements, including heating and air
conditioning units. Commenters noted that in guest rooms with two beds, each
bed was positioned close to a wall, reducing access on one side. Another
commenter stated that additional housekeeping time is needed to clean the room
when beds are placed closer to walls. The 2010 Standards require that, when
two beds are provided, there must be at least 36 inches of clear space between
the beds. The plans provided in the NPRM showed two bed arrangements with
adequate clear width complying with the 1991 Standards and the 2010 Standards.
Additional space can be provided on the other side of the beds to facilitate
housekeeping as long as the clear floor space between beds is at least 36
inches wide. Commenters stated that chases in sleeping room bathrooms that
route plumbing and other utilities can present challenges when modifying
existing facilities. In multi-story facilities, relocating or re-routing these
elements may not be possible, limiting options for providing access. The
Department recognizes that relocating mechanical chases in multi-story
facilities may be difficult or impossible to accomplish. While these issues do
not exist in new facilities, altered existing facilities must comply with the
2010 Standards to the extent that it is technically feasible to do so. When an
alteration cannot fully comply because it is technically infeasible to do so,
the alteration must still be designed to comply to the greatest extent
feasible. Commenters noted that on some of the Department´s plans where a
vanity is located adjacent to a bathtub, the vanity may require more
maintenance due to exposure to water. The Department agrees that it would be
advisable that items placed next to a bathtub or shower be made of materials
that are not susceptible to water damage.
Transient Lodging Guest Room Floor Plans and Related Text
The Department has included the following floor plans showing application of
the requirements of the 2010 Standards without significant loss of guest room
living space in transient lodging compared to the 1991 Standards.
Plan 1A: 13-Foot Wide Accessible Guest Room
This drawing shows an accessible 13-foot wide guest room with features
that comply with the 2010 Standards. Features include a standard
bathtub with a seat, comparable vanity, clothes closet with swinging
doors, and door connecting to adjacent guest room. Furnishings include
a king bed and additional seating.
|
|
The following accessible features are provided in the bathroom:
- Comparable vanity counter top space (section 806);
- Bathtub with a lavatory at the control end (section 607.2);
- Removable bathtub seat (section 607.3);
-
Clearance in front of the bathtub extends its full length and is
30 inches wide min. (section 607.2);
-
Recessed bathtub location permits shorter rear grab bar at water
closet (section 604.5.2);
- Circular turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Turning space includes knee and toe clearance at lavatory (section
304.3);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16-18 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3).
The following accessible features are provided in the living area:
- T-shaped turning space (section 304.3.2);
- Accessible route (section 402);
-
Clear floor space on both sides of the bed (section 806.2.3);
-
Maneuvering clearances at all doors (section 404.2);Accessible
operable window (section 309); and
-
Accessible controls for the heat and air conditioning (section
309).
|
Plan 1B: 13-Foot Wide Accessible Guest Room
This drawing shows an accessible 13-foot wide guest room with features
that comply with the 2010 Standards. Features include a standard
bathtub with a seat, comparable vanity, clothes closet with swinging
doors, and door connecting to adjacent guest room. Furnishings include
two beds.
|
|
The following accessible features are provided in the bathroom:
-
Comparable vanity counter top space (section 806);
-
Bathtub with a lavatory at the control end (section 607.2);
-
Removable bathtub seat (section 607.3);
-
Clearance in front of the bathtub extends its full length and is
30 inches wide min. (section 607.2);
-
Recessed bathtub location permits shorter rear grab bar at water
closet (section 604.5.2);
-
Circular turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Turning space includes knee and toe clearance at lavatory (section
304.3);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16-18 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3);
The following accessible features are provided in the living area:
-
T-shaped turning space (section 304.3.2);
- Accessible route (section 402);
-
Clear floor space between beds (section 806.2.3);
-
Maneuvering clearances at all doors (section 404.2);
-
Accessible operable window (section 309); and
-
Accessible controls for the heat and air conditioning (section
309).
|
Plan 2A: 13-Foot Wide Accessible Guest Room
This drawing shows an accessible 13-foot wide guest room with features
that comply with the 2010 Standards. Features include a standard
roll-in shower with a seat, comparable vanity, wardrobe, and door
connecting to adjacent guest room. Furnishings include a king bed and
additional seating.
|
|
The following accessible features are provided in the bathroom:
-
Comparable vanity counter top space (section 806);
-
Standard roll-in type shower with folding seat (section 608.2.2);
-
Recessed roll-in shower location permits shorter rear grab bar at
water closet (section 604.5.2);
-
Clear floor space adjacent to shower min. 30 inches wide by 60
inches long (section 608.2.2);
-
Circular turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Turning space includes knee and toe clearance at lavatory (section
304.3);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16-18 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3).
The following accessible features are provided in the living area:
-
T-shaped turning space (section 304.3.2);
- Accessible route (section 402);
-
Clear floor space on both sides of the bed (section 806.2.3);
-
Maneuvering clearances at all doors (section 404.2);
-
Accessible operable window (section 309); and
-
Accessible controls for the heat and air conditioning (section
309).
|
Plan 2B: 13-Foot Wide Accessible Guest Room
This drawing shows an accessible 13-foot wide guest room with features
that comply with the 2010 Standards. Features include an alternate
roll-in shower with a seat, comparable vanity, wardrobe, and door
connecting to adjacent guest room. Furnishings include two beds.
|
|
The following accessible features are provided in the bathroom:
- Comparable vanity counter top space (section 806);
-
Alternate roll-in type shower with folding seat is 36 inches deep
and 60 inches wide (section 608.2.3);
-
Alternate roll-in shower has a 36-inch wide entry at one end of
the long side of the compartment (section 608.2.3);
-
Recessed alternate roll-in shower location permits shorter rear
grab bar at water closet (section 604.5.2);
- Circular turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Turning space includes knee and toe clearance at lavatory (section
304.3);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16-18 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3)
The following accessible features are provided in the living area:
- T-shaped turning space (section 304.3.2);
- Accessible route (section 402);
- Clear floor space between beds (section 806.2.3);
- Maneuvering clearances at all doors (section 404.2);
- Accessible operable window (section 309); and
-
Accessible controls for the heat and air conditioning (section
309).
|
Plan 3A: 12-Foot Wide Accessible Guest Room
This drawing shows an accessible 12-foot wide guest room with features
that comply with the 2010 Standards. Features include a bathtub with a
seat, comparable vanity, open clothes closet, and door connecting to
adjacent guest room. Furnishings include a king bed and additional
seating.
|
|
The following accessible features are provided in the bathroom:
- Comparable vanity counter top space (section 806);
- Bathtub (section 607.2);
- Removable bathtub seat (section 607.3);
-
Clearance in front of the bathtub extends its full length and is
30 inches wide min. (section 607.2);
-
Recessed lavatory with vanity countertop permits shorter rear grab
bar at water closet (section 604.5.2);
- Circular turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Turning space includes knee and toe clearance at lavatory (section
304.3);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16-18 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3).
The following accessible features are provided in the living area:
- T-shaped turning space (section 304.3.2);
- Accessible route (section 402);
-
Clear floor space on both sides of the bed (section 806.2.3);
- Maneuvering clearances at all doors (section 404.2);
- Accessible operable window (section 309); and
-
Accessible controls for the heat and air conditioning (section
309).
|
Plan 3B: 12-Foot Wide Accessible Guest Room
This drawing shows an accessible 12-foot wide guest room with features
that comply with the 2010 Standards. Features include a standard
roll-in shower with a seat, comparable vanity, wardrobe, and door
connecting to adjacent guest room. Furnishings include two beds.
|
|
The following accessible features are provided in the bathroom:
-
The following accessible features are provided in the bathroom:
- Comparable vanity counter top space (section 806);
-
Standard roll-in type shower with folding seat (section 608.2.2);
-
Recessed lavatory with vanity counter top permits shorter rear
grab bar at water closet (section 604.5.2);
-
Clear floor space adjacent to shower min. 30 inches wide by 60
inches long (section 608.2.2);
- Circular turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Turning space includes knee and toe clearance at lavatory (section
304.3);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16-18 inches from side wall
(section 604.2); and
No other fixtures or obstructions located within required water closet
clearance (section 604.3). The following accessible features are
provided in the living area:
- T-shaped turning space (section 304.3.2);
- Accessible route (section 402);
- Clear floor space between beds (section 806.2.3);
- Maneuvering clearances at all doors (section 404.2);
- Accessible operable window (section 309); and
-
Accessible controls for the heat and air conditioning (section
309).
|
Plan 4A: 13-Foot Wide Accessible Guest Room
This drawing shows an accessible 13-foot wide guest room with features
that comply with the 2010 Standards. Features include a standard
roll-in shower with a seat, comparable vanity, clothes closet with
swinging doors, and door connecting to adjacent guest room.
Furnishings include a king bed and additional seating.
|
|
The following accessible features are provided in the bathroom:
- Comparable vanity counter top space (section 806);
-
Standard roll-in type shower with folding seat (section 608.2.2);
-
Clear floor space adjacent to shower min. 30 inches wide by 60
inches long (section 608.2.2);
-
Recessed roll-in shower location permits shorter rear grab bar at
water closet (section 604.5.2);
- Circular turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Turning space includes knee and toe clearance at lavatory (section
304.3);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16-18 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3).
-
30-inch wide by 48-inch long minimum clear floor space provided
beyond the arc of the swing of the entry door (section 603.2.3
exception 2).
The following accessible features are provided in the living area:
- T-shaped turning space (section 304.3.2);
- Accessible route (section 402);
-
Clear floor space on both sides of the bed (section 806.2.3);
- Maneuvering clearances at all doors (section 404.2);
- Accessible operable window (section 309); and
-
Accessible controls for the heat and air conditioning (section
309). 13’-0” 7’-6” 15’-4
|
Plan 4B: 13-Foot Wide Accessible Guest Room
This drawing shows an accessible 13-foot wide guest room with features
that comply with the 2010 Standards. Features include an alternate
roll-in shower with a seat, comparable vanity, wardrobe, and door
connecting to adjacent guest room. Furnishings include two beds.
|
|
The following accessible features are provided in the bathroom:
- Comparable vanity counter top space (section 806);
-
Alternate roll-in type shower with folding seat is 36 inches deep
and 60 inches wide (section 608.2.3);
-
Alternate roll-in shower has a 36-inch wide entry at one end of
the long end of the compartment (section 608.2.3);
-
Recessed alternate roll-in shower location permits shorter rear
grab bar at water closet (section 604.5.2);
- Circular turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Turning space includes knee and toe clearance at lavatory (section
304.3);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16-18 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3).
The following accessible features are provided in the living area:
- T-shaped turning space (section 304.3.2);
- Accessible route (section 402);
- Clear floor space between beds (section 806.2.3);
- Maneuvering clearances at all doors (section 404.2);
- Accessible operable window (section 309); and
-
Accessible controls for the heat and air conditioning (section
309).
|
Plan 5A: 13-Foot Wide Accessible Guest Room
This drawing shows an accessible 13-foot wide guest room with features
that comply with the 2010 Standards. Features include a transfer
shower, comparable vanity, clothes closet with swinging door, and door
connecting to adjacent guest room. Furnishings include a king bed and
additional seating.
|
|
The following accessible features are provided in the bathroom:
- Comparable vanity counter top space (section 806);
- Transfer shower (section 603.2);
- Shower seat (section 610.3);
-
Clearance in front of the shower extends beyond the seat and is 36
inches wide min. (section 607.2);
-
Recessed transfer shower location permits shorter rear grab bar at
water closet (section 604.5.2);
- Circular turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3).
The following accessible features are provided in the living area:
- Circular turning space (section 304.3.2);
- Accessible route (section 402);
-
Clear floor space on both sides of the bed (section 806.2.3);
- Maneuvering clearances at all doors (section 404.2);
- Accessible operable window (section 229); and
-
Accessible controls for the heat and air conditioning (section
309).
|
Plan 5B: 13-Foot Wide Accessible Guest Room
This drawing shows an accessible 13-foot wide guest room with features
that comply with the 2010 Standards. Features include a transfer
shower, comparable vanity, open clothes closet, and door connecting to
adjacent guest room. Furnishings include two beds.
|
|
The following accessible features are provided in the bathroom:
- Comparable vanity counter top space (section 806);
- Transfer shower (section 603.2);
- Shower seat (section 610.3);
-
Clearance in front of the shower extends beyond the seat and is 36
inches wide min. (section 607.2);
-
Lavatory with vanity counter top recessed to permit shorter rear
grab bar at water closet (section 604.5.2);
- T-shaped turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16-18 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3).
The following accessible features are provided in the living area:
- T-shaped turning space (section 304.3.2);
- Accessible route (section 402);
- Clear floor space between beds (section 806.2.3);
- Maneuvering clearances at all doors (section 404.2);
- Accessible operable window (section 229); and
-
Accessible controls for the heat and air conditioning (section
309).
|
Plan 6A: 12-Foot Wide Accessible Guest Room
This drawing shows an accessible 12-foot wide guest room with features
that comply with the 2010 Standards. Features include a transfer
shower, water closet length (rim to rear wall) 24 inches maximum,
comparable vanity, clothes closet with swinging door, and door
connecting to adjacent guest room. Furnishings include a king bed and
additional seating.
|
|
The following accessible features are provided in the bathroom:
- Comparable vanity counter top space (section 806);
- Transfer shower (section 603.2);
- Shower seat (section 610.3);
-
Clearance in front of the shower extends beyond the seat and is 36
inches wide min. (section 607.2);
-
Recessed lavatory with vanity counter top permits shorter rear
grab bar at water closet (section 604.5.2);
- T-shaped turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3).
The following accessible features are provided in the living area:
- T-shaped turning space (section 304.3.2);
- Accessible route (section 402);
-
Clear floor space on both sides of the bed (section 806.2.3);
- Maneuvering clearances at all doors (section 404.2);
- Accessible operable window (section 229); and
-
Accessible controls for the heat and air conditioning (section
309).
|
Plan 6B: 12-Foot Wide Accessible Guest Room
This drawing shows an accessible 12-foot wide guest room with features
that comply with the 2010 Standards. Features include a transfer
shower, water closet length (rim to rear wall) 24 inches maximum,
comparable vanity, wardrobe, and door connecting to adjacent guest
room. Furnishings include two beds.
|
|
The following accessible features are provided in the bathroom:
- Comparable vanity counter top space (section 806);
- Transfer shower (section 603.2);
- Shower seat (section 610.3);
-
Clearance in front of the shower extends beyond the seat and is 36
inches wide min. (section 607.2);
-
Recessed lavatory with vanity counter top permits shorter rear
grab bar at water closet (section 604.5.2);
- T-shaped turning space in room (section 603.2.1);
-
Required clear floor spaces at fixtures and turning space overlap
(section 603.2.2);
-
Water closet clearance is 60 inches at back wall and 56 inches
deep (section 604.3);
-
Centerline of the water closet at 16 inches from side wall
(section 604.2); and
-
No other fixtures or obstructions located within required water
closet clearance (section 604.3).
The following accessible features are provided in the living area:
- Circular turning space (section 304.3.2);
- Accessible route (section 402);
- Clear floor space between beds (section 806.2.3);
- Maneuvering clearances at all doors (section 404.2);
- Accessible operable window (section 229); and
-
Accessible controls for the heat and air conditioning (section
309).
|
225 and 811 Storage
Section 225 of the 2010 Standards provides that where storage is provided in
accessible spaces, at least one of each type shall comply with the 2010
Standards. Self-service shelving is required to be on an accessible route, but
is not required to comply with the reach range requirements. These
requirements are consistent with the 1991 Standards. Section 225.3 adds a new
scoping requirement for self-storage facilities. Facilities with 200 or fewer
storage spaces will be required to make at least five percent (5%) of the
storage spaces accessible. Facilities with more than 200 storage spaces will
be required to provide ten accessible storage spaces, plus two percent (2%) of
the total storage spaces over 200. Sections 225.2.1 and 811 of the 2010
Standards require lockers to meet accessibility requirements. Where lockers
are provided in clusters, five percent (5%) but at least one locker in each
cluster will have to comply. Under the 1991 Standards, only one locker of each
type provided must be accessible. Commenters recommended that the Department
adopt language requiring public accommodations to provide access to all
self-service shelves and display areas available to customers. Other
commenters opposed this requirement as too burdensome to retail and other
entities and claimed that significant revenue would be lost if this
requirement were to be implemented. Other commenters raised concerns that
section 225.2.2 of the 2010 Standards scopes only self-service shelving
whereas section 4.1.3(12)(b) of the 1991 Standards applies to both "shelves or
display units." Although "display units" were not included in the 2010
Standards under the belief that displays are not to be touched and therefore
by definition cannot be "self-service," both the 2010 Standards and the 1991
Standards should be read broadly to apply to all types of shelves, racks,
hooks, and similar self-service merchandising fittings, including self-service
display units. Such fixtures are permitted to be installed above or below the
reach ranges possible for many persons with disabilities so that space
available for merchandising is used as efficiently as possible.
226 and 902 Dining Surfaces and Work Surfaces
Section 226.1 of the 2010 Standards require that where dining surfaces are
provided for the consumption of food or drink, at least five percent (5%) of
the seating spaces and standing spaces at the dining surfaces comply with
section 902. Section 902.2 requires the provision of accessible knee and toe
clearance. Commenters stated that basing accessible seating on seating spaces
and standing spaces potentially represents a significant increase in scoping,
particularly given the ambiguity in what represents a "standing space" and
urged a return to the 1991 Standard of requiring accessible seating based on
fixed dining tables. The scoping change merely takes into account that tables
may vary in size so that basing the calculation on the number of tables rather
than on the number of individuals that may be accommodated by the tables could
unnecessarily restrict opportunities for persons with disabilities. The
revised scoping permits greater flexibility by allowing designers to disperse
accessible seating and standing spaces throughout the dining area. Human
factors data, which is readily available to designers, provides information
about the amount of space required for both eating and drinking while seated
or standing.
227 and 904 Sales and Service
Check-Out Aisles and Sales and Service Counters. The 1991
Standards, at section 7.2, and the 2010 Standards, at section 904.4, contain
technical requirements for sales and service counters. The 1991 Standards
generally require sales and service counters to provide an accessible portion
at least 36 inches long and no higher than 36 inches above the finish floor.
The nondiscrimination requirements of the ADA regulations require the level of
service provided at the accessible portion of any sales and service counter to
be the same as the level of service provided at the inaccessible portions of
the counter. The 2010 Standards specify different lengths for the accessible
portion of sales and service counters based on the type of approach provided.
Where a forward approach is provided, the accessible portion of the counter
must be at least 30 inches long and no higher than 36 inches, and knee and toe
space must be provided under the counter. The requirement that knee and toe
space be provided where only clear floor space for a forward approach to a
sales and service counter is provided is not a new requirement. It is a
clarification of the ongoing requirement that part of the sales and service
counter be accessible. This requirement applies to the entire accessible part
of sales and service counters and requires that the accessible clear floor or
ground space adjacent to those counters be kept clear of merchandise,
equipment, and other items so that the accessible part of the counter is
readily accessible to and usable by individuals with disabilities. The
accessible part of the counter must also be staffed and provide an equivalent
level of service as that provided to all customers. Where clear floor space
for a parallel approach is provided, the accessible portion of the counter
must be at least 36 inches long and no higher than 36 inches above the finish
floor. A clear floor or ground space that is at least 48 inches long x 30
inches wide must be provided positioned for a parallel approach adjacent to
the 36-inch minimum length of counter. Section 904.4 of the 2010 Standards
includes an exception for alterations to sales and service counters in
existing facilities. It permits the accessible portion of the counter to be at
least 24 inches long, where providing a longer accessible counter will result
in a reduction in the number of existing counters at work stations or existing
mailboxes, provided that the required clear floor or ground space is centered
on the accessible length of the counter. Section 904.4 of the 2010 Standards
also clarifies that the accessible portion of the counter must extend the same
depth as the sales or service counter top. Where the counter is a
single-height counter, this requirement applies across the entire depth of the
counter top. Where the counter is a split-height counter, this requirement
applies only to the customer side of the counter top. The employee-side of the
counter top may be higher or lower than the customer-side of the counter top.
Commenters recommended that the Department consider a regulatory alternative
exempting small retailers from the new knee and toe clearance requirement and
retaining existing wheelchair accessibility standards for sales and service
counters. These commenters believed that the knee and toe clearance
requirements will cause a reduction in the sales and inventory space at
check-out aisles and other sales and service counters. Both the 1991 and the
2010 Standards permit covered entities to determine whether they will provide
a forward or a parallel approach to sales and service counters. So any
facility that does not wish to provide the knee or toe clearance required for
a front approach to such a counter may avoid that option. However, the
Department believes that permitting a forward approach without requiring knee
and toe clearance is not adequate to provide accessibility because the person
using a wheelchair will be prevented from coming close enough to the counter
to see the merchandise or to transact business with a degree of convenience
that is comparable to that provided to other customers. A parallel approach to
sales and service counters also can provide the accessibility required by the
2010 Standards. Individuals using wheelchairs can approach sales and service
counters from the side, and, assuming the necessary elements, features, or
merchandise necessary to complete a business transaction are within the reach
range requirements for a side approach, the needs of individuals with
disabilities can be met effectively. Section 227 of the 2010 Standards
clarifies the requirements for food service lines. Queues and waiting lines
serving counters or check-out aisles, including those for food service, must
be accessible to individuals with disabilities.
229 Windows
A new requirement at section 229.1 of the 2010 Standards provides that if
operable windows are provided for building users, then at least one window in
an accessible space must be equipped with controls that comply with section
309. Commenters generally supported this provision but some commenters asked
whether the maximum five-pounds (5 lbs.) of force requirement of section 309
applies to the window latch itself or only to the force required to open the
window. Section 309 applies to all controls and operating mechanisms, so the
latch must comply with the requirement to operate with no more than five
pounds of force (5 lbf).
230 and 708 Two-Way Communication Systems
New provisions of the 2010 Standards at sections 230.1 and 708 require two-way
communications systems to be equipped with visible as well as audible signals.
231 and 808 Judicial Facilities and Courtrooms
Section 231 of the 2010 Standards adds requirements for accessible courtrooms,
holding cells, and visiting areas.
Accessible Courtroom Stations. Sections 231.2, 808, 304, 305,
and 902 of the 2010 Standards provide increased accessibility at courtroom
stations. Clear floor space for a forward approach is required for all
courtroom stations (judges´ benches, clerks´ stations, bailiffs´ stations,
deputy clerks´ stations, court reporters´ stations, and litigants´ and counsel
stations). Other applicable specifications include accessible work surface
heights and toe and knee clearance.
Accessible Jury Boxes, Attorney Areas, and Witness Stands.
Section 206.2.4 of the 2010 Standards requires, in new construction and
alterations, at least one accessible route to connect accessible building or
facility entrances with all accessible spaces and elements within the building
or facility that are connected by a circulation path unless they are exempted
by Exceptions 1 - 7 of section 206.2.3. Advisory 206.2.4 Spaces and Elements
Exception 1 explains that the exception allowing raised courtroom stations to
be used by court employees, such as judge´s benches, to be adaptable does not
apply to areas of the courtroom likely to be used by members of the public
such as jury areas, attorney areas, or witness stands. These areas must be on
an accessible route at the time of initial construction or alteration.
Raised Courtroom Stations Not for Members of the Public.
Section 206.2.4, Exception 1 of the 2010 Standards provides that raised
courtroom stations that are used by judges, clerks, bailiffs, and court
reporters will not have to provide full vertical access when first constructed
or altered if they are constructed to be easily adaptable to provide vertical
accessibility. One commenter suggested that a sufficient number of accessible
benches for judges with disabilities, in addition to requiring accessible
witness stands and attorney areas, be required. The Department believes that
the requirements regarding raised benches for judges are easily adaptable to
provide vertical access in the event a judge requires an accessible bench.
Section 206.2.4 of the 2010 Standards provides that raised courtroom stations
used by judges and other judicial staff do not have to provide full vertical
access when first constructed or altered as long as the required clear floor
space, maneuvering space, and electrical service, where appropriate, is
provided at the time of new construction or can be achieved without
substantial reconstruction during alterations. A commenter asserted that there
is nothing inherent in clerks´ stations, jury boxes, and witness stands that
require them to be raised. While it would, of course, be easiest to provide
access by eliminating height differences among courtroom elements, the
Department recognizes that accessibility is only one factor that must be
considered in the design process of a functioning courtroom. The need to
ensure the ability of the judge to maintain order, the need to ensure sight
lines among the judge, the witness, the jury, and other participants, and the
need to maintain the security of the participants all affect the design of the
space. The Department believes that the 2010 Standards have been drafted in a
way that will achieve accessibility without unduly constraining the ability of
a designer to address the other considerations that are unique to courtrooms.
Commenters argued that permitting courtroom stations to be adaptable rather
than fully accessible at the time of new construction likely will lead to
discrimination in hiring of clerks, court reporters, and other court staff.
The Department believes that the provisions will facilitate, not hinder, the
hiring of court personnel who have disabilities. All courtroom work stations
will be on accessible routes and will be required to have all fixed elements
designed in compliance with the 2010 Standards. Elevated work stations for
court employees may be designed to add vertical access as needed. Since the
original design must provide the proper space and electrical wiring to install
vertical access, the change should be easily accomplished.
232 Detention Facilities and Correctional Facilities
Section 232 of the 2010 Standards establishes requirements for the design and
construction of cells, medical care facilities, and visiting areas in
detention facilities and in correctional facilities. Section 35.151(k) of the
Department´s title II rule provides scoping for newly constructed general
holding cells and general housing cells requiring mobility features compliant
with section 807.2 of the 2010 Standards in a minimum of three percent (3%) of
cells, but no fewer than one cell. Section 232.2 of the 2010 Standards
provides scoping for newly constructed cells with communications features
requiring a minimum of two percent (2%) of cells, but at least one cell, to
have communication features. The Department´s title II rule at § 35.151(k)
also specifies scoping for alterations to detention and correctional
facilities. Generally a minimum of three percent (3%), but no fewer than one,
of the total number of altered cells must comply with section 807.2 of the
2010 Standards and be provided within each facility. Altered cells with
mobility features must be provided in each classification level, including
administrative and disciplinary segregation, each use and service area, and
special program. The Department notes that the three percent (3%), but no
fewer than one, requirement is a minimum. As corrections systems plan for new
facilities or alterations, the Department urges planners to include in their
population estimates a projection of the numbers of inmates with disabilities
so as to have sufficient numbers of accessible cells to meet inmate needs.
233 Residential Facilities
Homeless Shelters, Group Homes, and Similar Social Service
Establishments.
Section 233 of the 2010 Standards includes specific scoping and technical
provisions that apply to new construction and alteration of residential
facilities. In the 1991 Standards scoping and technical requirements for
homeless shelters, group homes, and similar social service establishments were
included in section 9 Transient Lodging. These types of facilities will be
covered by section 233 of the 2010 Standards and by 28 CFR 35.151(e) and
36.406(d) and will be subject to requirements for residential facilities
rather than the requirements for transient lodging. This approach will
harmonize federal accessibility obligations under both the ADA and section 504
of the Rehabilitation Act of 1973, as amended. In sleeping rooms with more
than 25 beds that are covered by § 36.406(d) a minimum of five percent (5%) of
the beds must have clear floor space compliant with section 806.2.3 of the
2010 Standards. In large facilities with more than 50 beds, at least one
roll-in shower compliant with section 608.2.2 or section 608.2.3 of the 2010
Standards must be provided. Where separate shower facilities are provided for
men and for women, at least one roll-in shower must be provided for each
gender.
Housing Operated By or On Behalf of Places of Education.
Housing at a place of education includes: residence halls, dormitories,
suites, apartments, or other places of residence operated by or on behalf of
places of education. Residence halls or dormitories operated by or on behalf
of places of education are covered by the provisions in sections 224 and 806
of the 2010 Standards. The Department has included in the title III rule at §
36.406(e) requirements that apply to housing at places of education that
clarify requirements for residence halls and dormitories and other types of
student housing. Requirements for housing at a place of education covered by
the title II rule are included at § 35.151(f).
Kitchens and Kitchenettes. Section 4.34.2 of the UFAS
requires a clear turning space at least 60 inches in diameter or an equivalent
T-shaped turning space in kitchens. Section 4.34.6 requires a clearance
between opposing base cabinets, counters, appliances, or walls of at least 40
inches except in a U-shaped kitchen where the minimum clearance is 60 inches.
Section 804 of the 2010 Standards provides technical requirements for kitchens
and kitchenettes. Section 804.2.1 requires that pass through kitchens, which
have two entries and counters, appliances, or cabinets on two opposite sides
or opposite a parallel wall, provide at least 40 inches minimum clearance.
Section 804.2.2 requires that U-shaped kitchens, which are enclosed on three
continuous sides, provide at least 60 inches minimum clearance between all
opposing base cabinets, countertops, appliances, or walls within kitchen work
areas. Kitchens that do not have a cooktop or conventional range are exempt
from the clearance requirements but still must provide an accessible route. If
a kitchen does not have two entries, the 2010 Standards require the kitchen to
have 60 inches minimum clearance between the opposing base cabinets, counters,
appliances, or walls. One commenter supported the provisions of section 804 of
the 2010 Standards but sought clarification whether this section applies to
residential units only, or to lodging and office buildings as well. Section
212 makes section 804 applicable to all kitchens and kitchenettes in covered
buildings.
Residential Facilities. Section 4.1.4(11) of the UFAS
contains scoping requirements for the new construction of housing. Under the
1991 title II regulation, state and local governments had the option of
complying with the UFAS or the 1991 Standards. After the compliance date for
the 2010 Standards, state and local governments will no longer have the option
of complying with the UFAS, but will have to use the 2010 Standards for new
construction and alterations. Sections 233.1, 233.2, 233.3, 233.3.1, and
233.3.2 of the 2010 Standards differentiate between entities subject to the
United States Department of Housing and Urban Development (HUD) regulations
implementing section 504 of the Rehabilitation Act of 1973 and entities not
subject to the HUD regulations. The HUD regulations apply to recipients of
federal financial assistance through HUD, and require at least five percent
(5%) of dwelling units in multi-family projects of five or more dwelling units
to provide mobility features and at least two percent (2%) of the dwelling
units to provide communication features. The HUD regulations define a project
unique to its programs as "one or more residential structures which are
covered by a single contract for federal financial assistance or application
for assistance, or are treated as a whole for processing purposes, whether or
not located on a common site." To avoid any potential conflicts with the HUD
regulations, the 2010 Standards require residential dwelling units subject to
the HUD regulations to comply with the scoping requirements in the HUD
regulations, instead of the scoping requirements in the 2010 Standards. For
entities not subject to the HUD regulations, the 2010 Standards require at
least five percent (5%) of the dwelling units in residential facilities to
provide mobility features, and at least two percent (2%) of the dwelling units
to provide communication features. The 2010 Standards define facilities in
terms of buildings located on a site. The 2010 Standards permit facilities
that contain 15 or fewer dwelling units to apply the scoping requirements to
all the dwelling units that are constructed under a single contract, or are
developed as whole, whether or not located on a common site.
Alterations to Residential Facilities. Section 4.1.6 of the
UFAS requires federal, state, and local government housing to comply with the
general requirements for alterations to facilities. Applying the general
requirements for alterations to housing can result in partially accessible
dwelling units where single elements or spaces in dwelling units are altered.
The 2010 Standards, at sections 202.3 Exception 3, 202.4, and 233.3, contain
specific scoping requirements for alterations to dwelling units. Dwelling
units that are not required to be accessible are exempt from the general
requirements for alterations to elements and spaces and for alterations to
primary function areas. The scoping requirements for alterations to dwelling
units generally are based on the requirements in the UFAS:
-
Where a building is vacated for purposes of alterations and has more than
15 dwelling units, at least five percent (5%) of the altered dwelling
units are required to provide mobility features and at least two percent
(2%) of the dwelling units are required to provide communication features.
-
Where a bathroom or a kitchen is substantially altered in an individual
dwelling unit and at least one other room is also altered, the dwelling
unit is required to comply with the scoping requirements for new
construction until the total number of dwelling units in the facility
required to provide mobility features and communication features is met.
As with new construction, the 2010 Standards permit facilities that contain 15
or fewer dwelling units to apply the scoping requirements to all the dwelling
units that are altered under a single contract, or are developed as a whole,
whether or not located on a common site. The 2010 Standards also permit a
comparable dwelling unit to provide mobility features where it is not
technically feasible for the altered dwelling unit to comply with the
technical requirements.
234 and 1002 Amusement Rides
New and Altered Permanently Installed Amusement Rides.
Section 234 of the 2010 Standards sets out scoping requirements and section
1002 sets out the technical requirements for the accessibility of permanently
installed amusement rides. These requirements apply to newly designed and
constructed amusement rides and used rides when certain alterations are made.
A commenter raised concerns that smaller amusement parks tend to purchase used
rides more frequently than new rides, and that the conversion of a used ride
to provide the required accessibility may be difficult to ensure because of
the possible complications in modifying equipment to provide accessibility.
The Department agrees with this commenter. The Department notes, however, that
the 2010 Standards will require modifications to existing amusement rides when
a ride´s structural and operational characteristics are altered to the extent
that the ride´s performance differs from that specified by the manufacturer or
the original design. Such an extensive alteration to an amusement ride may
well require that new load and unload areas be designed and constructed. When
load and unload areas serving existing amusement rides are newly designed and
constructed they must be level, provide wheelchair turning space, and be on an
accessible route compliant with Chapter 4 of the 2010 Standards except as
modified by section 1002.2 of the 2010 Standards.
Mobile or Portable Amusement Rides. The exception in section
234.1 of the 2010 Standards exempts mobile or portable amusement rides, such
as those set up for short periods of time at carnivals, fairs or festivals,
from having to comply with the 2010 Standards. However, even though the
mobile/portable ride itself is not subject to the Standards, these facilities
are still subject to the ADA´s general requirement to ensure that individuals
with disabilities have an equal opportunity to enjoy the services and
amenities of these facilities. Subject to these general requirements, mobile
or portable amusement rides should be located on an accessible route and the
load and unload areas serving a ride should provide a level wheelchair turning
space to provide equal opportunity for individuals with disabilities to be
able to participate on the amusement ride to the extent feasible. One
commenter noted that the exception in Section 234.1 of the 2010 Standards for
mobile or portable amusement rides limits the opportunities of persons with
disabilities to participate on amusement rides because traveling or temporary
amusement rides by their nature come to their customers´ town or a nearby town
rather than the customer having to go to them and so are less expensive than
permanent amusement parks. While the Department understands the commenter´s
concerns, the Department notes that most amusement rides are too complex to be
reasonably modified or re-engineered to accommodate the majority of
individuals with disabilities and that additional complexities and safety
concerns are added when the rides are mobile or portable. A commenter asked
that section 234 of the 2010 Standards make clear that the requirements for
accessible routes include the routes leading up to and including the loading
and unloading areas of amusement rides. Sections 206.2.9 and 1002.2 of the
2010 Standards clarify that the requirements for accessible routes include the
routes leading up to and including the loading and unloading areas of
amusement rides. A commenter requested that the final rule specifically allow
for wheelchair access through the exit or other routes, or alternate means of
wheelchair access routes to amusement rides. The commenter stated that the
concept of wheelchair access through the exit or alternate routes was a base
assumption for the 2010 Standards. The commenter noted that the concept is
apparent in the signage and load/unload area provisions in Section 216.12 (" *
* * where accessible unload areas also serve as accessible load areas, signs
indicating the location of the accessible load and unload areas shall be
provided at entries to queues and waiting lines"). The Department agrees with
the commenter that accessible load and unload areas may be the same where
signs that comply with section 216.12 are provided.
Wheelchair Space or Transfer Seat or Transfer Device.
Sections 234.3 and 1002.4 - 1002.6 of the 2010 Standards provide that each new
and altered amusement ride, except for mobile/portable rides and a few
additional excepted rides, will be required to provide at least one type of
access by means of one wheelchair space or one transfer seat or one transfer
device (the design of the transfer device is not specified). Commenters urged
the Department to revise the requirements for wheelchair spaces and transfer
seats and devices because most amusement rides are too complex to be
reasonably modified or re-engineered to accommodate the majority of
individuals with disabilities. They argued that the experience of amusement
rides will be significantly reduced if the proposed requirements are
implemented. The 2004 ADAAG, which the Department adopted as part of the 2010
Standards, was developed with the assistance of an advisory committee that
included representation from the design staffs of major amusement venues and
from persons with disabilities. The Department believes that the resulting
2004 ADAAG reflected sensitivity to the complex problems posed in adapting
existing rides by focusing on new rides that can be designed from the outset
to be accessible. To permit maximum design flexibility, the 2010 Standards
permit designers to determine whether it is more appropriate to permit
individuals who use wheelchairs to remain in their chairs on the ride, or to
provide for transfer access.
Maneuvering Space in Load and Unload Areas. Sections 234.2
and 1002.3 of the 2010 Standards require that a level wheelchair turning space
be provided at the load and unload areas of each amusement ride. The turning
space must comply with sections 304.2 and 304.3.
Signs Required at Waiting Lines to Amusement Rides. Section
216.12 of the 2010 Standards requires signs at entries to queues and waiting
lines identifying type and location of access for the amusement ride.
235 and 1003 Recreational Boating Facilities
These sections require that accessible boat slips and boarding piers be
provided. Most commenters approved of the requirements for recreational
boating facility accessibility and urged the Department to keep regulatory
language consistent with those provisions. They commented that the
requirements appropriately reflect industry conditions. Individual commenters
and disability organizations agreed that the 2010 Standards achieve acceptable
goals for recreational boating facility access.
Accessible Route. Sections 206.2.10 and 1003.2 of the 2010
Standards require an accessible route to all accessible boating facilities,
including boat slips and boarding piers at boat launch ramps. Section 1003.2.1
provides a list of exceptions applicable to structures such as gangways,
transition plates, floating piers, and structures containing combinations of
these elements that are affected by water level changes. The list of
exceptions specifies alternate design requirements applicable to these
structures which, because of water level variables, cannot comply with the
slope, cross slope, and handrail requirements for fixed ramps contained in
sections 403.3, 405.2, 405.3, 405.6, and 405.7 of the 2010 Standards.
Exceptions 3 and 4 in Section 1003.2.1, which permit a slope greater than that
specified in Section 405.2, are available for structures that meet specified
length requirements. Section 206.7.10 permits the use of platform lifts as an
alternative to gangways that are part of accessible routes. Commenters raised
concerns that because of water level fluctuations it may be difficult to
provide accessible routes to all accessible boating facilities, including boat
slips and boarding piers at boat launch ramps. One of the specific concerns
expressed by several commenters relates to the limits for running slope
permitted on gangways that are part of an accessible route as gangways may
periodically have a steeper slope than is permitted for a fixed ramp. The
exceptions contained in section 1003.2 of the 2010 Standards modify the
requirements of Chapter 4. For example, where the total length of a gangway or
series of gangways serving as an accessible route is 80 feet or more an
exception permits the slope on gangways to exceed the maximum slope in section
405.2. Some commenters suggested that permissible slope variations could be
reduced further by introducing a formula that ties required gangway length to
anticipated water level fluctuations. Such a formula would incorporate
predictions of tidal level changes such as those issued by the National
Oceanographic and Atmospheric Administration (NOAA) and the United States
Geologic Survey (USGS). This suggested approach would be an alternative to the
gangway length exceptions and limits in section 1003.2.1 of the 2010
Standards. These commenters noted that contemporary building materials and
techniques make gangways of longer length and alternative configurations
achievable. These commenters provided at least one example of a regional
regulatory authority using this type of formula. While this approach may be
successfully implemented and consistent with the goals of the ADA, the example
provided was applied in a highly developed area containing larger facilities.
The Department has considered that many facilities do not have sufficient
resources available to take advantage of the latest construction materials and
design innovations. Other commenters supported compliance exceptions for
facilities that are subject to extreme tidal conditions. One commenter noted
that if a facility is located in an area with limited space and extreme tidal
variations, a disproportionately long gangway might intrude into water travel
routes. The Department has considered a wide range of boating facility
characteristics including size, water surface areas, tidal fluctuations, water
conditions, variable resources, whether the facility is in a highly developed
or remote location, and other factors. The Department has determined that the
2010 Standards provide sufficient flexibility for such broad application.
Additionally, the length requirement for accessible routes in section 1003.2.1
provides an easily determinable compliance standard.
Accessible Boarding Piers. Where boarding piers are provided
at boat launch ramps, sections 235.3 and 1003.3.2 of the 2010 Standards
require that at least five percent (5%) of boarding piers, but at least one,
must be accessible.
Accessible Boat Slips. Sections 235.2 and 1003.3.1 of the
2010 Standards require that a specified number of boat slips in each
recreational boating facility meet specified accessibility standards. The
number of accessible boat slips required by the 2010 Standards is set out in a
chart in section 235.2. One accessible boat slip is required for facilities
containing 25 or fewer total slips. The number of required accessible boat
slips increases with the total number of slips at the facility. Facilities
containing more than one thousand (1000) boat slips are required to provide
twelve (12) accessible boat slips plus one for each additional one hundred
slips at the facility. One commenter asserted the need for specificity in the
requirement for dispersion of accessible slips. Section 235.2.1 of the 2010
Standards addresses dispersion and requires that boat slips "shall be
dispersed throughout the various types of boat slips provided." The commenter
was concerned that if a marina could not put accessible slips all on one pier,
it would have to reconstruct the entire facility to accommodate accessible
piers, gangways, docks and walkways. The provision permits required accessible
boat slips to be grouped together. The Department recognizes that economical
and structural feasibility may produce this result. The 2010 Standards do not
require the dispersion of the physical location of accessible boat slips.
Rather, the dispersion must be among the various types of boat slips offered
by the facility. Section 235.2.1 of the 2010 Standards specifies that if the
required number has been met, no further dispersion is required. For example,
if a facility offers five different ´types´ of boat slips but is only required
to provide three according to the table in Section 235.2, that facility is not
required to provide more than three accessible boat slips, but the three must
be varied among the five ´types´ of boat slips available at the facility.
236 and 1004 Exercise Machines and Equipment
Accessible Route to Exercise Machines and Equipment. Section
206.2.13 of the 2010 Standards requires an accessible route to serve
accessible exercise machines and equipment. Commenters raised concerns that
the requirement to provide accessible routes to serve accessible exercise
machines and equipment will be difficult for some facilities to provide,
especially some transient lodging facilities that typically locate exercise
machines and equipment in a single room. The Department believes that this
requirement is a reasonable one in new construction and alterations because
accessible exercise machines and equipment can be located so that an
accessible route can serve more than one piece of equipment.
Exercise Machines and Equipment. Section 236 of the 2010
Standards requires at least one of each type of exercise machine to meet clear
floor space requirements of section 1004.1. Types of machines are generally
defined according to the muscular groups exercised or the kind of
cardiovascular exercise provided. Several commenters were concerned that
existing facilities would have to reduce the number of available exercise
equipment and machines in order to comply with the 2010 Standards. One
commenter submitted prototype drawings showing equipment and machine layouts
with and without the required clearance specified in the 2010 Standards. The
accessible alternatives all resulted in a loss of equipment and machines.
However, because these prototype layouts included certain possibly erroneous
assumptions about the 2010 Standards, the Department wishes to clarify the
requirements. Section 1004.1 of the 2010 Standards requires a clear floor
space "positioned for transfer or for use by an individual seated in a
wheelchair" to serve at least one of each type of exercise machine and
equipment. This requirement provides the designer greater flexibility
regarding the location of the clear floor space than was employed by the
commenter who submitted prototype layouts. The 2010 Standards do not require
changes to exercise machines or equipment in order to make them more
accessible to persons with disabilities. Even where machines or equipment do
not have seats and typically are used by individuals in a standing position,
at least one of each type of machine or equipment must have a clear floor
space. Therefore, it is reasonable to assume that persons with disabilities
wishing to use this type of machine or equipment can stand or walk, even if
they use wheelchairs much of the time. As indicated in Advisory 1004.1, "the
position of the clear floor space may vary greatly depending on the use of the
equipment or machine." Where exercise equipment or machines require users to
stand on them, the clear floor space need not be located parallel to the
length of the machine or equipment in order to provide a lateral
seat-to-platform transfer. It is permissible to locate the clear floor space
for such machines or equipment in the aisle behind the device and to overlap
the clear floor space and the accessible route. Commenters were divided in
response to the requirement for accessible exercise machines and equipment.
Some supported requirements for accessible machines and equipment; others
urged the Department not to require accessible machines and equipment because
of the costs involved. The Department believes that the requirement strikes an
appropriate balance in ensuring that persons with disabilities, particularly
those who use wheelchairs, will have the opportunity to use the exercise
equipment. Providing access to exercise machines and equipment recognizes the
need and desires of individuals with disabilities to have the same opportunity
as other patrons to enjoy the advantages of exercise and maintaining health.
237 and 1005 Fishing Piers and Platforms
Accessible Route. Sections 206.2.14 and 1005.1 of the 2010
Standards require an accessible route to each accessible fishing pier and
platform. The exceptions described under Recreational Boating above also apply
to gangways and floating piers. All commenters supported the requirements for
accessible routes to fishing piers and platforms.
Accessible Fishing Piers and Platforms. Sections 237 and 1005
of the 2010 Standards require at least twenty-five percent (25%) of railings,
guards, or handrails (if provided) to be at a 34-inch maximum height (so that
a person seated in a wheelchair can cast a fishing line over the railing) and
to be located in a variety of locations on the fishing pier or platform to
give people a variety of locations to fish. An exception allows a guard
required to comply with the IBC to have a height greater than 34 inches. If
railings, guards, or handrails are provided, accessible edge protection and
clear floor or ground space at accessible railings are required. Additionally,
at least one turning space complying with section 304.3 of the 2010 Standards
is required to be provided on fishing piers and platforms. Commenters
expressed concerns about the provision for fishing piers and platforms at the
exception in section 1005.2.1 of the 2010 Standards that allows a maximum
height of 42 inches for a guard when the pier or platform is covered by the
IBC. Two commenters stated that allowing a 42-inch guard or railing height for
facilities covered by another building code would be difficult to enforce.
They also thought that this would hinder access for persons with disabilities
because the railing height would be too high for a person seated in a
wheelchair to reach over with their fishing pole in order to fish. The
Department understands these concerns but believes that the railing height
exception is necessary in order to avoid confusion resulting from conflicting
accessibility requirements, and therefore has retained this exception.
238 and 1006 Golf Facilities
Accessible Route. Sections 206.2.15, 1006.2, and 1006.3 of
the 2010 Standards require an accessible route to connect all accessible
elements within the boundary of the golf course and, in addition, to connect
golf car rental areas, bag drop areas, teeing grounds, putting greens, and
weather shelters. An accessible route also is required to connect any practice
putting greens, practice teeing grounds, and teeing stations at driving ranges
that are required to be accessible. An exception permits the accessible route
requirements to be met, within the boundaries of the golf course, by providing
a "golf car passage" (the path typically used by golf cars) if specifications
for width and curb cuts are met. Most commenters expressed the general
viewpoint that nearly all golf courses provide golf cars and have either
well-defined paths or permit the cars to drive on the course where paths are
not present, and thus meet the accessible route requirement. The Department
received many comments requesting clarification of the term "golf car
passage." Some commenters recommended additional regulatory language
specifying that an exception from a pedestrian route requirement should be
allowed only when a golf car passage provides unobstructed access onto the
teeing ground, putting green, or other accessible element of the course so
that an accessible golf car can have full access to those elements. These
commenters cautioned that full and equal access would not be provided if a
golfer were required to navigate a steep slope up or down a hill or a flight
of stairs in order to get to the teeing ground, putting green, or other
accessible element of the course. Conversely, another commenter requesting
clarification of the term "golf car passage" argued that golf courses
typically do not provide golf car paths or pedestrian paths up to actual tee
grounds or greens, many of which are higher or lower than the car path. This
commenter argued that if golf car passages were required to extend onto teeing
grounds and greens in order to qualify for an exception, then some golf
courses would have to substantially regrade teeing grounds and greens at a
high cost. Some commenters argued that older golf courses, small nine-hole
courses, and executive courses that do not have golf car paths would be unable
to comply with the accessible route requirements because of the excessive cost
involved. A commenter noted that, for those older courses that have not yet
created an accessible pedestrian route or golf car passage, the costs and
impacts to do so should be considered. A commenter argued that an accessible
route should not be required where natural terrain makes it infeasible to
create an accessible route. Some commenters cautioned that the 2010 Standards
would jeopardize the integrity of golf course designs that utilize natural
terrain elements and elevation changes to set up shots and create challenging
golf holes. The Department has given careful consideration to the comments and
has decided to adopt the 2010 Standards requiring that at least one accessible
route connect accessible elements and spaces within the boundary of the golf
course including teeing grounds, putting greens, and weather shelters, with an
exception provided that golf car passages shall be permitted to be used for
all or part of required accessible routes. In response to requests for
clarification of the term "golf car passage," the Department points out that
golf car passage is merely a pathway on which a motorized golf car can operate
and includes identified or paved paths, teeing grounds, fairways, putting
greens, and other areas of the course. Golf cars cannot traverse steps and
exceedingly steep slopes. A nine-hole golf course or an executive golf course
that lacks an identified golf car path but provides golf car passage to teeing
grounds, putting greens, and other elements throughout the course may utilize
the exception for all or part of the accessible pedestrian route. The
exception in section 206.2.15 of the 2010 Standards does not exempt golf
courses from their obligation to provide access to necessary elements of the
golf course; rather, the exception allows a golf course to use a golf car
passage for part or all of the accessible pedestrian route to ensure that
persons with mobility disabilities can fully and equally participate in the
recreational activity of playing golf.
Accessible Teeing Grounds, Putting Greens, and Weather Shelters. Sections 238.2 and 1006.4 of the 2010 Standards require that golf cars be
able to enter and exit each putting green and weather shelter. Where two
teeing grounds are provided, the forward teeing ground is required to be
accessible (golf car can enter and exit). Where three or more teeing grounds
are provided, at least two, including the forward teeing ground, must be
accessible. A commenter supported requirements for teeing grounds,
particularly requirements for accessible teeing grounds, noting that
accessible teeing grounds are essential to the full and equal enjoyment of the
golfing experience. A commenter recommended that existing golf courses be
required to provide access to only one teeing ground per hole. The majority of
commenters reported that most public and private golf courses already provide
golf car passage to teeing grounds and greens. The Department has decided that
it is reasonable to maintain the requirement. The 2010 Standards provide an
exception for existing golf courses with three or more teeing grounds not to
provide golf car passage to the forward teeing ground where terrain makes such
passage infeasible. Section 1006.3.2 of the 2010 Standards requires that where
curbs or other constructed barriers prevent golf cars from entering a fairway,
openings 60 inches wide minimum shall be provided at intervals not to exceed
75 yards. A commenter disagreed with the requirement that openings 60 inches
wide minimum be installed at least every 75 yards, arguing that a maximum
spacing of 75 yards may not allow enough flexibility for terrain and hazard
placements. To resolve this problem, the commenter recommended that the
standards be modified to require that each golf car passage include one
60-inch wide opening for an accessible golf car to reach the tee, and that one
opening be provided where necessary for an accessible golf car to reach a
green. The requirement for openings where curbs or other constructed barriers
may otherwise prevent golf cars from entering a fairway allows the distance
between openings to be less than every 75 yards. Therefore, the Department
believes that the language in section 1006.3.2 of the 2010 Standards allows
appropriate flexibility. Where a paved path with curbs or other constructed
barrier exists, the Department believes that it is essential that openings be
provided to enable golf car passages to access teeing grounds, fairways and
putting greens, and other required elements. Golf car passage is not
restricted to a paved path with curbs. Golf car passage also includes
fairways, teeing grounds, putting greens, and other areas on which golf cars
operate.
Accessible Practice Putting Greens, Practice Teeing Grounds, and Teeing
Stations at Driving Ranges.
Section 238.3 of the 2010 Standards requires that five percent (5%) but at
least one of each of practice putting greens, practice teeing grounds, and
teeing stations at driving ranges must permit golf cars to enter and exit.
239 and 1007 Miniature Golf Facilities
Accessible Route to Miniature Golf Course Holes. Sections
206.2.16, 239.3, and 1007.2 of the 2010 Standards require an accessible route
to connect accessible miniature golf course holes and the last accessible hole
on the course directly to the course entrance or exit. Accessible holes are
required to be consecutive with an exception permitting one break in the
sequence of consecutive holes provided that the last hole on the miniature
golf course is the last hole in the sequence. Many commenters supported
expanding the exception from one to multiple breaks in the sequence of
accessible holes. One commenter noted that permitting accessible holes with
breaks in the sequence would enable customers with disabilities to enjoy the
landscaping, water and theme elements of the miniature golf course. Another
commenter wrote in favor of allowing multiple breaks in accessible holes with
a connecting accessible route. Other commenters objected to allowing multiple
breaks in the sequence of miniature golf holes. Commenters opposed to this
change argued that allowing any breaks in the sequence of accessible holes at
a miniature golf course would disrupt the flow of play for persons with
disabilities and create a less socially integrated experience. A commenter
noted that multiple breaks in sequence would not necessarily guarantee the
provision of access to holes that are most representative of those with
landscaping, water elements, or a fantasy-like experience. The Department has
decided to retain the exception without change. Comments did not provide a
sufficient basis on which to conclude that allowing multiple breaks in the
sequence of accessible holes would necessarily increase integration of
accessible holes with unique features of miniature golf courses. Some designs
of accessible holes with multiple breaks in the sequence might provide
equivalent facilitation where persons with disabilities gain access to
landscaping, water or theme elements not otherwise represented in a
consecutive configuration of accessible holes. A factor that might contribute
to equivalent facilitation would be an accessible route designed to bring
persons with disabilities to a unique feature, such as a waterfall, that would
otherwise not be served by an accessible route connecting consecutive
accessible holes. Specified exceptions are permitted for accessible route
requirements when located on the playing surfaces near holes.
Accessible Miniature Golf Course Holes. Sections 239.2 and
1007.3 of the 2010 Standards require at least fifty percent (50%) of golf
holes on miniature golf courses to be accessible, including providing a clear
floor or ground space that is 48 inches minimum by 60 inches minimum with
slopes not steeper than 1:48 at the start of play.
240 and 1008 Play Areas
Section 240 of the 2010 Standards provides scoping for play areas and section
1008 provides technical requirements for play areas. Section 240.1 of the 2010
Standards sets requirements for play areas for children ages 2 and over and
covers separate play areas within a site for specific age groups. Section
240.1 also provides four exceptions to the requirements that apply to family
child care facilities, relocation of existing play components in existing play
areas, amusement attractions, and alterations to play components where the
ground surface is not altered.
Ground Surfaces. Section 1008.2.6 of the 2010 Standards
provides technical requirements for accessible ground surfaces for play areas
on accessible routes, clear floor or ground spaces, and turning spaces. These
ground surfaces must follow special rules, incorporated by reference from
nationally recognized standards for accessibility and safety in play areas,
including those issued by the American Society for Testing and Materials
(ASTM). A commenter recommended that the Department closely examine the
requirements for ground surfaces at play areas. The Department is aware that
there is an ongoing controversy about play area ground surfaces arising from a
concern that some surfaces that meet the ASTM requirements at the time of
installation will become inaccessible if they do not receive constant
maintenance. The Access Board is also aware of this issue and is working to
develop a portable field test that will provide more relevant information on
installed play surfaces. The Department would caution covered entities
selecting among the ground surfacing materials that comply with the ASTM
requirements that they must anticipate the maintenance costs that will be
associated with some of the products. Permitting a surface to deteriorate so
that it does not meet the 2010 Standards would be an independent violation of
the Department´s ADA regulations.
Accessible Route to Play Components. Section 206.2.17 of the
2010 Standards provides scoping requirements for accessible routes to ground
level and elevated play components and to soft contained play structures.
Sections 240.2 and 1008 of the 2010 Standards require that accessible routes
be provided for play components. The accessible route must connect to at least
one ground level play component of each different type provided (e.g., for
different experiences such as rocking, swinging, climbing, spinning, and
sliding). Table 240.2.1.2 sets requirements for the number and types of ground
level play components required to be on accessible routes. When elevated play
components are provided, an accessible route must connect at least fifty
percent (50%) of the elevated play components. Section 240.2.1.2, provides an
exception to the requirements for ground level play components if at least
fifty percent (50%) of the elevated play components are connected by a ramp
and at least three of the elevated play components connected by the ramp are
different types of play components. The technical requirements at section 1008
include provisions where if three or fewer entry points are provided to a soft
contained play structure, then at least one entry point must be on an
accessible route. In addition, where four or more entry points are provided to
a soft contained play structure, then at least two entry points must be served
by an accessible route. If elevated play components are provided, fifty
percent (50%) of the elevated components are required to be accessible. Where
20 or more elevated play components are provided, at least twenty five percent
(25%) will have to be connected by a ramp. The remaining play components are
permitted to be connected by a transfer system. Where less than 20 elevated
play components are provided, a transfer system is permitted in lieu of a
ramp. A commenter noted that the 2010 Standards allow for the provision of
transfer steps to elevated play structures based on the number of elevated
play activities, but asserted that transfer steps have not been documented as
an effective means of access. The 2010 Standards recognize that play
structures are designed to provide unique experiences and opportunities for
children. The 2010 Standards provide for play components that are accessible
to children who cannot transfer from their wheelchair, but they also provide
opportunities for children who are able to transfer. Children often interact
with their environment in ways that would be considered inappropriate for
adults. Crawling and climbing, for example, are integral parts of the play
experience for young children. Permitting the use of transfer platforms in
play structures provides some flexibility for creative playground design.
Accessible Play Components. Accessible play components are
required to be on accessible routes, including elevated play components that
are required to be connected by ramps. These play components must also comply
with other accessibility requirements, including specifications for clear
floor space and seat heights (where provided). A commenter expressed concerns
that the general requirements of section 240.2.1 of the 2010 Standards and the
advisory accompanying section 240.2.1 conflict. The comment asserts that
section 240.2.1 of the 2010 Standards provides that the only requirement for
integration of equipment is where there are two or more required ground level
play components, while the advisory appears to suggest that all accessible
components must be integrated. The commenter misinterprets the requirement.
The ADA mandates that persons with disabilities be able to participate in
programs or activities in the most integrated setting appropriate to their
needs. Therefore, all accessible play components must be integrated into the
general playground setting. Section 240.2.1 of the 2010 Standards specifies
that where there is more than one accessible ground level play component, the
components must be both dispersed and integrated.
241 and 612 Saunas and Steam Rooms
Section 241 of the 2010 Standards sets scoping for saunas and steam rooms and
section 612 sets technical requirements including providing accessible turning
space and an accessible bench. Doors are not permitted to swing into the clear
floor or ground space for the accessible bench. The exception in section 612.2
of the 2010 Standards permits a readily removable bench to obstruct the
required wheelchair turning space and the required clear floor or ground
space. Where they are provided in clusters, five percent (5%) but at least one
sauna or steam room in each cluster must be accessible. Commenters raised
concerns that the safety of individuals with disabilities outweighs the
usefulness in providing accessible saunas and steam rooms. The Department
believes that there is an element of risk in many activities available to the
general public. One of the major tenets of the ADA is that individuals with
disabilities should have the same opportunities as other persons to decide
what risks to take. It is not appropriate for covered entities to prejudge the
abilities of persons with disabilities.
242 and 1009 Swimming Pools, Wading Pools, and Spas
Accessible Means of Entry to Pools. Section 242 of the 2010
Standards requires at least two accessible means of entry for larger pools
(300 or more linear feet) and at least one accessible entry for smaller pools.
This section requires that at least one entry will have to be a sloped entry
or a pool lift; the other could be a sloped entry, pool lift, a transfer wall,
or a transfer system (technical specifications for each entry type are
included at section 1009). Many commenters supported the scoping and technical
requirements for swimming pools. Other commenters stated that the cost of
requiring facilities to immediately purchase a pool lift for each indoor and
outdoor swimming pool would be very significant especially considering the
large number of swimming pools at lodging facilities. One commenter requested
that the Department clarify what would be an "alteration" to a swimming pool
that would trigger the obligation to comply with the accessible means of entry
in the 2010 Standards. Alterations are covered by section 202.3 of the 2010
Standards and the definition of "alteration" is provided at section 106.5. A
physical change to a swimming pool which affects or could affect the usability
of the pool is considered to be an alteration. Changes to the mechanical and
electrical systems, such as filtration and chlorination systems, are not
alterations. Exception 2 to section 202.3 permits an altered swimming pool to
comply with applicable requirements to the maximum extent feasible if full
compliance is technically infeasible. "Technically infeasible" is also defined
in section 106.5 of the 2010 Standards. The Department also received comments
suggesting that it is not appropriate to require two accessible means of entry
to wave pools, lazy rivers, sand bottom pools, and other water amusements
where there is only one point of entry. Exception 2 of Section 242.2 of the
2010 Standards exempts pools of this type from having to provide more than one
accessible means of entry provided that the one accessible means of entry is a
swimming pool lift compliant with section 1009.2, a sloped entry compliant
with section 1009.3, or a transfer system compliant with section 1009.5 of the
2010 Standards.
Accessible Means of Entry to Wading Pools. Sections 242.3 and
1009.3 of the 2010 Standards require that at least one sloped means of entry
is required into the deepest part of each wading pool.
Accessible Means of Entry to Spas. Sections 242.4 and 1009.2,
1009.4, and 1009.5 of the 2010 Standards require spas to meet accessibility
requirements, including an accessible means of entry. Where spas are provided
in clusters, five percent (5%) but at least one spa in each cluster must be
accessible. A pool lift, a transfer wall, or a transfer system will be
permitted to provide the required accessible means of entry.
243 Shooting Facilities with Firing Positions
Sections 243 and 1010 of the 2010 Standards require an accessible turning
space for each different type of firing position at a shooting facility if
designed and constructed on a site. Where firing positions are provided in
clusters, five percent (5%), but at least one position of each type in each
cluster must be accessible.
Additional Technical Requirements
302.1 Floor or Ground Surfaces
Both section 4.5.1 of the 1991 Standards and section 302.2 of the 2010
Standards require that floor or ground surfaces along accessible routes and in
accessible rooms and spaces be stable, firm, slip-resistant, and comply with
either section 4.5 in the case of the 1991 Standards or section 302 in the
case of the 2010 Standards. Commenters recommended that the Department apply
an ASTM Standard (with modifications) to assess whether a floor surface is
"slip resistant" as required by section 302.1 of the 2010 Standards. The
Department declines to accept this recommendation since, currently, there is
no generally accepted test method for the slip-resistance of all walking
surfaces under all conditions.
304 Turning Space
Section 4.2.3 of the 1991 Standards and Section 304.3 of the 2010 Standards
allow turning space to be either a circular space or a T-shaped space. Section
304.3 permits turning space to include knee and toe clearance complying with
section 306. Section 4.2.3 of the 1991 Standards did not specifically permit
turning space to include knee and toe clearance. Commenters urged the
Department to retain the turning space requirement, but exclude knee and toe
clearance from being permitted as part of this space. They argued that
wheelchairs and other mobility devices are becoming larger and that more
individuals with disabilities are using electric three and four-wheeled
scooters which cannot utilize knee clearance. The Department recognizes that
the technical specifications for T-shaped and circular turning spaces in the
1991 and 2010 Standards, which are based on manual wheelchair dimensions, may
not adequately meet the needs of individuals using larger electric scooters.
However, there is no consensus about the appropriate dimension on which to
base revised requirements. The Access Board is conducting research to study
this issue in order to determine if new requirements are warranted. For more
information, see the Access Board´s website at
http://www.access-board.gov/research/current-projects.htm#suny. The Department
plans to wait for the results of this study and action by the Access Board
before considering any changes to the Department´s rules. Covered entities may
wish to consider providing more than the minimum amount of turning space in
confined spaces where a turn will be required. Appendix section A4.2.3 and
Fig. A2 of the 1991 Standards provide guidance on additional space for making
a smooth turn without bumping into surrounding objects.
404 Doors, Doorways, and Gates
A
utomatic Door Break Out Openings. The 1991 Standards do not
contain any technical requirement for automatic door break out openings. The
2010 Standards at sections 404.1, 404.3, 404.3.1, and 404.3.6 require
automatic doors that are part of a means of egress and that do not have
standby power to have a 32-inch minimum clear break out opening when operated
in emergency mode. The minimum clear opening width for automatic doors is
measured with all leaves in the open position. Automatic bi-parting doors or
pairs of swinging doors that provide a 32-inch minimum clear break out opening
in emergency mode when both leaves are opened manually meet the technical
requirement. Section 404.3.6 of the 2010 Standards includes an exception that
exempts automatic doors from the technical requirement for break out openings
when accessible manual swinging doors serve the same means of egress.
Maneuvering Clearance or Standby Power for Automatic Doors.
Section 4.13.6 of the 1991 Standards does not require maneuvering clearance at
automatic doors. Section 404.3.2 of the 2010 Standards requires automatic
doors that serve as an accessible means of egress to either provide
maneuvering clearance or to have standby power to operate the door in
emergencies. This provision has limited application and will affect, among
others, in-swinging automatic doors that serve small spaces. Commenters urged
the Department to reconsider provisions that would require maneuvering
clearance or standby power for automatic doors. They assert that these
requirements would impose unreasonable financial and administrative burdens on
all covered entities, particularly smaller entities. The Department declines
to change these provisions because they are fundamental life-safety issues.
The requirement applies only to doors that are part of a means of egress that
must be accessible in an emergency. If an emergency-related power failure
prevents the operation of the automatic door, a person with a disability could
be trapped unless there is either adequate maneuvering room to open the door
manually or a back-up power source.
Thresholds at Doorways. The 1991 Standards, at section
4.13.8, require the height of thresholds at doorways not to exceed 1/2 inch
and thresholds at exterior sliding doors not to exceed 3/4 inch. Sections
404.1 and 404.2.5 of the 2010 Standards require the height of thresholds at
all doorways that are part of an accessible route not to exceed 1/2 inch. The
1991 Standards and the 2010 Standards require raised thresholds that exceed ¼
inch in height to be beveled on each side with a slope not steeper than 1:2.
The 2010 Standards include an exception that exempts existing and altered
thresholds that do not exceed 3/4 inch in height and are beveled on each side
from the requirement.
505 Handrails
The 2010 Standards add a new technical requirement at section 406.3 for
handrails along walking surfaces. The 1991 Standards, at sections 4.8.5,
4.9.4, and 4.26, and the 2010 Standards, at section 505, contain technical
requirements for handrails. The 2010 Standards provide more flexibility than
the 1991 Standards as follows:
-
Section 4.26.4 of the 1991 Standards requires handrail gripping surfaces
to have edges with a minimum radius of 1/8 inch. Section 505.8 of the 2010
Standards requires handrail gripping surfaces to have rounded edges.
-
Section 4.26.2 of the 1991 Standards requires handrail gripping surfaces
to have a diameter of 1 ¼ inches to 1 1/2 inches, or to provide an
equivalent gripping surface. Section 505.7 of the 2010 Standards requires
handrail gripping surfaces with a circular cross section to have an
outside diameter of 1 ¼ inches to 2 inches. Handrail gripping surfaces
with a non-circular cross section must have a perimeter dimension of 4
inches to 6 ¼ inches, and a cross section dimension of 2 ¼ inches maximum.
-
Sections 4.8.5 and 4.9.4 of the 1991 Standards require handrail gripping
surfaces to be continuous, and to be uninterrupted by newel posts, other
construction elements, or obstructions. Section 505.3 of the 2010
Standards sets technical requirements for continuity of gripping surfaces.
Section 505.6 requires handrail gripping surfaces to be continuous along
their length and not to be obstructed along their tops or sides. The
bottoms of handrail gripping surfaces must not be obstructed for more than
twenty percent (20%) of their length. Where provided, horizontal
projections must occur at least 1 1/2 inches below the bottom of the
handrail gripping surface. An exception permits the distance between the
horizontal projections and the bottom of the gripping surface to be
reduced by 1/8 inch for each 1/2 inch of additional handrail perimeter
dimension that exceeds 4 inches.
-
Section 4.9.4 of the 1991 Standards requires handrails at the bottom of
stairs to continue to slope for a distance of the width of one tread
beyond the bottom riser nosing and to further extend horizontally at least
12 inches. Section 505.10 of the 2010 Standards requires handrails at the
bottom of stairs to extend at the slope of the stair flight for a
horizontal distance at least equal to one tread depth beyond the last
riser nosing. Section 4.1.6(3) of the 1991 Standards has a special
technical provision for alterations to existing facilities that exempts
handrails at the top and bottom of ramps and stairs from providing full
extensions where it will be hazardous due to plan configuration. Section
505.10 of the 2010 Standards has a similar exception that applies in
alterations.
A commenter noted that handrail extensions are currently required at the top
and bottom of stairs, but the proposed regulations do not include this
requirement, and urged the Department to retain the current requirement. Other
commenters questioned the need for the extension at the bottom of stairs.
Sections 505.10.2 and 505.10.3 of the 2010 Standards require handrail
extensions at both the top and bottom of a flight of stairs. The requirement
in the 1991 Standards that handrails extend horizontally at least 12 inches
beyond the width of one tread at the bottom of a stair was changed in the 2004
ADAAG by the Access Board in response to public comments. Existing horizontal
handrail extensions that comply with 4.9.4(2) of the 1991 Standards should
meet or exceed the requirements of the 2010 Standards. Commenters noted that
the 2010 Standards will require handrail gripping surfaces with a circular
cross section to have an outside diameter of 2 inches, and that this
requirement would impose a physical barrier to individuals with disabilities
who need the handrail for stability and support while accessing stairs. The
requirement permits an outside diameter of 1 ¼ inches to 2 inches. This range
allows flexibility in meeting the needs of individuals with disabilities and
designers and architects. The Department is not aware of any data indicating
that an outside diameter of 2 inches would pose any adverse impairment to use
by individuals with disabilities.
Handrails Along Walkways. The 1991 Standards do not contain
any technical requirement for handrails provided along walkways that are not
ramps. Section 403.6 of the 2010 Standards specifies that where handrails are
provided along walkways that are not ramps, they shall comply with certain
technical requirements. The change is expected to have minimal impact.